Plan Review Notes
Plan Review Notes For Permit 21070675
Permit Number 21070675
Review Stop M
Sequence Number 1
Notes
Date Text
2021-08-19 06:05:181ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21070675
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1.0: PLEASE IDENTIFY WHICH IS DRYERS AND
 WHICH ARE WASHING MACHINES. PLEASE ALSO PROVIDE THE
 COMMERCIAL CLOTHES DRYER INSTALLATION INSTRUCTIONS FOR
 THE DRYER EXHAUST DUCT. FBC M 504.9
  
 2) PLEASE ADD STATEMENT TO DRAWINGS THAT THE
 REFRIGERATION WILL NOT BE REVIEWED ON THIS PERMIT. THE
 REFRIGERATION WILL REQUIRE A SEPARATE PERMIT
 APPLICATION, REVIEW AND DRAWINGS SUBMITTED.
  
 3) PLEASE ADD STATEMENT TO DRAWINGS THAT THE KITCHEN
 HOODS WILL NOT BE REVIEWED ON THIS PERMIT. THE KITCHEN
 HOODS WILL REQUIRE A SEPARATE PERMIT APPLICATION,
 REVIEW AND DRAWINGS SUBMITTED.
  
 4) SHEET M1.1.0: PLEASE PROVIDE THE EXHAUST
 CALCULATIONS FOR THE EXHAUST AIR FOR THE CART PARKING
 GARAGE. FBC M 404
  
 5) SHEET M1.1.1: PLEASE IDENTIFY THE RTU?S FOR EACH
 DUCT SYSTEM( EXAMPLE THE DUCT WORK CONDITIONING THE
 DINING AREA IS SERVED FROM WHICH RTU?) FBC 107.2.1
  
 6) SHEET M1.1.1: PLEASE SHOW THAT THE MEN?S BATHROOM
 EXHAUST INCLUDES THE URINALS. FBC M TABLE 403.3.1.1
 FOOTNOTE (E).
  
 7) SHEET M1.1.1: PLEASE LABEL EXHAUST FANS FOR EACH
 EXHAUST DUCT SERVED. FBC 107.2.1
  
 8) SHEET M1.1.2: PLEASE SHOW ROOF ACCESS TO WORK ON THE
 MECHANICAL UNITS. FBC 306.5
  
 9) PLEASE SHOW THE CONDENSATE DISPOSAL PIPING AND
 TERMINATION LOCATIONS. FBC M 307
  
 10) SHEET M1.1.1: PLEASE SHOW THAT THE MECHANICAL
 EQUIPMENT ON THE ROOF MEETS THE 10 FEET CLEARANCE OR
 HAS GUARDS. FBC M 304.11
  
 11) SHEET M6.0.1: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS FOR ALL AREAS IN THIS NEW BUILDING BASED
 ON FBC 403.3.1.1 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  