| 2021-08-19 07:44:32 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21070679 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M6.0.1: PLEASE PROVIDE THE OUTDOOR AIR |
| | CALCULATIONS FOR EACH USE OF SPACE ACCORDING TO FBC |
| | 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 2) SHEET M1.1.1: PLEASE IDENTIFY THE RTU FOR EACH DUCT |
| | SYSTEM ON THIS SHEET (EXAMPLE, THE MULTIPURPOSE AREA IS |
| | SERVED BY WHICH AHU? FBC 107.2.1 |
| | |
| | 3) SHEET M1.1.1: IT APPEARS THAT THE RETURN GRILLS FOR |
| | THE OFFICES AT THE SOUTH SIDE OF THE BUILDING HAVE THE |
| | SUPPLY SYMBOL, PLEASE CORRECT. FBC 107.2.1 |
| | |
| | 4) SHEET M1.1.1: NOTE 1 SENDS ME TO THE ELEVATION SHEET |
| | FOR THE LOCATION OF THE FRESH AIR LOUVER FOR AHU-1. THE |
| | ELEVATION SHEET DOES NOT SHOW THIS LOUVER. PLEASE SHOW |
| | THE LOCATION OF THIS LOUVER. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |