| Date |
Text |
| 2021-08-23 15:04:52 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) THE FO;OWING SYSTEMS NEED SEPARATE PERMITS, |
| | GENERATOR, BDA, SITE LIGHTING, FIRE ALARM, LOW VOLTAGE |
| | WIRING. |
| | |
| | 2) PAGE E4.02 GFCI PROTECTION FOR THE KITCHEN PREP |
| | AREAS. |
| | 210.8(B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE |
| | RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50 |
| | AMPERES OR LESS AND THREEPHASE |
| | RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100 |
| | AMPERES OR LESS INSTALLED IN THE FOLLOWING LOCATIONS |
| | SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION |
| | FOR PERSONNEL. |
| | (2) KITCHENS, (5) SINKS ? WHERE RECEPTACLES ARE |
| | INSTALLED WITHIN 1.8 M (6 FT) FROM THE TOP INSIDE EDGE |
| | OF THE BOWL OF THE SINK |
| | (5) SINKS ? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 |
| | M (6 FT) FROM THE TOP INSIDE EDGE OF THE BOWL OF THE |
| | SINK |
| | (6) INDOOR WET LOCATIONS. |
| | |
| | 2) AIC RATING OF MAINS AND BRANCH BREAKERS REQUIRED PER |
| | 110.9, 110.10 |
| | |
| | 3) TAMPER RESISTANT OUTLETS ARE REQUIRED PER 406.12 |
| | 125- AND 250-VOLT NONLOCKING-TYPE RECEPTACLES IN THE |
| | AREAS SPECIFIED IN 406.12(1) THROUGH (7) SHALL BE |
| | LISTED TAMPERRESISTANT |
| | RECEPTACLES. |
| | (1) DWELLING UNITS IN ALL AREAS SPECIFIED IN 210.52 AND |
| | 550.13 |
| | (2) GUEST ROOMS AND GUEST SUITES OF HOTELS AND MOTELS |
| | (3) CHILD CARE FACILITIES |
| | (4) PRESCHOOLS AND ELEMENTARY EDUCATION FACILITIES |
| | (5) BUSINESS OFFICES, CORRIDORS, WAITING ROOMS AND THE |
| | LIKE IN |
| | CLINICS, MEDICAL AND DENTAL OFFICES AND OUTPATIENT |
| | FACILITIES |
| | (6) SUBSET OF ASSEMBLY OCCUPANCIES DESCRIBED IN 518.2 |
| | TO |
| | INCLUDE PLACES OF WAITING TRANSPORTATION, GYMNASIUMS, |
| | SKATING RINKS, AND AUDITORIUMS |
| | (7) DORMITORIES |