| 2021-08-19 15:02:44 | NEW BUILDING - CLUBHOUSE AND PRO SHOP |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | 1) DRAWING S4.1.C SHOWS BUILDING WIND DESIGN RISK |
| | CATEGORY III WITH WIND SPEED OF 170MPH - WIND SPEED FOR |
| | A RISK CATEGORY III BUILDING SHOULD BE 180MPH PER FBC |
| | WPB SECTION 120. |
| | 2) PLEASE PROVIDE A SOIL REPORT AS STATED IN THE NOTES |
| | ON DRAWING S4.1.C |
| | 3) PLEASE SHOW THE TYPE OF WATER PROOFING FOR THE |
| | BASEMENT WALLS FBC 1805.2.2 |
| | 4) DRAWING A6.0.1 DETAIL 3 AND 1 - THE HAND RAIL |
| | EXTENSION AT THE BOTTOM SHALL CONTINUE TO SLOPE DOWN |
| | THE WIDTH OF THE STAIR TREAD FBC 1014.6 |
| | 5) DRAWING A6.0.2 DETAIL 1 HANDRAIL EXTENSIONS AT THE |
| | BOTTOM SHALL CONTINUE TO SLOPE DOWN FOR THE LENGTH OF |
| | THE STAIR TREAD. FBC 1014.6 |
| | 6) DRAWING A6.0.2 DETAIL 4 HANDRAIL EXTENSION SHALL |
| | EXTEND 12" PAST THE TOP RISER FBC 1014.6 |
| | 7) PLEASE SHOW THE ACCESSIBLE SEATING IN EACH OF THE |
| | DINING AREAS PER FBC 226.1 |
| | 8) PLEASE SHOW THE ACCESSIBLE INSIDE AND PATIO BAR |
| | SEATING COUNTER HEIGHT, CLEAR FLOOR SPACE, KNEE AND TOE |
| | CLEARANCE TO COMPLY WITH FBC 902 |
| | 9) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET REAR |
| | GRAB BAR LOCATION DIMENSIONS FROM THE CENTER OF THE |
| | TOILET PER FBC 604.5.2 |
| | 10) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER |
| | HOLDER LOCATION FROM THE FACE OF THE TIOLET TO COMPLY |
| | WITH FBC 604.7 |
| | 11) ACCESSIBLE RESTROOM - PLEASE NOTE THE MIRROR |
| | MAXIMUM HEIGHT FROM THE FLOOR TO THE "REFLECTIVE |
| | SURFACE" PER FBC 603.3 |
| | 12) ACCESSIBLE SHOWERS - PLEASE SHOW THE GRAB BAR |
| | LOCATION DIMENSIONS TO COMPLY WITH FBC 608.3.2 AND |
| | 609.4 |
| | 13) ACCESSIBLE SHOWERS - PLEASE SHOW THE DIMENSIONS FOR |
| | THE SEAT PER FBC 610.3 |
| | 14) PLEASE SHOW THE ACCESSIBLE ROUTE TO THE BASEMENT - |
| | ROUTE, SLOPE, CROSS SLOPE ETC PER FBC 402.2 |
| | 15) PRODUCT APPROVAL PROVIDED FOR THE ROOF TILE - |
| | PLEASE CIRCLE THE TYPE OF TILE ATTACHMENT TO BE USED IN |
| | THE PRODUCT APPROVAL IF USING ADHESIVE PLEASE PROVIDE |
| | THE PRODUCT APPROVAL FOR THE ADHESIVE. |
| | 16) CIVIL PLANS SHOW PROPERTY IN AN "X" AND "AE 14.8" - |
| | PLEASE CLEARLY SHOW THE FLOOD ZONE DELINEATION LINES - |
| | ARE ANY OF THE BUILDINGS IN THE "AE 14.8" FLOOD ZONE? |
| | |