Plan Review Notes
Plan Review Notes For Permit 21070675
Permit Number 21070675
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-20 09:00:011ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21070675
 8/19/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 THE INSTALLATION OF THE , GREASE AND SOLIDS
 INTERCEPTORS, LIFT STATION, UNDERGROUND FIRE LINE,
 POTABLE WATER SERVICE BACKFLOW PREVENTER, IRRIGATION
 SERVICE BACKFLOW PREVENTER, FIRE LINE BACKFLOW
 PREVENTER, FIRE SPRINKLER, AND GAS-FIRED GENERATOR-
 SECTIONS 105.1 & 107.2.1 WPB.
  
 2) PROVIDE IRRIGATION PLANS OR INDICATE THE PLANS WILL
 BE SUBMITTED UNDER A SEPARATE PERMIT APPLICATION-
 SECTION 105.1 & 107.2.1 WPB.
  
 3) SHEET ALS.1.0 CODE DATA & PLUMBING FIXTURE REQ'S:
 THE LIFE SAFETY OCCUPANT LOAD AND FIXTURE CALCULATIONS
 ARE LACKING THE SQUARE FOOTAGES AND OCCUPANT LOADS OF
 EACH OF THE BUILDING AREAS (A2, M, B, & S). PLEASE NOTE
 THAT CODE SECTION 506.1.3 FBC B WHICH IS CALLED OUT IN
 THE DATA PERTAINS TO ALLOWABLE AREA FOR THE BUILDING
 AND DOES NOT EXCLUDE PLUMBING FIXTURE CALCULATIONS FOR
 THE BASEMENT AREAS. A COMPLETE REVIEW OF THE PLUMBING
 CANNOT BE COMPLETELY WITHOUT ACCURATE OCCUPANCY LOAD
 CALCULATIONS FOR EACH AREA OF THE BASEMENT AND GROUND
 FLOOR. THE RESTROOMS SHALL BE LABELED AS EITHER MALE OR
 FEMALE- TABLE 403.1 & SECTION 403.2 FBC P.THE PLANS
 SHOW FOUR RESTROOMS (TWO IN THE BASEMENT AND TWO ON THE
 FIRST FLOOR) THAT ARE NOT LABELED- SEE SECTION 403.1.2.
 A) ALS.1.0: REFER TO SECTION 403.1.4 FBC P AND INCLUDE
 THE OUTDOOR SEATING WITH THE CALCULATIONS.
  
 B) ALS.1.0: REFER TO SECTION 403.3 FBC P AND DESIGNATE
 THE REQUIRED EMPLOYEE TOILET FACILITIES AS EITHER
 SEPARATE OR COMBINED EMPLOYEE AND PUBLIC TOILET
 FACILITIES. PLEASE PROVIDE A BREAKDOWN CALCULATION FOR
 EMPLOYEES THAT INCLUDES THE GOLF CART GARAGE, CADDY
 LOUNGE, BEVERAGE AREA ETC.
  
 C) ALS.1.0: DRINKING FOUNTAINS ARE REQUIRED FIXTURES
 FOR MERCANTILE, BUSINESS, AND STORAGE OCCUPANCIES.
 EXCEPTION 410.4 IS CALLED OUT IN THE TABLE HOWEVER
 SECTION 410.4 SUBSTITUTION OF DRINKING WATER IN A
 CONTAINER FREE OF CHARGE APPLIES ONLY TO THE RESTAURANT
 AREA.
  
 4) A9.01: MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS
 PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 G) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 H) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
 I) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR A
 FORWARD OR PARALLEL APPROACH TO THE SINK IN THE LOUNGE-
 606.2. KNEE AND TOE CLEARANCES FOR FORWARD APPROACHES-
 SECTION 606.2
 J) LOUNGE SINK HEIGHT FROM THE FINISHED FLOOR TO THE
 RIM OF THE SINK- 606.3. NOTE- THE DRAWING SHOWS THE
 MEASUREMENT TO THE COUNTER.
 K) REACH RANGES AND OPERABLE PARTS FOR THE COFFEE
 MAKER- 308. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS
 TO VERY COMPLIANCE.
  
 5) A9.1.2: MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS
 PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAMETER- SECTION 304.3.
 D) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SECTION 604.4.
 E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 G) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE
 604.7.
 H) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 606.2
  
 6) A9.1.3: MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS
 PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAMETER- SECTION 304.3.
 D) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOORS- SECTION 604.4.
 E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 G) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE
 604.7.
 H) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 606.2.
 I) CLEAR INSIDE DIMENSIONS FOR THE ACCESSIBLE SHOWER-
 SECTION 608.2.1
 J) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 ACCESSIBLE SHOWER- 608.2.1.
 K) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER 608.3 AND 608.3.1
 L) SHOW THE LOCATION OF THE SHOWER CONTROL AND SPRAY IN
 ACCORDANCE WITH FIGURE 608.5.1.
 M) SHOWER SPRAY UNIT SPECIFICATIONS- 608.6.
 N) PROVIDE THE ACCESSIBLE SHOWER SEAT HEIGHT AND
 MOUNTING DETAILS- 610.3 & 610.3.2. & FIGURE 610.3.2.
  
 7) A9.1.5, A9.1.6 & A9.1.7: MISSING ACCESSIBLE PLUMBING
 FIXTURE DETAILS PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.LI) CLEAR INSIDE DIMENSIONS FOR THE ACCESSIBLE
 SHOWERS- SECTION 608.2.2.
 L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 ACCESSIBLE SHOWER- 608.2.2.1.
 M) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- 608.3.2.
 N) LOCATION OF THE SHOWER CONTROL AND SPRAY- 608.5.2
 O) SHOWER SPRAY UNIT SPECIFICATIONS- 608.6.
  
 8) A9.1.5: SHOW THE DEPTH MEASUREMENTS OF THE STANDARD
 WATER CLOSET COMPARTMENTS- SECTION 405.3.1 FBC P.
  
 9) A9.1.8 & A9.1.9: MISSING ACCESSIBLE PLUMBING FIXTURE
 DETAILS PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
 I) CLEAR INSIDE DIMENSIONS FOR THE ACCESSIBLE SHOWERS-
 SECTION 608.2.2.
 J) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 ACCESSIBLE SHOWER- 608.2.2.1.
 K) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- 608.3.2.
 L) LOCATION OF THE SHOWER CONTROL AND SPRAY- 608.5.2
 M) SHOWER SPRAY UNIT SPECIFICATIONS- 608.6.
 N) ACCESSIBLE URINAL- SHOW THE LOCATION(S), PROVIDE THE
 CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS, PROVIDE THE
 RIM HEIGHT FROM THE F.F., AND THE URINAL DEPTH-
 SECTIONS 213.3 & 605.2 FBC ACC.
  
 10) A9.1.8: SHOW THE DEPTH MEASUREMENTS OF THE STANDARD
 WATER CLOSET COMPARTMENTS- SECTION 405.3.1 FBC P.
  
 11) A9.1.5 & A9.1.8: IN ACCORDANCE WITH SECTION 213.3.1
 FBC ACC, AMBULATORY TOILET COMPARTMENT STALLS ARE
 REQUIRED FOR THE MEN'S (138) AND WOMEN'S (148)
 BATHROOMS. PLEASE SEE SECTIONS 604.8.2- 604.8.2.3 AND
 REVISE THE PLANS AND DETAILS ACCORDINGLY.
  
 12) P1.1.0 SAND/OIL INTERCEPTOR (SOI-1): A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS- SECTION 1003.4.2 FBC P. B) LABEL THE
 ACCESS COVER AND RATED TRAFFIC LID- 1003.10, 1003.11 &
 305.7. C) PROVIDE SIZING CALCULATIONS IN ACCORDANCE
 WITH SECTION 1003.4.2.1 OR PER MANUFACTURER'S
 SPECIFICATIONS.
  
 13) P1.1.0 LINT TRAP (LI-1): A) SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS- SECTION
 1003.6 FBC P.
  
 14) P1.1.0 STORM SUMP PUMP: A) SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS- SECTION
 1113.1 FBC P. B) PROVIDE PUMP SIZING CALCS AND PUMP
 CURVE- 1113.1.1 C) PROVIDE AN ENLARGED INSTALLATION
 DETAIL SHOWING THE SUMP PIT DIMENSIONS, PIT MATERIALS,
 LOCATIONS OF VALVES, ACCESS TO VALVES, AND TRAFFIC
 RATED COVER- 1113.1.2. (DETAIL ON P5.02 IS INCOMPLETE)
 .D) SHOW THE LOCATION AND SIZE OF REQUIRED VENT-
 1113.1.4
  
 15) P.1.1.0: PROVIDE A NOTE AND GPM FLOW FOR THE STORM
 DRAIN PIPE BY THE SOUTH ENTRY DOOR- SECTION 1106.2 FBC
 P.
  
 16) P1.1.0, C2 & C2.1: SHOW THE DRAINAGE PIPING
 CONNECTIONS FOR THE TRENCH DRAINS (TD-1) LOCATED AT THE
 BAY DOORS. IF CONNECTING TO THE CITY STORM DRAINAGE
 SYSTEM, REFER TO SEC. 90-203 WPB CODE OF ORDINANCES AND
 VERIFY THAT THE DRAINS WILL CONVEY ONLY STORM WATER
 INTO THE SYSTEM. PLEASE NOTE THAT IT IS UNLAWFUL FOR
 ANY OTHER SUBSTANCES TO DISCHARGE INTO THE SYSTEM
 UNLESS MEETING ONE OF THE EXCEPTIONS UNDER SEC. 90- 205
 WPB.
  
 17) P1.1.0 SANITARY BACKWATER VALVE: A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTIONS 715.2- 715.4. B) PROVIDE AN
 INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS
 715.5 & 305.7.
  
 18) P1.1.0: PLACE A NOTE TO INDICATE NON-POTABLE WATER
 SIGNAGE WILL BE PROVIDED AT THE HB-1 LOCATION IN
 ACCORDANCE WITH SECTION 608.8.1 FBC P.
  
 19) P1.1.1 GREASE INTERCEPTOR G1-1: A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTION 1003.3.4 FBC P. B) PROVIDE SIZING
 CALCULATIONS- 1003.3.4. C) PROVIDE AN ENLARGED
 SITE-SPECIFIC PIPING DRAWING- SECTION 107.2.1 WPB. D)
 PLEASE NOTE ONLY FIXTURES DISCHARGING GREASE LADEN
 WASTE WATER SHALL FLOW INTO THE GREASE INTERCEPTOR.
 CLEAR WATER WASTE FROM HAND SINKS, ICE MACHINES ETC.
 SHALL NOT DRAIN INTO THE SYSTEM- SECTION 1003.3.1 FBC
 P.
  
 20) P1.1.1 SOLIDS INTERCEPTOR S1-1: A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTION 1003.3.2 FBC P. B) PROVIDE SIZING
 CALCULATIONS- 1003.3.4. C) PROVIDE AN ENLARGED
 SITE-SPECIFIC PIPING DRAWING- SECTION 107.2.1 WPB.
  
 21) P1.1.1 SAMPLING PORT (SP-1): A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTION 1003.3.2 FBC P. B) PROVIDE AN
 ENLARGED SITE-SPECIFIC PIPING DRAWING- SECTION 107.2.1
 WPB.
  
 22) P1.1.1: PROVIDE NOTES AT THE TERMINATION LOCATIONS
 OF THE GREASE WASTE AND SANITARY SEWER LINES OR SHOW
 THE POINTS OF CONNECTIONS TO THE SEWER LINE- SECTION
 107.2.1 WPB.
  
 23) P1.1.1 STORM WATER BACKWATER VALVE: A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTIONS 715.2- 715.4. B) PROVIDE AN
 INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS
 715.5 & 305.7.
  
 24) P2.01: PROVIDE ROOF DRAINAGE PLANS AND A STORM
 DRAIN ISOMETRIC DRAWING- SECTION 107.3.5.1.3 FBC P.
 PLEASE NOTE THAT SEPARATE SYSTEMS ARE REQUIRED FOR
 PRIMARY AND SECONDARY (OVERFLOW) DRAINS- SECTION 1108.1
 FBC P. PLEASE SHOW THE PRIMARY AND SECONDARY SYSTEM
 DISCHARGE LOCATION(S). A) SHEET A2.01 SCHEDULE
 INCORRECTLY LISTS AREA 07 AS 02- SECTION 107.2.1 WPB.
 B) PROVIDE ROOF DRAIN AND OVERFLOW DRAIN INSTALLATION
 DETAILS- SECTIONS 1102.6 & 1105.1 C) PROVIDE GUTTER AND
 DOWNSPOUT INSTALLATION DETAILS INCLUDING DOWNSPOUT
 VERTICAL LEADERS TO UNDERGROUND STORM DRAIN
 CONNECTIONS- 1101.6, 1102.7.
  
 25) P4.01: PROVIDE CONDENSATE DISPOSAL DETAILS FOR THE
 TANKLESS WATER HEATERS- SECTION 314.1 FBC P. SEE GAS
 REVIEW COMMENTS FOR ADDITIONAL GAS WATER HEATER CODE
 REQUIREMENTS.
  
 26) P4.01, P7.02: THE GW FIXTURE DRAIN FROM THE MOP
 SINK IS SHOWN TO BE CONNECTING TO THE SANITARY DRAIN-
 SECTION 1003.3.1 FBC P.
  
 27) P4.01, P4.02, P7.01, P7.02, K7, K8, & K9: CLEAR
 WATER WASTE DRAINAGE FROM HAND SINKS AND WASTE
 RECEPTORS AT ICE BIN AND ICE MAKER LOCATIONS ARE SHOWN
 DISCHARGING INTO THE GW LINE WHICH IS PROHIBITED-
 SECTION 1003.3.1 FBC P.
  
 28) P4.01 & K7: CONDENSATE FROM THE WALK-IN BOX
 EVAPORATORS SHALL NOT DRAIN INTO THE CITY SANITARY
 SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES.
  
 29) P4.01 & P4.02: INDICATE TEMPERED WATER IS BEING
 SUPPLIED TO LAVATORIES L-1, L-2, & L-3- SECTION 419.5
 FBC P.
  
 30) P7.01: THE RISER IS LABELED AS BASEMENT WASTE AND
 VENT RISER, HOWEVER THE 1ST FLOOR GREASE WASTE/VENT
 RISER IS ALSO SHOWN- SECTION 107.2.1 WPB.
  
 31) P7.01: THE 2-INCH WASTE STACKS FOR THE WASHING
 MACHINES ARE UNDERSIZED. MINIMUM 3-INCH STACKS ARE
 REQUIRED- SECTION 406.2 FBC P.
  
 32) P7.02: TD-2 AND SH-2 IN THE MEN'S BATHROOM DO NOT
 APPEAR TO BE VENTED PROPERLY. PLEASE CLARIFY HOW THE
 FIXTURES ARE BEING VENTED- SECTION 901.2.1 FBC P.
  
 33) P7.01 & P7.02: INDICATE HOW TRAP SEAL PROTECTION
 WILL BE PROVIDED FOR FLOOR DRAINS AND OTHER TRAP SEALS
 SUBJECT TO EVAPORATION WILL BE PROTECTED- SECTION
 1002.4.1 FBC P.
  
 34) P7.03, P7.04, K9: REQUIRED BACKFLOW PREVENTERS NOT
 SHOWN FOR SUPPLY LINES TO THE PIZZA OVEN, DISHWASHERS,
 COFFEE BREWER, ICED TEA BREWER, GLASS FILLER STATION,
 ICE AND SODA DISPENSER, SODA SYSTEM, HOT FOOD WELL, ICE
 MAKER, ICE BIN, WATER FILTRATION SYSTEM, BLENDER
 STATION, AND THE REF IMB-1- SECTION 608.3. FBC P.
  
 35) P7.03 & P7.04: PROVIDE A SHUTOFF VALVE AT THE TOP
 OF THE COLD WATER DOWN FEED PIPE FROM FIRST TO BASEMENT
 FLOOR- SECTION 606.1 (5) FBC P.
  
 36) P7.03 & P7.04: SHOW THE LOCATIONS OF WATER HAMMER
 ARRESTORS FOR SUPPLY LINES TO FLUSH VALVES, WASHING
 MACHINES, DISHWASHERS, AND OTHER FIXTURES AND EQUIPMENT
 WITH QUICK CLOSING VALVES- SECTION 604.9 FBC P.
  
 37) P7.04: PROVIDE AN ENLARGED PIPING DIAGRAM FOR
 INSTALLATION OF THE WATER HEATERS AND RECIRCULATION
 PUMPS SHOWING COMPLIANCE WITH 607.2.2 FBC P. SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE PUMPS SHOWING
 COMPLIANCE WITH SECTION 607.2.1.2 ITEMS 1 & 2 FBC P-
 CONTROLS OPERATION.
  
 38) P.7.04: PROVIDE AN ENLARGED WATER FILTRATION PIPING
 DETAIL SHOWING SUPPLY CONNECTION TO THE FILTER, AND
 SUPPLY LINES TO FIXTURES AND EQUIPMENT REQUIRING
 FILTRATION. PLEASE NOTE THAT BACKFLOW PREVENTERS ARE
 REQUIRED FOR THE WATER SUPPLY LINES IN AND OUT OF THE
 FILTER- SECTION 608.3 FBC P.
  
 39) PLEASE NOTE THAT ALL REQUESTED MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION MANUALS FOR FIXTURES,
 APPLIANCES, AND EQUIPMENT MAY BE DEFERRED IN ACCORDANCE
 WITH SECTION 107.3.4.1 WPB. PLEASE NOTE THAT ALL
 DEFERRED SUBMITTALS SHALL BE LISTED ON THE PLAN.
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY
 SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED
 AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF
 THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  