| 2021-08-02 05:21:57 | 1) SHT. G-104 - TYPICAL DEVICE PLACEMENT DETAILS - THE |
| | ROOM SIGN ABOVE THE FINISH FLOOR SHALL BE LOCATED 60 |
| | INCHES MAXIMUM TO THE BASELINE OF THE HIGHEST TACTILE |
| | CHARACTER, NOT TO THE CENTERLINE OF THE SIGN AS SHOWN. |
| | FBC-ACCESS. SEC. 703.4.1. |
| | 2) SHT. G-104 - SHOW THE REQUIRED KNEE AND TOE |
| | CLEARANCES FOR THE LAVATORY. COMPLY WITH FBC-ACCESS. |
| | SEC. 306. |
| | 3) SHT. G-105 - SOME OF THE FIRESTOPPING DETAILS ARE |
| | MISSING THE TYPE OF PIPE MATERIALS AND THE MAXIMUM SIZE |
| | OF THE PENETRATING ITEMS. WPB AMEND. TO FBC |
| | SEC.107.3.5.1.1. SEE DETAILS #8, 10 & 11. |
| | 4) SHT. B-101 AND ARCHITECTURAL SHEETS - THE |
| | "UNIVERSAL' TOILET ROOMS SHALL BE GENDER SPECIFIC IN |
| | ACCORDANCE WITH FBC-PLUMBING SEC. 403.2. REVISE ALL |
| | APPLICABLE SHEETS TO COMPLY. |
| | 5) THE REQUIRED LAVATORY IS NOT SHOWN ON SHT. A-101. |
| | 6) SHTS. A-400 & A-410 - SHOW THE REQUIRED CLEAR FLOOR |
| | SPACES FOR THE HANDICAPPED ACCESSIBLE FIXTURES IN ALL |
| | TOILET ROOMS AND THE DRINKING FOUNTAINS AND SHOW THE |
| | DIMENSIONS (L X W) OF EACH CLEAR FLOOR SPACE. COMPLY |
| | WITH FBC-ACCESS. SECS.602.2, 604.3 & 606.2, |
| | 7) SHT. A-400 - DETAIL #1 - SHOW THE INSIDE CLEAR |
| | LENGTH OF THE TOILET ROOM. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 8) SHT. A- 410 - DETAILS #1 & #6 - SHOW THE INSIDE |
| | CLEAR LENGTH OF THE TOILET ROOMS ON THE PLANS. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 9) SHT. A- 410 - DETAILS #1 & #6 - SHOW THE FIXTURE |
| | CLEARANCE OF THE ACCESSIBLE WATER CLOSET FROM THE |
| | ADJACENT WALL. COMPLY WITH FBC-ACCESS. SEC. 604.2. |
| | 10) SHT.A- 410 - DETAIL #6 - TOILET ROOM #125 - THE |
| | LAVATORY APPEARS TO BE ENCROACHING INTO THE CLEAR FLOOR |
| | SPACE FOR THE WATER CLOSET. COMPLY WITH FBC- ACCESS. |
| | SEC.604.3.1. |
| | 11) TOILET ROOMS 124 & 125 SHALL COMPLY WITH |
| | FBC-ACCESS. SEC.213.1, 213.2. |
| | 12) TOILET ROOM #125 IS NOT LISTED ON THE FINISH |
| | SCHEDULE ON SHTS. ID-101 OR ID-110. CLARIFY. |
| | 13) SHT. G-102 - THE SHEET INDEX LISTS DRAWINGS P- 105 |
| | & P-106 BUT THESE DRAWINGS ARE NOT INCLUDED IN THIS |
| | SUBMITTAL. CLARIFY. |
| | 14) SHT. P-101 - THERE IS A NOTE AT THE UNDERGROUND |
| | SANITARY LINES THE STATES " FOR CONT. SEE P-101." THERE |
| | IS NO CONTINUATION OF THESE LINES SHOWN ON P-101. THIS |
| | ALSO OCCURS ON THE GAS LINE. CLARIFY. |
| | 15) SHT. P-102 - LEFT SIDE OF DRAWING - THERE IS A NOTE |
| | STATING " EX. GW FROM TENANTS" BUT THIS GREASE LINE IS |
| | SHOWN CONNECTED TO THE SANITARY SYSTEM. THE GREASE |
| | CANNOT CONNECT TO THE SANITARY SYSTEM. FBC-PLUMBING |
| | SEC.1003.1. |
| | 16) ALL HAND SINKS SHALL DISCHARGE TO THE SANITARY |
| | SYSTEM PER FBC-PLUMBING SEC.1003.2. |
| | 17) CLEAR WATER CONDENSATE WASTE FROM |
| | EVAPORATORS/COOLERS SHALL NOT BE DISCHARGED TO THE |
| | GREASE WASTE SYSTEM PER FBC-PLUMBING SEC.1003.2. |
| | 18) SHT. P-102 - SHOW THE CONTINUATION OF THE SANITARY |
| | LINE BY COLUMN #16. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 19) BACKFLOW PREVENTION DEVICES ARE REQUIRED ON THE |
| | DISHWASHER, COFFEE MACHINES, STEAMER, ROTISSERIE OVEN, |
| | ICE MACHINES, WATER FILTRATION SYSTEM, & COMBI-OVENS |
| | AND ANY OTHER APPLIANCE /EQUIPMENT THAT UTILIZES |
| | POTABLE WATER. FBC-PLUMBING SECS.608.3, 608.4, |
| | 608.17.1, 608.17.1.2. |
| | 20) SHT. P-103 - THERE IS A NOTE ON THE 3-INCH COLD |
| | WATER LINE AT THE TOP OF THE DRAWING THAT STATES " 3" |
| | CW. SEE CIVIL PLAN FOR CONT." THHERE ARE NO CIVIL PLANS |
| | IN THIS SUBMITTAL. LARIFY. |
| | 21) A FULL OPEN SHUTOFF VALVE IS REQUIRED ON THE WATER |
| | SUPPLY TO THIS SPACE PER FBC-PLUMBING SEC.606.1 (2). |
| | 22) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND. |
| | TO FBC SEC. 107.3.5.1.3. |
| | 23) SHTS. P-102 & P-103 - SHOW THE PIPE SIZES ON THE |
| | DRAWING. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 24) SHT. P-102 - THE LEFT SIDE OF THE DRAWING SHOWS AN |
| | EXISTING 3 INCH SANITARY LINE FROM THE 2ND FLOOR AND |
| | SHT. P-104 SHOWS THE SAME LINE AS 4 INCH. CLARIFY. |
| | 25) SHT. P-104 - TOILET ROOMS # 121 & 122 - NOT MORE |
| | THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE |
| | UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION. |
| | THE WATER CLOSETS UPSTREAM OF THE LAVATORIES DO NOT |
| | COMPLY WITH THE CODE AS DRAWN.FBC-PLUMBING SEC. |
| | 912.2.1. |
| | 26) SHT. P-102 - THERE ARE 4 TRENCH DRAINS SHOWN ON THE |
| | FLOOR PLAN IN THE RECEIVING/PRODUCE AREA BUT ONLY 3 ARE |
| | SHOWN ON THE SANITARY RISER.CLARIFY. |
| | 27) SHT. P-104 - SIZE THE BRANCH VENTS FOR THE TRENCH |
| | DRAINS IN THE PREPARED FOODS AREA. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 28)FOOD SERVICE PLANS - THERE IS A NOTE IN THE LOWER |
| | RIGHT CORNER OF THE PLANS THAT READS "NOT FOR |
| | CONSTRUCTION." CLARIFY. |
| | 29) THE FOOD SERVICE PLANS SHALL BE REVIEWED BY THE |
| | DESIGN PROFESSIONAL OF RECORD AND THEIR STAMP OF |
| | APPROVAL SHALL BE ON THE DRAWINGS NOTING ANY EXCEPTIONS |
| | TAKEN. WPB AMEND. TO FBC SEC.107.3.4. |
| | 30) SHOW MATCH LINES ON THE FOOD SERVICE PLANS FOR THE |
| | CONTINUATION OF THE AREAS.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 31) SUBMIT GREASE TRAP SIZING CALCULATIONS TO ENSURE |
| | THAT THE EXISTING TRAPS HAVE THE REQUIRED CAPACITY FOR |
| | THE NEW GREASE WASTE SYSTEM LOAD. FBC-PLUMBING |
| | SECS.1003.2, 1003.3.5.1. |
| | 32) SHT. G-103 - INDICATE ON THE PLAN IF THIS IS A |
| | CHANGE OF OCCUPANCY IN ACCORDANCE WITH FBC-EXISTING |
| | BUILDING CODE. IF THIS IS A CHANGE OF OCCUPANCY, |
| | INDICATE THE PREVIOUS OCUPANCY ON THE PLAN. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 33) THE PLANS AND APPLICATION SHOW THE ADDRESS AS 2751 |
| | S. DIXIE HWY. BUT THE PCN ON THE APPLICATION COMES UP |
| | AS 2715 S. DIXIE HWY. ON THE PALM BEACH COUNTY PROPERTY |
| | APPRAISER'S WEBSITE. CLARIFY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |