| 2021-08-11 10:41:26 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21070509 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE |
| | HOODS SHALL HAVE A SEPARATE PERMIT , DRAWINGS AND PLAN |
| | REVIEW AS THEY WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 2) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE |
| | REFRIGERATION SYSTEMS SHALL HAVE A SEPARATE PERMIT, |
| | DRAWINGS AND PLAN REVIEW AS THEY WILL NOT BE REVIEWED |
| | UNDER THIS PERMIT. |
| | |
| | 3) SHEET M-001: PLEASE REVISIT THE OUTDOOR AIR |
| | CALCULATIONS. USING THE NUMBERS YOU SHOW IN THE MINIMUM |
| | VENTILATION RATES IN BREATHING ZONE TABLE, I CALCULATE |
| | A TOTAL OF 1,765 CFM REQUIRED OUTDOOR AIR FOR THIS |
| | TENANT SPACE. |
| | |
| | 4) SHEET M-103: PLEASE SHOW THE CONDENSATE PIPING, |
| | MATERIAL AND THE TERMINATION LOCATION. FBC M 307 |
| | |
| | 5) SHEET M-103: PLEASE PROVIDE A DETAIL DRAWING OF THE |
| | BOILER EQUIPMENT EXHAUST. PROVIDE MATERIAL TYPE AND |
| | LENGTHS OF PIPING ALONG WITH COMPLIANCE OF FBC M |
| | CHAPTER 10. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |