Plan Review Notes
Plan Review Notes For Permit 21070675
Permit Number 21070675
Review Stop P
Sequence Number 2
Notes
Date Text
2021-10-08 10:07:282ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21070675
 10/8/2021
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITONAL NOTES IN CAP
 LETTERS.
  
 3C) FAILED. ALS.1.0: DRINKING FOUNTAINS ARE REQUIRED
 FIXTURES FOR MERCANTILE, BUSINESS, AND STORAGE
 OCCUPANCIES. EXCEPTION 410.4 IS CALLED OUT IN THE TABLE
 HOWEVER SECTION 410.4 SUBSTITUTION OF DRINKING WATER IN
 A CONTAINER FREE OF CHARGE APPLIES ONLY TO THE
 RESTAURANT AREA. THE PLUMBING FIXTURE SCHEDULE
 INDICATES DRINKING FOUNTAIN EXCEPTION 410.4 ONLY FOR
 THE ASSEMBLY OCCUPANCIES. PLEASE PROVIDE THE REQUIRED
 FIXTURES PER THE COMMENT. BASED ON THE DRAWINGS
 SUBMITTED, IT APPEARS THAT THE PUBLIC CAN ACCESS THE
 SEPARATE MERCANTILE BUILDING (GOLF SHOP) WITHOUT HAVING
 TO ENTER THE RESTAURANT. HOW WOULD A PATRON OF THE GOLF
 SHOP THEN BE SUPPLIED WITH DRINKING WATER FROM THE
 RESTAURANT? THE SAME QUESTION APPLIES TO THE PUBLIC AND
 EMPLOYEES WHO ARE ACCESSING AND OCCUPYING THE LOWER
 LEVEL. THE CADDY LOUNGE AND THE BEVERAGE STATION ARE
 NOT CLASSIFIED AS RESTAURANTS.
  
 4) FAILED. A9.01: MISSING ACCESSIBLE PLUMBING FIXTURE
 DETAILS PER FBC ACC: SEE NOTES BELOW.
 A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE WATER CLOSETS- SECTION 604.3. DEPTH DIMENSIONS NOT
 SHOWN
 C) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3.
 DIAMETER MEASUREMENT NOT PROVIDED.
 E) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. REQUIRED OVERALL MINIMUM
 LENGTHS NOT INDICATED PER THE FIGURES.
 I) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR
 A FORWARD OR PARALLEL APPROACH TO THE SINK IN THE
 LOUNGE- 606.2. KNEE AND TOE CLEARANCES FOR FORWARD
 APPROACHES- SECTION 606.2. THE COMMENT WAS FOR THE
 CADDY LOUNG DETAIL SHOWN IN DETAIL 3. THE RESPONSE
 REFERS TO THE FOUNDER?S LOUNGE SINK.
 J) FAILED. LOUNGE SINK HEIGHT FROM THE FINISHED FLOOR
 TO THE RIM OF THE SINK- 606.3. NOTE- THE DRAWING SHOWS
 THE MEASUREMENT TO THE COUNTER. DETAIL 3 SHOWS
 MEASUREMENT TO THE COUNTER NOT THE SINK.
 K) FAILED. REACH RANGES AND OPERABLE PARTS FOR THE
 COFFEE MAKER- 308. PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS TO VERY COMPLIANCE. A DEFERRED SUBMITTAL
 IS ACCEPTABLE. PLACE A NOTE THAT COMPLIANCE WITH
 SECTIONS 308 & 309 WILL BE MET.
  
 5) FAILED. A9.1.2: MISSING ACCESSIBLE PLUMBING FIXTURE
 DETAILS PER FBC ACC: SEE NOTES BELOW.
 A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR
 THE WATER CLOSET- SECTION 604.3. DIMENSIONS NOT
 PROVIDED.
 B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR
 THE LAVATORY- SECTION 606.2. DIMENSIONS NOT PROVIDED.
 C) FAILED. TURNING SPACE DIAMETER- SECTION 304.3.
 DIAMETER MEASUREMENT NOT PROVIDED.
 E) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. REQUIRED OVERALL MINIMUM
 LENGTHS NOT INDICATED PER THE FIGURES.
 F) FAILED. LOCATIONS OF THE WATER CLOSET FLUSH CONTROL-
 SECTION 604.6. NOT PROVIDED.
 G) FAILED. CENTERLINE OF THE TOILET PAPER DISPENSER
 MEASURED FROM THE FRONT OF THE WATER CLOSET- SECTION
 AND FIGURE 604.7. NOT PROVIDED.
 H) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORY-
 SECTION 606.2. NOT PROVIDED. IF USING A TYPICAL FIGURE
 PLEASE PROVIDE IT ON THE PLAN OR REFERENCE THE SHEET IT
 IS ON.
  
 6) FAILED. A9.1.3: MISSING ACCESSIBLE PLUMBING FIXTURE
 DETAILS PER FBC ACC: SEE NOTES BELOW.
 A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR
 THE WATER CLOSET- SECTION 604.3. DIMENSIONS NOT
 PROVIDED. THE DOOR IS SWINGING INTO THE CLEAR FLOOR
 SPACE FOR THE WATER CLOSET. THE 30X48-INCH CLEAR FLOOR
 SPACE INSERTED IS NOT BEYOND THE ARC OF THE DOOR SWING-
 SECTION 603.2.3 (2).
 B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR
 THE LAVATORY- SECTION 606.2. DIMENSIONS NOT PROVIDED.
 C) FAILED. TURNING SPACE DIAMETER- SECTION 304.3.
 DIAMETER MEASUREMENT NOT PROVIDED.
 E) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. REQUIRED OVERALL MINIMUM
 LENGTHS NOT INDICATED PER THE FIGURES.
 F) FAILED. LOCATIONS OF THE WATER CLOSET FLUSH CONTROL-
 SECTION 604.6. NOT PROVIDED.
 G) FAILED. CENTERLINE OF THE TOILET PAPER DISPENSER
 MEASURED FROM THE FRONT OF THE WATER CLOSET- SECTION
 AND FIGURE 604.7. NOT PROVIDED.
 H) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORY-
 SECTION 606.2. NOT PROVIDED. IF USING A TYPICAL FIGURE
 PLEASE PROVIDE IT ON THE PLAN OR REFERENCE THE SHEET IT
 IS ON.
 I) FAILED. CLEAR INSIDE DIMENSIONS FOR THE ACCESSIBLE
 SHOWER- SECTION 608.2.1. WIDTH MEASUREMENT NOT
 PROVIDED.
 J) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE ACCESSIBLE SHOWER- 608.2.1. DIMENSIONS NOT
 PROVIDED.
 K) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE ACCESSIBLE SHOWER 608.3 AND 608.3.1.
 REQUIRED OVERALL MINIMUM LENGTHS NOT INDICATED PER THE
 FIGURES.
 L) FAILED. SHOW THE LOCATION OF THE SHOWER CONTROL AND
 SPRAY IN ACCORDANCE WITH FIGURE 608.5.1. NOT PROVIDED-
 REFER TO THE FIGURE 608.5.1.
 N) FAILED PROVIDE THE ACCESSIBLE SHOWER SEAT HEIGHT AND
 MOUNTING DETAILS- 610.3 & 610.3.2. & FIGURE 610.3.2.
 NOT PROVIDED- REFER TO THE FIGURES ABOVE.
  
 7) FAILED. A9.1.5, A9.1.6 & A9.1.7: MISSING ACCESSIBLE
 PLUMBING FIXTURE DETAILS PER FBC ACC: SEE NOTES BELOW.
 C) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3. NOT
 PROVIDED.
 E) FAILED. HEIGHTS OF THE WATER CLOSET SEATS FROM THE
 FINISHED FLOORS- SECTION 604.4. NOT PROVIDED.
 H) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. REQUIRED OVERALL MINIMUM
 LENGTHS NOT INDICATED PER THE FIGURES.
 J) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS
 MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SECTION
 AND FIGURE 604.7. NOT PROVIDED.
 K) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 606.2. NOT PROVIDED. IF USING A TYPICAL FIGURE
 PLEASE PROVIDE IT ON THE PLAN OR REFERENCE THE SHEET IT
 IS ON.
 M) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE ACCESSIBLE SHOWER- 608.3.2. GRAB BAR
 LOCATIONS AND POSITIONING DEPEND ON WHETHER A SEAT IS
 BEING INSTALLED. THE FLOOR PLAN DOES NOT SHOW A SEAT IN
 THE SHOWER, HOWEVER DETAIL 5 SHOWS A SEAT.
 N) FAILED. LOCATION OF THE SHOWER CONTROL AND SPRAY-
 608.5.2. SHOWER CONTROL LOCATIONS AND POSITIONING
 DEPEND ON WHETHER A SEAT IS BEING INSTALLED. THE FLOOR
 PLAN DOES NOT SHOW A SEAT IN THE SHOWER, HOWEVER DETAIL
 5 SHOWS A SEAT.
  
 9) FAILED. A9.1.8 & A9.1.9: MISSING ACCESSIBLE PLUMBING
 FIXTURE DETAILS PER FBC ACC: SEE NOTES BELOW.
 A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE WATER CLOSETS- SECTION 604.3. NOT PROVIDED.
 B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE LAVATORIES- SECTION 606.2. NOT PROVIDED. IF USING A
 TYPICAL FIGURE PLEASE PROVIDE IT ON THE PLAN OR
 REFERENCE THE SHEET IT IS ON.
 C) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3. NOT
 PROVIDED.
 E) FAILED. HEIGHTS OF THE WATER CLOSET SEATS FROM THE
 FINISHED FLOORS- SECTION 604.4.NOT PROVIDED.
 F) FAILED. HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER
 SURFACE FROM THE FINISHED FLOOR- SECTION 606.3. NOT
 PROVIDED. IF USING A TYPICAL FIGURE PLEASE PROVIDE IT
 ON THE PLAN OR REFERENCE THE SHEET IT IS ON.
 G) FAILED. HEIGHTS OF THE MIRRORS FROM THE FINISHED
 FLOORS TO THE REFLECTIVE SURFACES- SECTION 603.3
 H) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. REQUIRED OVERALL MINIMUM
 LENGTHS NOT INDICATED PER THE FIGURES.
 I) FAILED. LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS
 - SECTION 604.6. NOT PROVIDED.
 J) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS
 MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SECTION
 AND FIGURE 604.7. NOT PROVIDED.
 K) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 606.2. NOT PROVIDED. IF USING A TYPICAL FIGURE
 PLEASE PROVIDE IT ON THE PLAN OR REFERENCE THE SHEET IT
 IS ON.
 L) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE ACCESSIBLE SHOWER- 608.2.2.1. NOT PROVIDED.
 N) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE ACCESSIBLE SHOWER- 608.3.2. GRAB BAR
 LOCATIONS AND POSITIONING DEPEND ON WHETHER A SEAT IS
 BEING INSTALLED. THE FLOOR PLAN DOES NOT SHOW A SEAT IN
 THE SHOWER, HOWEVER DETAIL 8 SHOWS A SEAT.
 O) FAILED. LOCATION OF THE SHOWER CONTROL AND SPRAY-
 608.5.2. SHOWER CONTROL LOCATIONS AND POSITIONING
 DEPEND ON WHETHER A SEAT IS BEING INSTALLED. THE FLOOR
 PLAN DOES NOT SHOW A SEAT IN THE SHOWER, HOWEVER DETAIL
 8 SHOWS A SEAT.
 P) FAILED. ACCESSIBLE URINAL- SHOW THE LOCATION(S),
 PROVIDE THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS,
 PROVIDE THE RIM HEIGHT FROM THE F.F., AND THE URINAL
 DEPTH- SECTIONS 213.3 & 605.2 FBC ACC. NOT PROVIDED.
  
 10) FAILED. A9.1.8: SHOW THE DEPTH MEASUREMENTS OF THE
 STANDARD WATER CLOSET COMPARTMENTS- SECTION 405.3.1 FBC
 P. NOT PROVIDED.
  
 11) FAILED. A9.1.5 & A9.1.8: IN ACCORDANCE WITH SECTION
 213.3.1 FBC ACC, AMBULATORY TOILET COMPARTMENT STALLS
 ARE REQUIRED FOR THE MEN'S (138) AND WOMEN'S (148)
 BATHROOMS. PLEASE SEE SECTIONS 604.8.2- 604.8.2.3 AND
 REVISE THE PLANS AND DETAILS ACCORDINGLY. AMBULATORY
 COMPARTMENT FOR MEN NOT SHOWN ON A9.18. NO GRAB BAR
 DETAILS PROVIDED ON EITHER SHEET- SEE SECTIONS
 604.8.2.3 & 604.5.1 FBC ACC.
  
 12) FAILED P1.1.0 SAND/OIL INTERCEPTOR (SOI-1): A)
 FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS- SECTION 1003.4.2 FBC P.
 PLEASE ADD THE SOI-1 TO THE SEPARATE PERMIT LIST ON
 SHEET G1.0.1. FAILED. C) PROVIDE SIZING CALCULATIONS IN
 ACCORDANCE WITH SECTION 1003.4.2.1 OR PER
 MANUFACTURER'S SPECIFICATIONS. IT APPEARS THAT THE
 SO1-1 CALCULATIONS HAVE BEEN MISLABELED AS LINT
 INTERCEPTOR CALCULATION. IF THAT IS THE CASE, IT ALSO
 APPEARS THAT THE OS-75 AT 93 GALLONS CAPACITY IS
 UNDERSIZED PER THE 110 GALLONS REQUIRED BY THE
 CALCULATIONS.
  
 13) FAILED. P1.1.0 LINT TRAP (LI-1): A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS- SECTION 1003.6 FBC P. SEE COMMENT #12
 REGARDING THE LINT INTERCEPTOR SIZING CALCULATIONS.
 PLEASE CLARIFY HOW THE LINT INTERCEPTOR WAS SIZED.
  
 14) FAILED. P1.1.0 STORM SUMP PUMP: A) FAILED. SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS- SECTION 1113.1 FBC P. PLEASE ADD THE SUMP
 PUMP COMPONENTS TO THE DEFERRED SUBMITTALS LIST ON
 G1.01. REVIEW COMMENT #16 NOTES BELOW.
  
 16) FAILED. P1.1.0, C2 & C2.1: SHOW THE DRAINAGE PIPING
 CONNECTIONS FOR THE TRENCH DRAINS (TD-1) LOCATED AT THE
 BAY DOORS. IF CONNECTING TO THE CITY STORM DRAINAGE
 SYSTEM, REFER TO SEC. 90-203 WPB CODE OF ORDINANCES AND
 VERIFY THAT THE DRAINS WILL CONVEY ONLY STORM WATER
 INTO THE SYSTEM. PLEASE NOTE THAT IT IS UNLAWFUL FOR
 ANY OTHER SUBSTANCES TO DISCHARGE INTO THE SYSTEM
 UNLESS MEETING ONE OF THE EXCEPTIONS UNDER SEC. 90- 205
 WPB. PLEASE REFER TO SEC. 90-203-205 WPB CODE OF
 ORDINANCES- THE PLAN SHOWS TRENCH DRAINS FROM THE
 GARAGE DRAINING DIRECTLY INTO THE SUMP PIT, BUT NEARBY
 FLOOR DRAINS DRAINING INTO THE OIL SEPARATOR. PLEASE
 CLARIFY WHY THE DRAINAGE FROM THE FLOOR DRAINS WOULD
 CONTAIN SUBSTANCES THAT REQUIRE SEPARATION AND THE
 TRENCH DRAINS WOULD NOT. THE EOR SHALL VERIFY THAT THE
 DISCHARGE FROM THE SUMP INTO THE STORM DRAIN SYSTEM
 WILL CONTAIN ONLY STORMWATER AND NO OTHER SUBSTANCES
 SUCH AS OIL, GREASE, OR CHEMICALS. PLEASE NOTE THAT AN
 OIL SEPARATOR MAY BE REQUIRED- SEC. 1003.4 FBC P.
  
 17) FAILED- SEE NOTES. P1.1.0 SANITARY BACKWATER VALVE:
 A) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATIONS INSTRUCTIONS- SECTIONS 715.2- 715.4. NOT
 PROVIDED. PLEASE ADD THE VALVE TO THE DEFERRED
 SUBMITTALS LIST ON G1.01.B) FAILED. PROVIDE AN
 INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS
 715.5 & 305.7. NOT PROVIDED.
  
 19) FAILED. P1.1.1 GREASE INTERCEPTOR. C) FAILED.
 PROVIDE AN ENLARGED SITE-SPECIFIC PIPING DRAWING-
 SECTION 107.2.1 WPB. NOT PROVIDED. D) FAILED. PLEASE
 NOTE ONLY FIXTURES DISCHARGING GREASE LADEN WASTE WATER
 SHALL FLOW INTO THE GREASE INTERCEPTOR. CLEAR WATER
 WASTE FROM HAND SINKS, ICE MACHINES ETC. SHALL NOT
 DRAIN INTO THE SYSTEM- SECTION 1003.3.1 FBC P. THE
 CALCULATIONS ON P5.02 SHOW BAR SINKS. PLEASE CLARIFY
 THE LOCATIONS OF BAR SINKS ON THE PLANS AND WHAT THEIR
 USES ARE- THEY ARE NOT SPECIFIED IN THE SCHEDULE.
  
 20) FAILED. P1.1.1 SOLIDS INTERCEPTOR S1-1: A) FAILED.
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTION 1003.3.2 FBC P. NOT PROVIDED. THE
 RESPONSE NARRATIVE INDICATES THE S1-1 SPECS LOCATED AT
 DETAIL 2 ON SHEET P5.02 HOWEVER DETAIL 2 IS THE STORM
 SUMP PUMP DETAIL. B) FAILED. PROVIDE SIZING
 CALCULATIONS- 1003.3.4. NOT PROVIDED. C) FAILED.
 PROVIDE AN ENLARGED SITE-SPECIFIC PIPING DRAWING-
 SECTION 107.2.1 WPB.
  
 21) FAILED. P1.1.1 SAMPLING PORT (SP-1): A) FAILED.
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTION 1003.3.2 FBC P. NOT PROVIDED-
 PLEASE ADD TO THE DEFERRED SUBMITTALS LIST. B) FAILED.
 PROVIDE AN ENLARGED SITE-SPECIFIC PIPING DRAWING-
 SECTION 107.2.1 WPB. NOT PROVIDED- PLEASE ADD TO THE
 DEFERRED SUBMITTALS LIST.
  
 22) FAILED. P1.1.1: PROVIDE NOTES AT THE TERMINATION
 LOCATIONS OF THE GREASE WASTE AND SANITARY SEWER LINES
 OR SHOW THE POINTS OF CONNECTIONS TO THE SEWER LINE-
 SECTION 107.2.1 WPB. SHEET C3.1 SHOWS A SEWER
 CONNECTION AT THE LIFT STATION FOR THE STORM DRAINAGE-
 PLEASE CORRECT.
  
 23) FAILED. P1.1.1 STORM WATER BACKWATER VALVE: A)
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTIONS 715.2- 715.4. B) PROVIDE AN
 INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS
 715.5 & 305.7. NOT PROVIDED. PLEASE ADD TO THE DEFERRED
 SUBMITTALS LIST.
  
 24) FAILED. P2.01: PROVIDE ROOF DRAINAGE PLANS AND A
 STORM DRAIN ISOMETRIC DRAWING- SECTION 107.3.5.1.3 FBC
 P. THE NARRATIVE INDICATES THE ISOMETRIC DRAWING IS ON
 P.7.06 HOWEVER THE DRAWING WAS NOT UPLOADED FOR REVIEW.
 PLEASE SHOW THE LOCATIONS OF THE OVERFLOW SCUPPERS ON
 SHEET P.2.01.
  
 26) FAILED. P4.01, P7.02: THE GW FIXTURE DRAIN FROM THE
 MOP SINK IS SHOWN TO BE CONNECTING TO THE SANITARY
 DRAIN- SECTION 1003.3.1 FBC P. THE GREASE WASTE
 ISOMETRIC IS MISSING FROM THE DRAWINGS.
  
 27) FAILED. P4.01, P4.02, P7.01, P7.02, K7, K8, & K9:
 CLEAR WATER WASTE DRAINAGE FROM HAND SINKS AND WASTE
 RECEPTORS AT ICE BIN AND ICE MAKER LOCATIONS ARE SHOWN
 DISCHARGING INTO THE GW LINE WHICH IS PROHIBITED-
 SECTION 1003.3.1 FBC P. THE GREASE WASTE ISOMETRIC IS
 MISSING FROM THE DRAWINGS.
  
 28) FAILED. P4.01 & K7: CONDENSATE FROM THE WALK-IN BOX
 EVAPORATORS SHALL NOT DRAIN INTO THE CITY SANITARY
 SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES. REFER TO
 SHEETS P.401 & P.702 AND CLARIFY HOW THE CONDENSATE
 WILL BE DISPOSED OF. SHOW THE CONDENSATE LINES FROM THE
 EVAPORATORS AND DISCHARGE LOCATIONS. IT APPEARS THAT
 HUB DRAINS CANNOT BE USED BECAUSE THEY MAY BE CONVEYING
 OTHER WASTE AND NOT JUST CONDENSATE. PLEASE NOTWE THAT
 P.4021 SHOWS THE HUB DRAINS CONNECTING TO THE STORM,
 AND P.702 SHOWS CONNECTION TO THE SANITARY.
  
 29) FAILED. P4.01 & P4.02: INDICATE TEMPERED WATER IS
 BEING SUPPLIED TO LAVATORIES L-1, L-2, & L-3- SECTION
 419.5 FBC P. ACCORDING TO SECTION 607.1.2 FBC P.
 TEMPERED WATER SHALL BE SUPPLIED THROUGH A WATER
 TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070.
 PLEASE ADD THE COMPLIANCE NOTE IN THE SCHEDYULE AND ADD
 THE FAUCETS TO THE DEFERRED SUBMITTAL LIST.
  
 32) FAILED. P7.02: TD-2 AND SH-2 IN THE MEN'S BATHROOM
 DO NOT APPEAR TO BE VENTED PROPERLY. PLEASE CLARIFY HOW
 THE FIXTURES ARE BEING VENTED- SECTION 901.2.1 FBC P.
 A) RELOCATE THE 2-INCH VENT FOR BETWEEN THE TWO L2
 DRAIN CONNECTIONS- SECTION 912.2.1 FBC P. B) PROVIDE AN
 INDIVIDAUL VENT FOR SH-2- SECTION 910.1 FBC P. C)
 RELOCATE THE SH-1 SHOWER VENT TO A LOCATION BETWEEN THE
 TWO MOST UPSTREM FIXTURES CONNECTING TO THE HORIZONTAL
 BRANCH- SECTION 912.2.1 FBC P.
  
 33) FAILED. P7.01 & P7.02: INDICATE HOW TRAP SEAL
 PROTECTION WILL BE PROVIDED FOR FLOOR DRAINS AND OTHER
 TRAP SEALS SUBJECT TO EVAPORATION WILL BE PROTECTED-
 SECTION 1002.4.1 FBC P. THE CHIEF PLUMBING INSPECTOR
 FOR THE CITY OF WPB BUILDING DEPT. HAS PROHIBITED THE
 USE OF BARRIER-TYPE TRAP SEALS IN AREAS SUCH AS
 COMMERCAIL KITCHENS AND OTHER FLOOR AREAS WHERE
 EXCESSIVE GREASE OR OTHER SUBSTANCES AND DEBRIS WILL
 CAUSE THE TRAP TO FAIL. PLEASE PROVIDE AN ACCEPTABLE
 MEANS IN THE KITCHEN, BASEMENT AND LAUNDRY AREAS.
  
 35) FAILED. P7.03 & P7.04: PROVIDE A SHUTOFF VALVE AT
 THE TOP OF THE COLD WATER DOWN FEED PIPE FROM FIRST TO
 BASEMENT FLOOR- SECTION 606.1 (5) FBC P. P.704- SHUT
 OFF NOT SHOWN FOR 2-1/2-INCH CW LINE TO BASEMENT.
  
 38) FAILED. P.7.04: PROVIDE AN ENLARGED WATER
 FILTRATION PIPING DETAIL SHOWING SUPPLY CONNECTION TO
 THE FILTER, AND SUPPLY LINES TO FIXTURES AND EQUIPMENT
 REQUIRING FILTRATION. PLEASE NOTE THAT BACKFLOW
 PREVENTERS ARE REQUIRED FOR THE WATER SUPPLY LINES IN
 AND OUT OF THE FILTER- SECTION 608.3 FBC P. THE
 REQUESTED ENLARGED FILTER PIPING PLAN NOT PROVIDED. THE
 ISOMETRIC DRAWING APPEARS TO SHOW THE LOCATION FO THE
 FILTER BUT NO SUPPLY LINES TO EQUIPMENT.
  
 39) FAILED. PLEASE NOTE THAT ALL REQUESTED
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUALS
 FOR FIXTURES, APPLIANCES, AND EQUIPMENT MAY BE DEFERRED
 IN ACCORDANCE WITH SECTION 107.3.4.1 WPB. PLEASE NOTE
 THAT ALL DEFERRED SUBMITTALS SHALL BE LISTED ON THE
 PLAN. SEE PLAN REVIEW NOTES AND MODUIFY THE DEFERRED
 SUBMITTALS LIST.
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY
 SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED
 AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF
 THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 NEW COMMENT: TO HELP EXPEDITE THE REVIEW PROCESS,
 PLEASE CORRELATE THE PLUMBING FIXTURES AND EQUIPMENT
 SHOWN ON THE DRAWING WITH THE KITCHEN AND PLUMBING
 EQUIPMENT SCHEDULES. THE DRAWINGS ARE USING THE LETTER
 (P) HOWEVER THE SCHEDULES USE (K) AND IT APPEARS SOME
 OF THE NUMBERS ARE NOT MARCHING BETWEEN THE PLANS AND
 SCHEDULE FOR EXAMPLE- (PS2).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER