| 2021-08-20 09:00:01 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21070675 |
| | 8/19/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR |
| | THE INSTALLATION OF THE , GREASE AND SOLIDS |
| | INTERCEPTORS, LIFT STATION, UNDERGROUND FIRE LINE, |
| | POTABLE WATER SERVICE BACKFLOW PREVENTER, IRRIGATION |
| | SERVICE BACKFLOW PREVENTER, FIRE LINE BACKFLOW |
| | PREVENTER, FIRE SPRINKLER, AND GAS-FIRED GENERATOR- |
| | SECTIONS 105.1 & 107.2.1 WPB. |
| | |
| | 2) PROVIDE IRRIGATION PLANS OR INDICATE THE PLANS WILL |
| | BE SUBMITTED UNDER A SEPARATE PERMIT APPLICATION- |
| | SECTION 105.1 & 107.2.1 WPB. |
| | |
| | 3) SHEET ALS.1.0 CODE DATA & PLUMBING FIXTURE REQ'S: |
| | THE LIFE SAFETY OCCUPANT LOAD AND FIXTURE CALCULATIONS |
| | ARE LACKING THE SQUARE FOOTAGES AND OCCUPANT LOADS OF |
| | EACH OF THE BUILDING AREAS (A2, M, B, & S). PLEASE NOTE |
| | THAT CODE SECTION 506.1.3 FBC B WHICH IS CALLED OUT IN |
| | THE DATA PERTAINS TO ALLOWABLE AREA FOR THE BUILDING |
| | AND DOES NOT EXCLUDE PLUMBING FIXTURE CALCULATIONS FOR |
| | THE BASEMENT AREAS. A COMPLETE REVIEW OF THE PLUMBING |
| | CANNOT BE COMPLETELY WITHOUT ACCURATE OCCUPANCY LOAD |
| | CALCULATIONS FOR EACH AREA OF THE BASEMENT AND GROUND |
| | FLOOR. THE RESTROOMS SHALL BE LABELED AS EITHER MALE OR |
| | FEMALE- TABLE 403.1 & SECTION 403.2 FBC P.THE PLANS |
| | SHOW FOUR RESTROOMS (TWO IN THE BASEMENT AND TWO ON THE |
| | FIRST FLOOR) THAT ARE NOT LABELED- SEE SECTION 403.1.2. |
| | A) ALS.1.0: REFER TO SECTION 403.1.4 FBC P AND INCLUDE |
| | THE OUTDOOR SEATING WITH THE CALCULATIONS. |
| | |
| | B) ALS.1.0: REFER TO SECTION 403.3 FBC P AND DESIGNATE |
| | THE REQUIRED EMPLOYEE TOILET FACILITIES AS EITHER |
| | SEPARATE OR COMBINED EMPLOYEE AND PUBLIC TOILET |
| | FACILITIES. PLEASE PROVIDE A BREAKDOWN CALCULATION FOR |
| | EMPLOYEES THAT INCLUDES THE GOLF CART GARAGE, CADDY |
| | LOUNGE, BEVERAGE AREA ETC. |
| | |
| | C) ALS.1.0: DRINKING FOUNTAINS ARE REQUIRED FIXTURES |
| | FOR MERCANTILE, BUSINESS, AND STORAGE OCCUPANCIES. |
| | EXCEPTION 410.4 IS CALLED OUT IN THE TABLE HOWEVER |
| | SECTION 410.4 SUBSTITUTION OF DRINKING WATER IN A |
| | CONTAINER FREE OF CHARGE APPLIES ONLY TO THE RESTAURANT |
| | AREA. |
| | |
| | 4) A9.01: MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS |
| | PER FBC ACC: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | G) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | H) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2 |
| | I) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR A |
| | FORWARD OR PARALLEL APPROACH TO THE SINK IN THE LOUNGE- |
| | 606.2. KNEE AND TOE CLEARANCES FOR FORWARD APPROACHES- |
| | SECTION 606.2 |
| | J) LOUNGE SINK HEIGHT FROM THE FINISHED FLOOR TO THE |
| | RIM OF THE SINK- 606.3. NOTE- THE DRAWING SHOWS THE |
| | MEASUREMENT TO THE COUNTER. |
| | K) REACH RANGES AND OPERABLE PARTS FOR THE COFFEE |
| | MAKER- 308. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | TO VERY COMPLIANCE. |
| | |
| | 5) A9.1.2: MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS |
| | PER FBC ACC: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE |
| | WATER CLOSET- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE |
| | LAVATORY- SECTION 606.2. |
| | C) TURNING SPACE DIAMETER- SECTION 304.3. |
| | D) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED |
| | FLOOR- SECTION 604.4. |
| | E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROL- SECTION |
| | 604.6. |
| | G) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| | FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE |
| | 604.7. |
| | H) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION |
| | 606.2 |
| | |
| | 6) A9.1.3: MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS |
| | PER FBC ACC: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE |
| | WATER CLOSET- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE |
| | LAVATORY- SECTION 606.2. |
| | C) TURNING SPACE DIAMETER- SECTION 304.3. |
| | D) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROL- SECTION |
| | 604.6. |
| | G) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| | FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE |
| | 604.7. |
| | H) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION |
| | 606.2. |
| | I) CLEAR INSIDE DIMENSIONS FOR THE ACCESSIBLE SHOWER- |
| | SECTION 608.2.1 |
| | J) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | ACCESSIBLE SHOWER- 608.2.1. |
| | K) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWER 608.3 AND 608.3.1 |
| | L) SHOW THE LOCATION OF THE SHOWER CONTROL AND SPRAY IN |
| | ACCORDANCE WITH FIGURE 608.5.1. |
| | M) SHOWER SPRAY UNIT SPECIFICATIONS- 608.6. |
| | N) PROVIDE THE ACCESSIBLE SHOWER SEAT HEIGHT AND |
| | MOUNTING DETAILS- 610.3 & 610.3.2. & FIGURE 610.3.2. |
| | |
| | 7) A9.1.5, A9.1.6 & A9.1.7: MISSING ACCESSIBLE PLUMBING |
| | FIXTURE DETAILS PER FBC ACC: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SECTION 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| | FROM THE FINISHED FLOOR- SECTION 606.3. |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2.LI) CLEAR INSIDE DIMENSIONS FOR THE ACCESSIBLE |
| | SHOWERS- SECTION 608.2.2. |
| | L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | ACCESSIBLE SHOWER- 608.2.2.1. |
| | M) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWER- 608.3.2. |
| | N) LOCATION OF THE SHOWER CONTROL AND SPRAY- 608.5.2 |
| | O) SHOWER SPRAY UNIT SPECIFICATIONS- 608.6. |
| | |
| | 8) A9.1.5: SHOW THE DEPTH MEASUREMENTS OF THE STANDARD |
| | WATER CLOSET COMPARTMENTS- SECTION 405.3.1 FBC P. |
| | |
| | 9) A9.1.8 & A9.1.9: MISSING ACCESSIBLE PLUMBING FIXTURE |
| | DETAILS PER FBC ACC: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SECTION 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| | FROM THE FINISHED FLOOR- SECTION 606.3. |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2. |
| | I) CLEAR INSIDE DIMENSIONS FOR THE ACCESSIBLE SHOWERS- |
| | SECTION 608.2.2. |
| | J) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | ACCESSIBLE SHOWER- 608.2.2.1. |
| | K) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWER- 608.3.2. |
| | L) LOCATION OF THE SHOWER CONTROL AND SPRAY- 608.5.2 |
| | M) SHOWER SPRAY UNIT SPECIFICATIONS- 608.6. |
| | N) ACCESSIBLE URINAL- SHOW THE LOCATION(S), PROVIDE THE |
| | CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS, PROVIDE THE |
| | RIM HEIGHT FROM THE F.F., AND THE URINAL DEPTH- |
| | SECTIONS 213.3 & 605.2 FBC ACC. |
| | |
| | 10) A9.1.8: SHOW THE DEPTH MEASUREMENTS OF THE STANDARD |
| | WATER CLOSET COMPARTMENTS- SECTION 405.3.1 FBC P. |
| | |
| | 11) A9.1.5 & A9.1.8: IN ACCORDANCE WITH SECTION 213.3.1 |
| | FBC ACC, AMBULATORY TOILET COMPARTMENT STALLS ARE |
| | REQUIRED FOR THE MEN'S (138) AND WOMEN'S (148) |
| | BATHROOMS. PLEASE SEE SECTIONS 604.8.2- 604.8.2.3 AND |
| | REVISE THE PLANS AND DETAILS ACCORDINGLY. |
| | |
| | 12) P1.1.0 SAND/OIL INTERCEPTOR (SOI-1): A) SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | INSTRUCTIONS- SECTION 1003.4.2 FBC P. B) LABEL THE |
| | ACCESS COVER AND RATED TRAFFIC LID- 1003.10, 1003.11 & |
| | 305.7. C) PROVIDE SIZING CALCULATIONS IN ACCORDANCE |
| | WITH SECTION 1003.4.2.1 OR PER MANUFACTURER'S |
| | SPECIFICATIONS. |
| | |
| | 13) P1.1.0 LINT TRAP (LI-1): A) SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS- SECTION |
| | 1003.6 FBC P. |
| | |
| | 14) P1.1.0 STORM SUMP PUMP: A) SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS- SECTION |
| | 1113.1 FBC P. B) PROVIDE PUMP SIZING CALCS AND PUMP |
| | CURVE- 1113.1.1 C) PROVIDE AN ENLARGED INSTALLATION |
| | DETAIL SHOWING THE SUMP PIT DIMENSIONS, PIT MATERIALS, |
| | LOCATIONS OF VALVES, ACCESS TO VALVES, AND TRAFFIC |
| | RATED COVER- 1113.1.2. (DETAIL ON P5.02 IS INCOMPLETE) |
| | .D) SHOW THE LOCATION AND SIZE OF REQUIRED VENT- |
| | 1113.1.4 |
| | |
| | 15) P.1.1.0: PROVIDE A NOTE AND GPM FLOW FOR THE STORM |
| | DRAIN PIPE BY THE SOUTH ENTRY DOOR- SECTION 1106.2 FBC |
| | P. |
| | |
| | 16) P1.1.0, C2 & C2.1: SHOW THE DRAINAGE PIPING |
| | CONNECTIONS FOR THE TRENCH DRAINS (TD-1) LOCATED AT THE |
| | BAY DOORS. IF CONNECTING TO THE CITY STORM DRAINAGE |
| | SYSTEM, REFER TO SEC. 90-203 WPB CODE OF ORDINANCES AND |
| | VERIFY THAT THE DRAINS WILL CONVEY ONLY STORM WATER |
| | INTO THE SYSTEM. PLEASE NOTE THAT IT IS UNLAWFUL FOR |
| | ANY OTHER SUBSTANCES TO DISCHARGE INTO THE SYSTEM |
| | UNLESS MEETING ONE OF THE EXCEPTIONS UNDER SEC. 90- 205 |
| | WPB. |
| | |
| | 17) P1.1.0 SANITARY BACKWATER VALVE: A) SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS |
| | INSTRUCTIONS- SECTIONS 715.2- 715.4. B) PROVIDE AN |
| | INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS |
| | 715.5 & 305.7. |
| | |
| | 18) P1.1.0: PLACE A NOTE TO INDICATE NON-POTABLE WATER |
| | SIGNAGE WILL BE PROVIDED AT THE HB-1 LOCATION IN |
| | ACCORDANCE WITH SECTION 608.8.1 FBC P. |
| | |
| | 19) P1.1.1 GREASE INTERCEPTOR G1-1: A) SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS |
| | INSTRUCTIONS- SECTION 1003.3.4 FBC P. B) PROVIDE SIZING |
| | CALCULATIONS- 1003.3.4. C) PROVIDE AN ENLARGED |
| | SITE-SPECIFIC PIPING DRAWING- SECTION 107.2.1 WPB. D) |
| | PLEASE NOTE ONLY FIXTURES DISCHARGING GREASE LADEN |
| | WASTE WATER SHALL FLOW INTO THE GREASE INTERCEPTOR. |
| | CLEAR WATER WASTE FROM HAND SINKS, ICE MACHINES ETC. |
| | SHALL NOT DRAIN INTO THE SYSTEM- SECTION 1003.3.1 FBC |
| | P. |
| | |
| | 20) P1.1.1 SOLIDS INTERCEPTOR S1-1: A) SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS |
| | INSTRUCTIONS- SECTION 1003.3.2 FBC P. B) PROVIDE SIZING |
| | CALCULATIONS- 1003.3.4. C) PROVIDE AN ENLARGED |
| | SITE-SPECIFIC PIPING DRAWING- SECTION 107.2.1 WPB. |
| | |
| | 21) P1.1.1 SAMPLING PORT (SP-1): A) SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS |
| | INSTRUCTIONS- SECTION 1003.3.2 FBC P. B) PROVIDE AN |
| | ENLARGED SITE-SPECIFIC PIPING DRAWING- SECTION 107.2.1 |
| | WPB. |
| | |
| | 22) P1.1.1: PROVIDE NOTES AT THE TERMINATION LOCATIONS |
| | OF THE GREASE WASTE AND SANITARY SEWER LINES OR SHOW |
| | THE POINTS OF CONNECTIONS TO THE SEWER LINE- SECTION |
| | 107.2.1 WPB. |
| | |
| | 23) P1.1.1 STORM WATER BACKWATER VALVE: A) SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS |
| | INSTRUCTIONS- SECTIONS 715.2- 715.4. B) PROVIDE AN |
| | INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS |
| | 715.5 & 305.7. |
| | |
| | 24) P2.01: PROVIDE ROOF DRAINAGE PLANS AND A STORM |
| | DRAIN ISOMETRIC DRAWING- SECTION 107.3.5.1.3 FBC P. |
| | PLEASE NOTE THAT SEPARATE SYSTEMS ARE REQUIRED FOR |
| | PRIMARY AND SECONDARY (OVERFLOW) DRAINS- SECTION 1108.1 |
| | FBC P. PLEASE SHOW THE PRIMARY AND SECONDARY SYSTEM |
| | DISCHARGE LOCATION(S). A) SHEET A2.01 SCHEDULE |
| | INCORRECTLY LISTS AREA 07 AS 02- SECTION 107.2.1 WPB. |
| | B) PROVIDE ROOF DRAIN AND OVERFLOW DRAIN INSTALLATION |
| | DETAILS- SECTIONS 1102.6 & 1105.1 C) PROVIDE GUTTER AND |
| | DOWNSPOUT INSTALLATION DETAILS INCLUDING DOWNSPOUT |
| | VERTICAL LEADERS TO UNDERGROUND STORM DRAIN |
| | CONNECTIONS- 1101.6, 1102.7. |
| | |
| | 25) P4.01: PROVIDE CONDENSATE DISPOSAL DETAILS FOR THE |
| | TANKLESS WATER HEATERS- SECTION 314.1 FBC P. SEE GAS |
| | REVIEW COMMENTS FOR ADDITIONAL GAS WATER HEATER CODE |
| | REQUIREMENTS. |
| | |
| | 26) P4.01, P7.02: THE GW FIXTURE DRAIN FROM THE MOP |
| | SINK IS SHOWN TO BE CONNECTING TO THE SANITARY DRAIN- |
| | SECTION 1003.3.1 FBC P. |
| | |
| | 27) P4.01, P4.02, P7.01, P7.02, K7, K8, & K9: CLEAR |
| | WATER WASTE DRAINAGE FROM HAND SINKS AND WASTE |
| | RECEPTORS AT ICE BIN AND ICE MAKER LOCATIONS ARE SHOWN |
| | DISCHARGING INTO THE GW LINE WHICH IS PROHIBITED- |
| | SECTION 1003.3.1 FBC P. |
| | |
| | 28) P4.01 & K7: CONDENSATE FROM THE WALK-IN BOX |
| | EVAPORATORS SHALL NOT DRAIN INTO THE CITY SANITARY |
| | SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES. |
| | |
| | 29) P4.01 & P4.02: INDICATE TEMPERED WATER IS BEING |
| | SUPPLIED TO LAVATORIES L-1, L-2, & L-3- SECTION 419.5 |
| | FBC P. |
| | |
| | 30) P7.01: THE RISER IS LABELED AS BASEMENT WASTE AND |
| | VENT RISER, HOWEVER THE 1ST FLOOR GREASE WASTE/VENT |
| | RISER IS ALSO SHOWN- SECTION 107.2.1 WPB. |
| | |
| | 31) P7.01: THE 2-INCH WASTE STACKS FOR THE WASHING |
| | MACHINES ARE UNDERSIZED. MINIMUM 3-INCH STACKS ARE |
| | REQUIRED- SECTION 406.2 FBC P. |
| | |
| | 32) P7.02: TD-2 AND SH-2 IN THE MEN'S BATHROOM DO NOT |
| | APPEAR TO BE VENTED PROPERLY. PLEASE CLARIFY HOW THE |
| | FIXTURES ARE BEING VENTED- SECTION 901.2.1 FBC P. |
| | |
| | 33) P7.01 & P7.02: INDICATE HOW TRAP SEAL PROTECTION |
| | WILL BE PROVIDED FOR FLOOR DRAINS AND OTHER TRAP SEALS |
| | SUBJECT TO EVAPORATION WILL BE PROTECTED- SECTION |
| | 1002.4.1 FBC P. |
| | |
| | 34) P7.03, P7.04, K9: REQUIRED BACKFLOW PREVENTERS NOT |
| | SHOWN FOR SUPPLY LINES TO THE PIZZA OVEN, DISHWASHERS, |
| | COFFEE BREWER, ICED TEA BREWER, GLASS FILLER STATION, |
| | ICE AND SODA DISPENSER, SODA SYSTEM, HOT FOOD WELL, ICE |
| | MAKER, ICE BIN, WATER FILTRATION SYSTEM, BLENDER |
| | STATION, AND THE REF IMB-1- SECTION 608.3. FBC P. |
| | |
| | 35) P7.03 & P7.04: PROVIDE A SHUTOFF VALVE AT THE TOP |
| | OF THE COLD WATER DOWN FEED PIPE FROM FIRST TO BASEMENT |
| | FLOOR- SECTION 606.1 (5) FBC P. |
| | |
| | 36) P7.03 & P7.04: SHOW THE LOCATIONS OF WATER HAMMER |
| | ARRESTORS FOR SUPPLY LINES TO FLUSH VALVES, WASHING |
| | MACHINES, DISHWASHERS, AND OTHER FIXTURES AND EQUIPMENT |
| | WITH QUICK CLOSING VALVES- SECTION 604.9 FBC P. |
| | |
| | 37) P7.04: PROVIDE AN ENLARGED PIPING DIAGRAM FOR |
| | INSTALLATION OF THE WATER HEATERS AND RECIRCULATION |
| | PUMPS SHOWING COMPLIANCE WITH 607.2.2 FBC P. SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS FOR THE PUMPS SHOWING |
| | COMPLIANCE WITH SECTION 607.2.1.2 ITEMS 1 & 2 FBC P- |
| | CONTROLS OPERATION. |
| | |
| | 38) P.7.04: PROVIDE AN ENLARGED WATER FILTRATION PIPING |
| | DETAIL SHOWING SUPPLY CONNECTION TO THE FILTER, AND |
| | SUPPLY LINES TO FIXTURES AND EQUIPMENT REQUIRING |
| | FILTRATION. PLEASE NOTE THAT BACKFLOW PREVENTERS ARE |
| | REQUIRED FOR THE WATER SUPPLY LINES IN AND OUT OF THE |
| | FILTER- SECTION 608.3 FBC P. |
| | |
| | 39) PLEASE NOTE THAT ALL REQUESTED MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION MANUALS FOR FIXTURES, |
| | APPLIANCES, AND EQUIPMENT MAY BE DEFERRED IN ACCORDANCE |
| | WITH SECTION 107.3.4.1 WPB. PLEASE NOTE THAT ALL |
| | DEFERRED SUBMITTALS SHALL BE LISTED ON THE PLAN. |
| | |
| | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY |
| | SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE |
| | BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED |
| | AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF |
| | THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |