| 2021-10-18 10:11:55 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21070557 |
| | 10/18/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1: PLEASE PROVIDE WATER HEATER EQUIPMENT |
| | SCHEDULES ON THE PLAN AND SUBMIT MANUFACTURERS |
| | SPECIFICATIONS. INDICATE THE MAKES AND MODELS, GALLON |
| | SIZES, AND EFFICIENCY RATINGS, AND INCLUDE THE |
| | COMPLIANCE DATA IN THE ENERGY CALCULATIONS- TABLE |
| | C404.2 FBC EC. |
| | |
| | 2) WPB CROSS CONNECTION MANUAL: PLEASE ITEM C. CONTROL |
| | OF BACKFLOW. A BACKFLOW PREVENTER IS REQUIRED FOR A |
| | MULTI-FAMILY RESIDENTIAL AT THE POINT OF POTABLE WATER |
| | SERVICE DELIVERY. |
| | |
| | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |