Plan Review Notes
Plan Review Notes For Permit 21070675
Permit Number 21070675
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-07-23 16:32:25THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 THERE ARE NO INDICATIONS OF A MONITORED FIRE SPRINKLER
 SYSTEM. THE LIFE SAFETY CODE REQUIRES THAT THE FIRE
 SPRINKLER SYSTEM BE MONITORED.
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING
 COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE
 COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR AND
 SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, ARE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE
 FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
 ALL WORK ON THE FKITCHEN SUPPRESSION SYSTEM IS REQUIRED
 TO BE COMPLETED BY A CERTIFIED FCONTRACTOR AND SHALL
 COMPLY WITH NFPA 96. SEPARATE SHOP DRAWINGS, ARE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE
 FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
  
 PLEASE ADDRESS FIRE PROTECTION AND NOTIFICATION SYSTMS
 IN MASTER PERMIT ACCORDING TO FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]