| 2021-08-19 06:45:40 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21070678 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M6.0.1: PLEASE PROVIDE THE OUTDOOR AIR | | | CALCULATIONS FOR EACH USE OF SPACE IN THIS BUILDING | | | ACCORDING TO FBC 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THE | | | DS UNITS (PB-1, PB-2, PB-3) DOES NOT SHOW THE ROLL UP | | | DOOR FOR THE ENVELOPE LOADS. PLEASE EXPLAIN THE USE OF | | | THESE ROOMS. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|