| 2021-08-13 09:01:31 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21070600 |
| | 8/13/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. IN RESAPONSE TO COMMENTS |
| | #2 & #3 PRINTED BELOW THE ARCHTECT OF RECORD STATES IN |
| | HIS NARRATIVE RESPONSE: "THE TEMPORARY TRAILER IS |
| | UTILIZED TO SUPPLEMENT CRITICAL MEDICAL MODALITIES (CT, |
| | MRI, X-RAY, ETC.) AND NOT AS AN OFFICE OR A PLACE OF |
| | DWELLING. SEE ATTACHED TRAILER PLAN SHOWING NO PLUMBING |
| | FIXTURES IN THIS TRAILER. PLUMBING SUPPLY IS BEING |
| | PROVIDED FOR ANY FUTURE TRAILER THAT MAY HAVE PLUMBING |
| | REQUIREMENTS". THE PLUMBING PLAN SHEET P1.1 HOWEVER IS |
| | INDICATING WATER LINE AND SANITARY DRAIN CONNECTIONS TO |
| | THE TRAILER. PLEASE CLARIFY THE NEED FOR WATER SUPPLY |
| | AND DRAIN CONNECTIONS TO THE TRAILER IF THERE ARE NO |
| | PLUMBING FIXTURES. |
| | |
| | 2) A0.0 & P1.1 PLUMBING FIXTURE CALCULATIONS: PROVIDE A |
| | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED |
| | NUMBER OF FIXTURES FOR THE TRAILER IN ACCORDANCE WITH |
| | TABLE 403.3 FBC P AND SHOW THEIR LOCATIONS. PLEASE NOTE |
| | THAT SECTION 102.2 WPB DOES NOT EXEMPT THE TRAILER FROM |
| | MEETING THE PLUMBING CODE. THE FIXTURES SHALL BE |
| | PROVIDED FOR BOTH PUBLIC AND STAFF USE- SECTION 403.3 |
| | FBC P. |
| | |
| | 3) P1.1: A COMPLETE PLUMBING REVIEW CANNOT BE COMPLETED |
| | AT THIS TIME BECAUSE THE TRAILER ARCHITECTURAL AND |
| | PLUMBING PLANS HAVE NOT BEEN PROVIDED. IN ACCORDANCE |
| | WITH SECTION 107.2.1 & 107.23.5.1.3 WPB THE TRAILER |
| | PLANS SHALL SHOW: |
| | A) LOCATIONS AND TYPES OF PLUMBING FIXTURES INSTALLED. |
| | B) SOURCE OF HOT WATER WHERE HOT WATER USE IS REQUIRED. |
| | C) WATER AND SANITARY RISER DRAWINGS. |
| | D) FBC ACC FIXTURE COMPLIANCE DETAILS AND DRAWINGS. |
| | |
| | NEW COMMENT. |
| | 1) THE NEW TRAILER SUBMITTAL SHOWS AN AC SYSTEM WHICH |
| | WILL PRODUCE CONDENSATE. PLEASE PROVIDE A CONDENSATE |
| | DISPOSAL PLAN IN COMPLIANCE WITH SECTIONS 314.2 & |
| | 314.2.1 FBC P. PLEASE NOTE THE SANITARY DRAIN AND THE |
| | PARKING LOT ARE NOT APPROVED PLACES OF DISPOSAL- |
| | SECTION 90-126 WPB CODE OR ORDINANCES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |