Plan Review Notes
Plan Review Notes For Permit 21070675
Permit Number 21070675
Review Stop G
Sequence Number 1
Notes
Date Text
2021-08-20 16:32:221ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21070675
 8/20/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUALS FOR THE WATER HEATERS AND DIRECT
 VENT SYSTEM, COOKING APPLIANCES, DRYERS, REGULATORS,
 SOLENOID VALVES- SECTION 305.1, 623.1, & 624.1 FBC FG,
 AND 107.2.1 WPB.
  
 2) PLACE A NOTE ON THE PLAN TO INDICATE THE GENERATOR
 WILL BE INSTALLED UNDER A SEPARATE PERMIT- SECTIONS
 105.1 & 107.2.1 WPB. THE CURRENT REVIEW UNDER THIS MAIN
 PERMIT IS LIMITED TO THE GAS PIPING RUN TO THE
 GENERATOR. SUBMITTAL OF A CUT SHEET SHOWING THE
 GENERATOR GAS LOADS AND INPUT PRESSURE WOULD BE HELPFUL
 FOR REVIEW OF GAS PIPE SIZING.
  
 3) SHEET P4.01: PROVIDE A KEYNOTE AT THE GAS LINE
 CONTINUATION TO THE GENERATOR AND INDICATE THE TYPE OF
 PIPING TO BE INSTALLED- SECTION 401.8 & 402.1 FBC FG
 AND SECTION 107.2.1 WPB. PROVIDE AN ENLARGED GAS PIPING
 LAYOUT DRAWING FOR THE AREA OF THE BUILDING SHOWING THE
 GAS PIPING RUN TO THE GENERATOR.
  
 4) P4.01 & P7.05: THE GAS SUPPLY PIPE TO THE GENERATOR
 SHALL BE CONNECTED ON THE SUPPLY SIDE OF THE MAIN GAS
 SHUTOFF VALVE TO THE BUILDING AND BE MARKED AS
 SUPPLYING AN EMERGENCY GENERATOR- SECTION 7.9.7 NFPA
 110.
  
 5) P4.01, P4.02 & P7.05: CLARIFY IF THE REGULATORS ARE
 EQUIPPED WITH LISTED AND LABELED VENT LIMITING DEVICES,
 OR PROVIDE VENTING DETAILS INCLUDING THE TYPES AND
 SIZES OF VENT PIPING, VENT PIPING RUNS AND DISCHARGE
 LOCATIONS- SECTIONS 410.3 & 410.3.1 FBC FG.
  
 6) P4.01, P4.02 & P7.05: PLACE NOTES TO INDICATE ALL
 SHUTOFF VALVES INCLUDING THE SOLENOID VALVES WITH
 MANUAL RESETS ARE IN ACCESSIBLE LOCATIONS- SECTION
 409.1.3 FBC FG.
  
 7) P4.01 & P7.05: PLACE A NOTE TO INDICATE THE SOLENOID
 VALVE SHOWN AT THE COOKING LINE MEETS COMPLIANCE WITH
 SECTION 10.4.1 NFPA 96: AN AUTOMATIC GAS SHUTOFF VALVE
 IS REQUIRED TO BE CONNECTED TO THE HOOD FIRE
 SUPPRESSION SYSTEM.
  
 8) P4.01 & P7.05: SHOW THE LOCATION OF THE AUTOMATIC
 GAS VALVE FOR THE GAS LINE SERVICE COOKING APPLIANCES
 PK39, PK40 & PK41- SECTION 10.4.1 NFPA 96.
  
 9) P4.01 & P7.05: PROVIDE A NOTE ON P4.01 TO SHOW THE
 LOCATION OF THE GAS PIPING DROP TO THE DRYERS IN THE
 BASEMENT AND PROVIDE A GAS PIPING FLOOR PLAN LAYOUT
 DRAWING- SECTIONS 107.2.1 & 107.3.5.1.5 WPB.
  
 10) P7.05: SHOW THE BRANCH LENGTHS AND CUT PIPE LENGTH
 MEASUREMENTS ON THE RISER INCLUDING BRANCH AND TOTAL
 LENGTHS FROM SECONDARY REGULATORS TO APPLIANCE AND
 EQUIPMENT OUTLETS- SECTIONS 402.4.1 & 402.4.2 FBC FG.
  
 11) P7.05: PROVIDE REGULATORS AT THE GAS DRYER AND
 GENERATOR LOCATIONS- SECTIONS 410.2 FBC FG.
  
 12) P7.05: SHOW THE LOCATIONS OF REQUIRED TEE FITTINGS
 AT REGULATOR LOCATIONS OR PROVIDE A NOTE TO ENSURE
 COMPLIANCE- SECTION 410.2(5,6) FBC FG.
  
 13) P7.05: SHOW THE LOCATIONS OF REQUIRED PIPE UNIONS
 AT REGULATOR LOCATIONS OR PROVIDE A NOTE TO ENSURE
 COMPLIANCE- SECTION 410.2(7) FBC FG.
  
 14) P7.05 & P.1.1.1: BASED ON SHEET P1.1.1 IT APPEARS
 THE GAS PIPING TO THE GENERATOR MAY BE RUNNING
 UNDERGROUND. P1.1.1 SHOWS THE PIPING CROSSING IN FRONT
 OF THE ENTRY DOOR TO THE WATER ROOM. PLEASE PLACE NOTES
 ON THE RISER TO CLARIFY AND PROVIDE COMPLIANCE DETAILS
 FOR UNDERGROUND PIPING- SECTIONS 404.6 & 404.11 FBC FG.
 IF THE PIPING IS PE PLEASE PROVIDE INSTALLATION AND
 RISER DETAILS, AND THE PIPE SIZING TABLE TO BE USED-
 SECTION 402.4 FBC FG.
  
 15) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES AND INDICATE HOW THE AIR
 WILL BE PROVIDED- SECTION 304.1 FBC FG
  
 16) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED DRYERS AND INDICATE HOW THE AIR WILL BE
 PROVIDED- SECTION 304.1 FBC FG.
  
 17) PROVIDE A GAS DRYER EXHAUST DIAGRAM INDICATING THE
 TYPE AND SIZE OF EXHAUST DUCT, TOTAL RUN LENGTH AND
 TERMINATION LOCATION- SECTION 614.1 FBC FG. SHOW THE
 LOCATION OF REQUIRED CLEANOUTS- 614.3 AND PROVIDE
 TERMINATION CAP DETAILS- 614.4.
  
 18) PLEASE NOTE THAT ALL REQUESTED MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION MANUALS FOR FIXTURES,
 APPLIANCES, AND EQUIPMENT MAY BE DEFERRED IN ACCORDANCE
 WITH SECTION 107.3.4.1 WPB. ALL DEFERRED SUBMITTALS
 SHALL BE LISTED ON THE PLAN.
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY
 SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED
 AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF
 THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.