Plan Review Notes
Plan Review Notes For Permit 21070678
Permit Number 21070678
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-23 13:29:571) SHT. LS.1.1 - THE CODE DATA TABLE LISTS THE SQUARE
 FOOTAGE AS 3,712 SQUARE FEET BUT THE OCCUPANT LOAD
 TABLE LISTS THE TOTAL SQUARE FOOTAGE AS 2,163 SQUARE
 FEET. CLARIFY.
 2) SHT. A9.0.1 - DETAIL #2 - THE REAR WALL GRAB BAR
 SHALL BE LOCATED PER FBC-ACCESS. SEC.604.5.2 AND FIGURE
 604.5.2. SHOW THE DIMENSIONS ON THE PLAN.
 3) SHT. A10.1.1 - DETAIL #1 - THE FRONT OF THE HIGHER
 OF THE RIM OR COUNTER SURFACE SHALL BE LOCATED 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER
 FBC-ACCESS. SEC.606.3.
 4) SHT. SP.0.1 REFERS TO DRAWING SP.0.2. THERE IS NO
 SUCH DRAWING IN THIS SUBMITTAL. CLARIFY..
 5) THE PLUMBING SHEETS REFER TO CIVIL DRAWINGS. THERE
 ARE NO CIVIL DRAWINGS IN THIS SUBMITTAL. CLARIFY.
 6) DOWNSPOUTS SHALL DISCHARGE A MINIMUM OF ONE FOOT
 FROM THE STRUCTURE SIDEWALL PER FBC-BUILDING
 SEC.1503.7. SHOW THIS ON THE PLANS.
 7) SHOW THE WALL FINISH AROUND THE MOP SINK. THE WALL
 FINISH SHALL COMPLY WITH FBC-BUILDING SEC. 1210.2.2.
 NOTE: EPOXY PAINT ON DRYWALL DOES NOT MEET THE INTENT
 OF THIS SECTION.
 8) SHT. P.7.0.1 - THE WATER RISER SHOWS HOT AND COLD
 WATER TO A HOSE BIBB. CLARIFY.
 9) CLARIFY THE ITEMS LABELED AS PWC-1 AND CS-1 ON THE
 WATER RISER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  