| Date |
Text |
| 2021-12-09 13:21:17 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT-21070558 |
| | 12/9/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS 2-8 LISTED BELOW |
| | WERE NOT ADDRESSED. THE CORRECTED PLANS WERE NOT |
| | UPLOADED FOR REVIEW. |
| | |
| | 2) P301, P302, & P601: PROVIDE 3-INCH DRAIN STACKS AND |
| | BRANCH DRAINS FOR THE WASHING MACHINES (WM-1)- SECTION |
| | 406.2 FBC P. PLEASE NOTE THE A/P601 STACK CONTINUATION |
| | IS UNDERSIZED. |
| | |
| | 3) P301 & P601: PROVIDE A FLOOR DRAIN FOR THE ICE |
| | MACHINE (IM-1) IF REQUIRED BY MANUFACTURER?S |
| | SPECIFICATIONS (NOT PROVIDED)- SECTION 412.2 FBC P. |
| | |
| | 4) P301 & P601: SHOW THE LOCATION OF THE REQUIRED |
| | CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND |
| | SEWER- SECTION 708.1.2 FBC P. |
| | |
| | 5) P401 & P602: SHOW THE LOCATIONS OF THE MAIN WATER |
| | DISTRIBUTION SHUTOFF VALVES FOR EACH DWELLING UNIT- |
| | SECTION 606.1 (2) (6) FBC P. |
| | |
| | 6) P401, P701, P801: THE RINNAI RUR WATER HEATERS ARE |
| | LISTED FOR INDOOR USE, BUT THE PLAN SHOWS THE UNITS ON |
| | THE EXTERIOR OF THE BUILDING- SECTION 502.1 FBC P. |
| | |
| | 7) P401, P402, P602, P701: THE HWR LINE IS NOT SHOWN IN |
| | THE WATER HEATER DETAIL- SECTION 607.2 FBC P. PLEASE |
| | PROVIDE HOT WATER PIPIE INSULATION DETAILS- THICKNESS |
| | AND R-VALUE- TABLE C403.2.10 FBC EC. |
| | |
| | 8) P701: THE LOCATION OF THE EXPANSION TANK FOR THE |
| | TANKLESS WATER HEATER MUST BE IN ACCORDANCE WITH |
| | MANUFACTURER'S SPECIFICATIONS WHICH HAVE NOT BEEN |
| | PROVIDED- SECTION 502.1 FBC P. PLEASE NOTE THAT |
| | EXPANSION TANKS FOR STORAGE TYPE WATER HEATERS SHALL BE |
| | LOCATED DOWNSTREAM OF ALL CHECK VALVES AND PRESSURE |
| | REDUCING VALVES- SECTION 607.3 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |