| 2021-08-23 15:19:36 | NEW COMMERCIAL BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | 1) DRAWING S3.1.K SHOWS WIND DESIGN 170MPH FOR RISK |
| | CATEGORY III - RISK CATEGORY III REQUIRES A WIND SPEED |
| | OF 180MPH - FBC WPB SECTION 120 |
| | 2) DRAWING A5.0.3 SHOWS ROOF SHEATHING 5/8 PLYWOOD - |
| | DRAWING A2.0.3 SHOWS ROOF SHEATHING 3/4 PLYWOOD - |
| | DRAWINGS NEED TO MATCH. |
| | 3) PLEASE PROVIDE A WALL FINISH DETAIL FOR THE SERVICE |
| | SINK AREA TO COMPLY WITH FBC 1210.2.2 (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | 4) ROOF TILE PRODUCT APPROVAL PROVIDED - PLEASE CIRCLE |
| | THE ROOFING TILE ATTACHMENT TYPE TO BE USED ON THE |
| | PRODUCT APPROVAL (ATTACHMENT TYPE WILL NEED TO MEET OR |
| | EXCEED THE REQUIRED PRESSURES). IF USING ADHESIVE |
| | PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL. |
| | 5) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR MAXIMUM |
| | DIMENSION FROM THE FINISHED FLOOR TO THE BOTTOM OF THE |
| | "REFLECTIVE SURFACE" PER FBC A603.3 |
| | 6) STORAGE ROOM ENTRY FROM THE INTERIOR OF THE BUILDING |
| | - AN ACCESSIBLE ENTRY SHOULD BE PROVIDED PER FBC |
| | A206.2.4 SPACES AND ELEMENTS. |
| | AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE |
| | BUILDING OR FACILITY ENTRANCES WITH ALL ACCESSIBLE |
| | SPACES AND ELEMENTS WITHIN THE BUILDING OR FACILITY |
| | WHICH ARE OTHERWISE CONNECTED BY A CIRCULATION PATH |
| | UNLESS EXEMPTED BY 206.2.3 EXCEPTIONS 1 THROUGH 7. |
| | 7) CORRIDOR 128 SHOWS DOORS THAT MAY BE BLOCKING THE |
| | EGRESS - 1005.7.1DOORS. |
| | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED |
| | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY |
| | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE |
| | THAN ONE-HALF. |
| | 8) PLEASE SHOW THE FLAT DECK ROOF SLOPE TO COMPLY WITH |
| | FBC 1507.13.1 |
| | 9) PLEASE SHOW THE ATTIC ACCESS TO COMPLY WITH FBC |
| | 1209.2 |
| | 10) DRAWING C1.0 SHOWS 228 PARKING SPACES - 7 |
| | ACCESSIBLE PARKING SPACES ARE REQUIRED PER FBC A TABLE |
| | 208.2 |
| | 11) CIVIL PLANS SHOW PROPERTY IN AN "X" AND "AE 14.8" - |
| | PLEASE CLEARLY SHOW THE FLOOD ZONE DELINEATION LINES - |
| | ARE ANY OF THE BUILDINGS IN THE "AE 14.8" FLOOD ZONE? |