| 2021-07-30 12:12:38 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21070558 |
| | 7/30/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P401, P701, P801: THE RINNAI RUR WATER HEATERS ARE |
| | LISTED FOR INDOOR USE, BUT THE PLAN SHOWS THE UNITS ON |
| | THE EXTERIOR OF THE BUILDING- SECTIONS 305.1 & 624.1 |
| | FBC FG. |
| | |
| | 2) P401 & P701: SHOW WH CONDENSATE LINES, |
| | NEUTRALIZATION DEVICE AND CONDENSATE LINE DISPOSAL |
| | LOCATIONS- SECTION 307.2 FBC FG. |
| | |
| | 3) P401 & P701: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE WATER HEATERS- SECTION 624.1 FBC FG. PROVIDE A |
| | BASIC INSTALLATION DIAGRAM ON THE PLAN SHOWING THE |
| | REQUIRED CLEARANCES FROM THE UNITS TO GRADE, OVERHEAD |
| | CONSTRUCTION AND TO THE ADJACENT WINDOW OPENING- WATER |
| | HEATER- SECTIONS 624.1 & 503.8 FBC FG. |
| | |
| | 4) P601 OR P602: PLEASE PROVIDE A GAS RISER DRAWING- |
| | SECTION 107.3.5.1.3 WPB. PLEASE NOTE THE GAS DEMAND |
| | SCHEDULE INDICATES 1-INCH PE BRANCHES TO THE WATER |
| | HEATERS THAT ARE UNDERSIZED USING THE LONGEST LENGTH |
| | METHOD AND THE SPECIFIED SIZING TABLE 402.4(21) FBC FG |
| | AND SECTION 402.4.1 FBC FG. GAS RISER: |
| | |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| | UNIONS. |
| | H) OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | J) PIPE SIZING TABLES. |
| | |
| | 5) SUBMIT CUT SHEETS FOR ALL EQUIPMENT RELATING TO THE |
| | GAS INSTALLATION SUCH AS REGULATORS, AND THE GENERATOR |
| | FLEX CONNECTOR- SECTIONS G2421.2 & G2422.1.2 FBC RES. |
| | |
| | 6) PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR |
| | INSTALLATION OF THE GENERATOR- SECTION 105.1 & 107.2.1 |
| | WPB, HOWEVER, IN ORDER TO PERFORM A COMPLETE GAS REVIEW |
| | AT THIS TIME PLEASE SUBMIT A CUT SHEET FOR THE |
| | GENERATOR SHOWING THE BTUH LOAD AND INPUT PRESSURE- |
| | SECTIONS 305.1 & 402.2 FBC FG. |
| | |
| | 7) SUBMIT A GAS SUB-PERMIT APPLICATION- SECTION 105.1 |
| | WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |