| 2021-09-28 09:49:42 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21070675 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M6.0.1: IF THE OUTDOOR AIR CALCULATIONS ARE |
| | GOING TO BE BASED ON ASHRAE 62.1-2016 EDITION THE |
| | OCCUPANT COUNT FOR EACH USE OF SPACE MUST MATCH THE |
| | OCCUPANT COUNT BASED ON FBC 1004.5 SOME OF THE OUTDOOR |
| | AIR CALCULATIONS APPEAR TO BE LOW. PLEASE CHECK AGAIN |
| | AND MAKE SURE THAT YOU ARE MEETING THE MINIMUM REQUIRED |
| | OUTDOOR AIR CALCULATIONS. FBC M 403.3.1.1 AND TABLE |
| | 403.3.1.1 EXAMPLE- PRIVATE DINING 2- 400 SQ FT; 400/15 |
| | = 27 OCCUPANTS. |
| | 27 X 7.5 = 202.5; 400 X .18 = 72; 202.5 + 72 = 275 CFM |
| | OF REQUIRED OUTDOOR AIR. |
| | |
| | 2) PLEASE PROVIDE THE MODEL NUMBER OF THE GAS DRYERS AS |
| | THE LENGTH AND 90 DEGREE DUCTS ARE SPECIFIED IN THE |
| | INSTRUCTION MANUAL. |
| | |
| | 3) PLEASE SHOW THE LOCATION OF THE REQUIRED LOUVERS FOR |
| | THE MAKEUP AIR FOR THE COMMERCIAL DRYERS ACCORDING TO |
| | THE MODELS OF THE DRYERS AND PAGE 52 OF THE INSTRUCTION |
| | MANUAL FOR THE DRYERS. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |