| 2021-10-08 13:20:14 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21070675 |
| | 10/8/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITONAL NOTES IN CAP |
| | LETTERS. |
| | |
| | 1) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION MANUALS FOR THE WATER HEATERS AND DIRECT |
| | VENT SYSTEM, COOKING APPLIANCES, DRYERS, REGULATORS, |
| | SOLENOID VALVES- SECTION 305.1, 623.1, & 624.1 FBC FG, |
| | AND 107.2.1 WPB. BASED ON THE NARRATIVE RESPONSE PLEASE |
| | ADD THE ITEMS TO THE DEFERRED SUBMITALL LIST- SECTION |
| | 107.3.4.1 WPB. |
| | |
| | 4) FAILED. P4.01 & P7.05: THE GAS SUPPLY PIPE TO THE |
| | GENERATOR SHALL BE CONNECTED ON THE SUPPLY SIDE OF THE |
| | MAIN GAS SHUTOFF VALVE TO THE BUILDING AND BE MARKED AS |
| | SUPPLYING AN EMERGENCY GENERATOR- SECTION 7.9.7 NFPA |
| | 110. THE DRAWINGS WERE NOT CORRECTED. |
| | |
| | 6) FAILED. P4.01, P4.02 & P7.05: PLACE NOTES TO |
| | INDICATE ALL SHUTOFF VALVES INCLUDING THE SOLENOID |
| | VALVES WITH MANUAL RESETS ARE IN ACCESSIBLE LOCATIONS- |
| | SECTION 409.1.3 FBC FG. IT APPEARS THAT ONE AUTO VALVE |
| | WILL SERVE BOTH COOKING LINES WHICH APPEARS TO NOT MEET |
| | THE INTENT OF THE CODE. THERE ARE TWO HOOD EXHAUST |
| | SYSTEMS WHICH WILL TYPICALLY HAVE TWO SEPARATE FIRE |
| | SUPPRESSION SYSTEMS. CLARIFY IF THE INTENTION IS TO |
| | HAVE GAS SUPPLY SHUT DOWN TO BOTH COOKING LINES IF AN |
| | INCIDENT OCCURS AT ONLY ONE OF THE TWO COOKING LINES |
| | AND SUPPRESSION SYSTEMS. PLEASE ENSURE THAT THE FIRE |
| | SUPPRESSION SYSTEMS WILL CORRELATE TO THIS DESIGN- |
| | SECTION 107.2.1 WPB. |
| | |
| | 7) FAILED. P4.01 & P7.05: PLACE A NOTE TO INDICATE THE |
| | SOLENOID VALVE SHOWN AT THE COOKING LINE MEETS |
| | COMPLIANCE WITH SECTION 10.4.1 NFPA 96: AN AUTOMATIC |
| | GAS SHUTOFF VALVE IS REQUIRED TO BE CONNECTED TO THE |
| | HOOD FIRE SUPPRESSION SYSTEM. PLEASE SEE COMMENT #6 |
| | NOTES. |
| | |
| | 8) FAILED. P4.01 & P7.05: SHOW THE LOCATION OF THE |
| | AUTOMATIC GAS VALVE FOR THE GAS LINE SERVICE COOKING |
| | APPLIANCES PK39, PK40 & PK41- SECTION 10.4.1 NFPA 96. |
| | PLEASE SEE COMMENT #6 NOTES. |
| | |
| | 10) FAILED. P7.05: SHOW THE BRANCH LENGTHS AND CUT PIPE |
| | LENGTH MEASUREMENTS ON THE RISER INCLUDING BRANCH AND |
| | TOTAL LENGTHS FROM SECONDARY REGULATORS TO APPLIANCE |
| | AND EQUIPMENT OUTLETS- SECTIONS 402.4.1 & 402.4.2 FBC |
| | FG. A) THE MEASUREMENTS SHOWN ON THE RISER INDICATE THE |
| | 5 PSI LINE FROM THE METER TO THE LOW PRESSURE REGULATOR |
| | FOR THE DRYERS HAS A TDL OF 103 FT. THE LENGTH TO THE |
| | LOW PRESSURE REGULATOR SERVING THE COOKING LINES IS 91 |
| | FT. NOTE #1 ON THE PLAN INDICATES 202 FT. WHICH APPEARS |
| | INCORRECT. |
| | |
| | 11) FAILED. P7.05: PROVIDE REGULATORS AT THE GAS DRYER |
| | AND GENERATOR LOCATIONS- SECTIONS 410.2 FBC FG. |
| | REGULATOR/NOTE NOT PROVIDED AT THE GENERATOR. PLEASE |
| | SEE PAGE 57- 60 OF THE ALLIANCE LAUNDRY SYSTEM |
| | INSTALLATION MANUAL AND PROVIDE THE INPUT PRESSURES |
| | RATING OF THE DRYERS AND VERIFY COMPLIANCE WITH THE |
| | PRESSURE DROP TABLES SHOWN. |
| | |
| | 14) FAILED. P7.05 & P.1.1.1: BASED ON SHEET P1.1.1 IT |
| | APPEARS THE GAS PIPING TO THE GENERATOR MAY BE RUNNING |
| | UNDERGROUND. P1.1.1 SHOWS THE PIPING CROSSING IN FRONT |
| | OF THE ENTRY DOOR TO THE WATER ROOM. PLEASE PLACE NOTES |
| | ON THE RISER TO CLARIFY AND PROVIDE COMPLIANCE DETAILS |
| | FOR UNDERGROUND PIPING- SECTIONS 404.6 & 404.11 FBC FG. |
| | IF THE PIPING IS PE PLEASE PROVIDE INSTALLATION AND |
| | RISER DETAILS, AND THE PIPE SIZING TABLE TO BE USED- |
| | SECTION 402.4 FBC FG. THE METALLIC PIPING RUNNING |
| | UNDERGROUND SHALL BE PROTECTED AGAINST CORROSION- |
| | SECTIONS 404.11- 404.11.2 FBC FG. PLEASE INDICATE THE |
| | METHOD OF PROTECTION. |
| | |
| | 15) FAILED. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | GAS-FIRED COOKING APPLIANCES AND INDICATE HOW THE AIR |
| | WILL BE PROVIDED- SECTION 304.1 FBC FG. BASED ON THE |
| | NARRATIVE RESPONSE, REVIEW OF SHEET M6.0.1 INDICATES |
| | RTU 6 FOR THE KITCHEN HAS AN EXCESS SUPPLY OF 267 CFMS |
| | OF O/A AND THE CALCULATIONS INDICATE 435 CFMS IS |
| | REQUIRED. PLEASE NOTE THAT SECTION 304.9.3 REQUIRES THE |
| | SYSTEM SHALL PROVIDE THE SPECIFIED RATE IN ADDITION TO |
| | THE VENTILATION AIR RATE. |
| | |
| | 16) FAILED. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | GAS-FIRED DRYERS AND INDICATE HOW THE AIR WILL BE |
| | PROVIDED- SECTION 304.1 FBC FG. REFER TO SECTION |
| | 304.6.2 FG FOR COMBUSTION AIR USING THE ONE |
| | PERMANENT-OPENING METHOD. THE OPENING IN THE DOOR DOES |
| | NOT MEET COMPLIANCE FOR SIZE AND LOCATION. THE OPENING |
| | SHALL BE WITHIN 12 INCHES TO THE TOP OF THE ENCLOSURE |
| | AND COMMUNICATING DIRECTLY WITH THE OUTDOORS. IN |
| | ADDTION, PLEASE REFER TO SECTION 404.3 FBC M WHICH |
| | REQUIRES ROOMS ADJACENT TO PARKING GARAGES TO BE |
| | MAINTAINED AT A POSITIVE PRESSURE. A) PLEASE SEE PAGE |
| | 21 OF THE SUBMITTED ALLIANCE LAUNDRY SYSTEM SPECS AND |
| | INDICATE THE MODEL NUMBER OF THE DRYER. B) PLEASE SEE |
| | PAGE 52 OF THE ALLIANCE LAUNDRY SYSTEM SPECIFICATIONS |
| | AND SHOW COMPLIANCE FOR MAKEUP AIR OPENINGS. |
| | |
| | 17) FAILED. PROVIDE A GAS DRYER EXHAUST DIAGRAM |
| | INDICATING THE TYPE AND SIZE OF EXHAUST DUCT, TOTAL RUN |
| | LENGTH AND TERMINATION LOCATION- SECTION 614.1 FBC FG. |
| | SHOW THE LOCATION OF REQUIRED CLEANOUTS- 614.3 AND |
| | PROVIDE TERMINATION CAP DETAILS- 614.4. PLEASE PROVIDE |
| | A SITE-SPECIFIC EXHAUST DUCT DIAGRAM BASED ON THE |
| | MANUFACTURER'S RECOMMENDATIONS SHOWN ON PAGES 52-56 OF |
| | THE SUBMITTED ALLIANCE LAUNDRY SYSTEMS SPECS. REFER TO |
| | PAGE 4- THE MAXIMUM ALLOWABLE LENGTH IS 14 FT AND WITH |
| | TWO 90 DEGREE ELBOWS OR EQUIVALENT FOR AN INDIVIDUAL |
| | VENT. SEE THE TABLE ON PAGE 54 FOR DUCT DIAMETERS AND |
| | ELBOW LENGTHS. |
| | |
| | 18) FAILED. PLEASE NOTE THAT ALL REQUESTED |
| | MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUALS |
| | FOR FIXTURES, APPLIANCES, AND EQUIPMENT MAY BE DEFERRED |
| | IN ACCORDANCE WITH SECTION 107.3.4.1 WPB. ALL DEFERRED |
| | SUBMITTALS SHALL BE LISTED ON THE PLAN. PLEASE PROVIDE |
| | A LIST OF DEFERRED SUBMITTALS THAT INCLUDE THE WATER |
| | HEATERS, COOKING APPLIANCES, REGULATORS, SOLENOID VALVE |
| | ETC. |
| | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY |
| | SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE |
| | BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED |
| | AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF |
| | THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |