Plan Review Notes
Plan Review Notes For Permit 21070678
Permit Number 21070678
Review Stop B
Sequence Number 1
Notes
Date Text
2021-08-23 11:23:57NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DRAWING S2.1.P SHOWS WIND DESIGN 170MPH FOR RISK
 CATEGORY III - RISK CATEGORY III REQUIRES A WIND SPEED
 OF 180MPH - FBC WPB SECTION 120
 2) DRAWING S1.2.P SHOWS ROOF SHEATHING 5/8 PLYWOOD -
 DRAWING A2.0.2 SHOWS ROOF SHEATHING 3/4 PLYWOOD -
 DRAWINGS NEED TO MATCH.
 3) PLEASE PROVIDE A WALL FINISH SCHEDULE.
 4) ROOF TILE PRODUCT APPROVAL PROVIDED - PLEASE CIRCLE
 THE ROOFING TILE ATTACHMENT TYPE TO BE USED ON THE
 PRODUCT APPROVAL (ATTACHMENT TYPE WILL NEED TO MEET OR
 EXCEED THE REQUIRED PRESSURES). IF USING ADHESIVE
 PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL.
 5) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET REAR
 GRAB BAR DIMENSIONS FROM THE CENTER OF THE TOILET PER
 FBC A604.5.2
 6) A DEMO PLAN HAS BEEN PROVIDED - BUILDING DEMO NEEDS
 TO BE ON A SEPARATE BUILDING DEMO PERMIT - PLEASE
 ACKNOWLEDGE THIS.
 7) PLEASE SHOW THE ATTIC ACCESS OPENING TO COMPLY WITH
 FBC 1209.2
 8) PLEASE SHOW THE DRAFT STOPPING IN THE ATTIC SPACE TO
 COMPLY WITH FBC 718.4.3
 9) CIVIL PLANS SHOW PROPERTY IN AN "X" AND "AE 14.8" -
 PLEASE CLEARLY SHOW THE FLOOD ZONE DELINEATION LINES -
 ARE ANY OF THE BUILDINGS IN THE "AE 14.8" FLOOD ZONE?