Plan Review Notes
Plan Review Notes For Permit 21070679
Permit Number 21070679
Review Stop B
Sequence Number 1
Notes
Date Text
2021-08-23 15:19:36NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DRAWING S3.1.K SHOWS WIND DESIGN 170MPH FOR RISK
 CATEGORY III - RISK CATEGORY III REQUIRES A WIND SPEED
 OF 180MPH - FBC WPB SECTION 120
 2) DRAWING A5.0.3 SHOWS ROOF SHEATHING 5/8 PLYWOOD -
 DRAWING A2.0.3 SHOWS ROOF SHEATHING 3/4 PLYWOOD -
 DRAWINGS NEED TO MATCH.
 3) PLEASE PROVIDE A WALL FINISH DETAIL FOR THE SERVICE
 SINK AREA TO COMPLY WITH FBC 1210.2.2 (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
 4) ROOF TILE PRODUCT APPROVAL PROVIDED - PLEASE CIRCLE
 THE ROOFING TILE ATTACHMENT TYPE TO BE USED ON THE
 PRODUCT APPROVAL (ATTACHMENT TYPE WILL NEED TO MEET OR
 EXCEED THE REQUIRED PRESSURES). IF USING ADHESIVE
 PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL.
 5) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR MAXIMUM
 DIMENSION FROM THE FINISHED FLOOR TO THE BOTTOM OF THE
 "REFLECTIVE SURFACE" PER FBC A603.3
 6) STORAGE ROOM ENTRY FROM THE INTERIOR OF THE BUILDING
 - AN ACCESSIBLE ENTRY SHOULD BE PROVIDED PER FBC
 A206.2.4 SPACES AND ELEMENTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE
 BUILDING OR FACILITY ENTRANCES WITH ALL ACCESSIBLE
 SPACES AND ELEMENTS WITHIN THE BUILDING OR FACILITY
 WHICH ARE OTHERWISE CONNECTED BY A CIRCULATION PATH
 UNLESS EXEMPTED BY 206.2.3 EXCEPTIONS 1 THROUGH 7.
 7) CORRIDOR 128 SHOWS DOORS THAT MAY BE BLOCKING THE
 EGRESS - 1005.7.1DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
 8) PLEASE SHOW THE FLAT DECK ROOF SLOPE TO COMPLY WITH
 FBC 1507.13.1
 9) PLEASE SHOW THE ATTIC ACCESS TO COMPLY WITH FBC
 1209.2
 10) DRAWING C1.0 SHOWS 228 PARKING SPACES - 7
 ACCESSIBLE PARKING SPACES ARE REQUIRED PER FBC A TABLE
 208.2
 11) CIVIL PLANS SHOW PROPERTY IN AN "X" AND "AE 14.8" -
 PLEASE CLEARLY SHOW THE FLOOD ZONE DELINEATION LINES -
 ARE ANY OF THE BUILDINGS IN THE "AE 14.8" FLOOD ZONE?