| Date |
Text |
| 2021-08-31 14:17:43 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE ARE INDICATION OF WHAT APPEARS TO BE SHOWER |
| | HANDRAILS; HOWEVER, THERE ARE NO DETAILED INDICATIONS |
| | OF MEETING THE REQUIRMENTS OF THE FIRE CODE. |
| | |
| | PER NFPA 101 |
| | |
| | 32.2.2.7 WHERE BATHTUBS, BATHTUB-SHOWER COMBINATIONS, |
| | OR SHOWERS ARE |
| | PRESENT, GRAB BARS SHALL BE PROVIDED IN ACCORDANCE WITH |
| | THE PROVISIONS |
| | OF 24.2.8. |
| | |
| | 24.2.8.2.1* BATHTUB END WALL VERTICAL GRAB BARS. END |
| | WALL VERTICAL |
| | GRAB BARS FOR BATHTUBS SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING: |
| | (1) VERTICAL GRAB BARS SHALL HAVE A LENGTH OF NOT LESS |
| | THAN 36 IN. |
| | (914 MM). |
| | (2) VERTICAL GRAB BARS SHALL BE LOCATED BETWEEN 24 IN. |
| | (610 MM) AND |
| | 27 IN. (686 MM) ABOVE THE FINISHED FLOOR, MEASURED TO |
| | THE LOWER END. |
| | (3) VERTICAL GRAB BARS SHALL BE INSTALLED AT THE END |
| | THAT IS LEAST OBSTRUCTED |
| | FOR ENTRY AND EGRESS. |
| | (4) VERTICAL GRAB BARS SHALL BE LOCATED BETWEEN 9 IN. |
| | (228 MM) AND |
| | 12 IN. (305 MM) FROM THE OPEN ENTRY AND EGRESS SIDE OF |
| | THE BATHTUB |
| | OR BATHTUB-SHOWER COMBINATION, MEASURED HORIZONTALLY |
| | FROM THE |
| | EXTERIOR PLANE OF THE BATHTUB OR BATHTUB-SHOWER |
| | COMBINATION. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 2) THE PRIMARY MEAND OF ESCAPE FROM THE 2ND FLOOR DOES |
| | NOT APPEAR TO MEET THE REQUIREMENTS OF UNENCLOSED ON |
| | THE 1ST FLOOR. |
| | |
| | THE 1ST FLOOR PORTION HAS TO BE A 1/2 HOUR PROTECTED |
| | ARE WITHOUT FURNITURE. |
| | |
| | 32.2.2.4.2 STAIRS SHALL COMPLY WITH 7.2.2.5.3. |
| | 32.2.2.4.3 THE ENTIRE PRIMARY MEANS OF ESCAPE SHALL BE |
| | ARRANGED SO THAT |
| | OCCUPANTS ARE NOT REQUIRED TO PASS THROUGH A PORTION OF |
| | A STORY ABOVE OR |
| | A STORY BELOW, UNLESS THAT ROUTE IS SEPARATED FROM ALL |
| | SPACES ON THAT STORY |
| | BY CONSTRUCTION HAVING A MINIMUM 1?2-HOUR FIRE |
| | RESISTANCE RATING. |
| | 32.2.2.4.4 IN BUILDINGS OF CONSTRUCTION OTHER THAN TYPE |
| | II(000), |
| | TYPE III(200), OR TYPE V(000), THE SUPPORTING |
| | CONSTRUCTION SHALL BE |
| | PROTECTED TO AFFORD THE REQUIRED FIRE RESISTANCE RATING |
| | OF THE SUPPORTED |
| | WALL. |
| | 32.2.2.4.5 STAIRS THAT CONNECT A STORY AT STREET LEVEL |
| | TO ONLY ONE OTHER |
| | STORY SHALL BE PERMITTED TO BE OPEN TO THE STORY THAT |
| | IS NOT AT STREET LEVEL. |
| | 32.2.2.4.6 IN BUILDINGS THREE OR FEWER STORIES IN |
| | HEIGHT AND PROTECTED |
| | BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 32.2.3.5, |
| | STAIR ENCLOSURES SHALL NOT BE REQUIRED, PROVIDED THAT |
| | THERE STILL REMAINS |
| | A PRIMARY MEANS OF ESCAPE FROM EACH SLEEPING AREA THAT |
| | DOES NOT REQUIRE |
| | OCCUPANTS TO PASS THROUGH A PORTION OF A LOWER FLOOR, |
| | UNLESS THAT ROUTE |
| | IS SEPARATED FROM ALL SPACES ON THAT FLOOR BY |
| | CONSTRUCTION HAVING A MINIMUM |
| | 1?2-HOUR FIRE RESISTANCE RATING. |
| | 32.2.2.4.7 STAIRS SERVING A MAXIMUM OF TWO STORIES IN |
| | BUILDINGS PROTECTED |
| | WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH |
| | 32.2.3.5 SHALL BE PERMITTED TO BE UNENCLOSED. |
| | |
| | ONE OF THE REQUIREMENTS OF THIS CODE TO USE AN |
| | UNENCLOSED STAIR IS WITH PROMPT EVACUATION CAPABILITY. |
| | |
| | THE PROVISIONS OF 32/33.2.2.4.7 PERMIT A TWO-STORY OPEN |
| | STAIR |
| | (AND ITS ASSOCIATED EXPOSURE TO THE AREAS THAT ARE |
| | OCCUPIED OR FURNISHED, |
| | OR BOTH, ON THE GROUND FLOOR) TO SERVE AS PRIMARY MEANS |
| | OF |
| | ESCAPE FOR NEW SMALL FACILITIES AND EXISTING SMALL |
| | FACILITIES (NOT |
| | MORE THAN EIGHT RESIDENTS) WITH PROMPT EVACUATION |
| | CAPABILITY, |
| | PROVIDED THAT THE FACILITY IS SPRINKLERED USING |
| | QUICK-RESPONSE OR |
| | RESIDENTIAL SPRINKLERS. |
| | |
| | 32.1.5 ACCEPTABILITY OF MEANS OF EGRESS OR ESCAPE. NO |
| | MEANS OF |
| | ESCAPE OR MEANS OF EGRESS SHALL BE CONSIDERED AS |
| | COMPLYING WITH THE |
| | MINIMUM CRITERIA FOR ACCEPTANCE, UNLESS EMERGENCY |
| | EVACUATION DRILLS |
| | ARE REGULARLY CONDUCTED USING THAT ROUTE IN ACCORDANCE |
| | WITH THE REQUIREMENTS |
| | OF 32.7.3 |
| | |
| | 3.3.81.2 PROMPT EVACUATION CAPABILITY. THE ABILITY OF A |
| | GROUP TO |
| | MOVE RELIABLY TO A POINT OF SAFETY IN A TIMELY MANNER |
| | THAT IS EQUIVALENT |
| | TO THE CAPACITY OF A HOUSEHOLD IN THE GENERAL |
| | POPULATION. |
| | |
| | A.3.3.81 EVACUATION CAPABILITY. THE EVACUATION |
| | CAPABILITY OF THE |
| | RESIDENTS AND STAFF IS A FUNCTION OF BOTH THE ABILITY |
| | OF THE RESIDENTS TO |
| | EVACUATE AND THE ASSISTANCE PROVIDED BY THE STAFF. IT |
| | IS INTENDED THAT THE |
| | EVACUATION CAPABILITY BE DETERMINED BY THE PROCEDURE |
| | ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. IT IS ALSO INTENDED THAT |
| | THE TIMING OF DRILLS, |
| | THE RATING OF RESIDENTS, AND SIMILAR ACTIONS RELATED TO |
| | DETERMINING THE |
| | EVACUATION CAPABILITY BE PERFORMED BY PERSONS APPROVED |
| | BY OR ACCEPTABLE |
| | TO THE AUTHORITY HAVING JURISDICTION. THE EVACUATION |
| | CAPABILITY CAN |
| | BE DETERMINED BY THE USE OF THE DEFINITIONS IN 3.3.81, |
| | THE APPLICATION OF |
| | NFPA 101A CHAPTER 6, OR A PROGRAM OF DRILLS (TIMED). |
| | EVACUATION DOES NOT INCLUDE THE RELOCATION OF OCCUPANTS |
| | WITHIN A |
| | BUILDING. |
| | WHERE DRILLS ARE USED IN DETERMINING EVACUATION |
| | CAPABILITY, IT IS |
| | SUGGESTED THAT THE FACILITY CONDUCT AND RECORD FIRE |
| | DRILLS SIX TIMES PER |
| | YEAR ON A BIMONTHLY BASIS, WITH A MINIMUM OF TWO DRILLS |
| | CONDUCTED |
| | DURING THE NIGHT WHEN RESIDENTS ARE SLEEPING, AND THAT |
| | THE FACILITY CONDUCT |
| | THE DRILLS IN CONSULTATION WITH THE AUTHORITY HAVING |
| | JURISDICTION. RECORDS |
| | SHOULD INDICATE THE TIME TAKEN TO REACH A POINT OF |
| | SAFETY, DATE AND TIME |
| | OF DAY, LOCATION OF SIMULATED FIRE ORIGIN, ESCAPE PATHS |
| | USED, AND COMMENTS |
| | RELATING TO RESIDENTS WHO RESISTED OR FAILED TO |
| | PARTICIPATE IN THE |
| | DRILLS. |
| | TRANSLATION OF DRILL TIMES TO EVACUATION CAPABILITY IS |
| | DETERMINED AS |
| | FOLLOWS: |
| | (1) 3 MINUTES OR LESS ? PROMPT |
| | (2) OVER 3 MINUTES, BUT NOT IN EXCESS OF 13 MINUTES ? |
| | SLOW |
| | (3) MORE THAN 13 MINUTES ? IMPRACTICAL |
| | EVACUATION CAPABILITY, IN ALL CASES, IS BASED ON THE |
| | TIME OF DAY OR |
| | NIGHT WHEN EVACUATION OF THE FACILITY WOULD BE MOST |
| | DIFFICULT, SUCH AS |
| | WHEN RESIDENTS ARE SLEEPING OR FEWER STAFF ARE PRESENT. |
| | EVACUATION CAPABILITY DETERMINATION IS CONSIDERED SLOW |
| | IF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) ALL RESIDENTS ARE ABLE TO TRAVEL TO CENTRALIZED |
| | DINING FACILITIES WITHOUT |
| | CONTINUOUS STAFF ASSISTANCE. |
| | (2) THERE IS CONTINUOUS STAFFING WHENEVER THERE ARE |
| | RESIDENTS IN THE |
| | FACILITY. |
| | |
| | IT WOULD BE ANTICIPATED THAT THE EVACUATION TIME OF 3 |
| | MINUTES WOULD BE FOR CLIENTS WITH NO OR LIMITED |
| | PHYISCAL/MENTAL DISABILITES. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS OF THE PROPOSED |
| | CLIENTS AND THE ABILITY TO MEET THE PROMPT EVACUATION |
| | OR CORRECT AND ENLCOSE THE STAIT EITHER AT THE TOP OR |
| | THE BOTTOM. |
| | |
| | |
| | |
| | |
| | 3) THERE ARE 2 EXTERIOR DOORS/GATES WITHIN THE EGRESS |
| | TRAVEL PATH LEADING TO A PUBLIC WAY OR POINT OF SAFETY. |
| | |
| | 32.2.2.5.5 NO DOOR IN ANY MEANS OF ESCAPE, OTHER THAN |
| | THOSE MEETING |
| | THE REQUIREMENT OF 32.2.2.5.5.1, 32.2.2.5.5.2, OR |
| | 32.2.2.5.5.3, SHALL BE |
| | LOCKED AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED. |
| | |
| | PLEASE PROVIDE DETAILS INDICATING HOW THESE DOORS/GATES |
| | WILL COMPLY WITH THE CODE. |
| | |
| | |
| | |
| | 4) THERE ARE INDICATIONS OF A 13D FIRE SPRINKLER |
| | SYSTEM; HOWEVER, THERE IS ONLY 1 DOMESTIC WATER LINE |
| | INDICATED. |
| | |
| | PER THE WATER UTILITIES DEPARTMENT, A DEDICATED WATER |
| | SUPPLY AND WATER METER FOR A FIRE SPRINKLER SYSTEM IS |
| | REQUIRED. |
| | |
| | PLEASE CONTACT THE WATER UTILITIES DEPARTMENT FOR THEIR |
| | REQUIERMENTS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT |
| | AND PROVIDE REVISION AS AND WHERE REQUIRED PRIOR TO |
| | INSTALLATIONS. |
| | |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |