| 2021-10-22 14:04:24 | 2ND REVIEW FBC-2020 GREASE WASTE |
| | PERMIT- 21070505 |
| | 10/22/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTED IN |
| | CAP LETTERS. |
| | |
| | 16) FAILED. SHT.P-101 - INDICATE ON THE PLAN WHAT |
| | STANDARD WAS USED IN THE SIZING OF THE GREASE |
| | INTERCEPTOR. THE PLAN REFERS TO A CH.24-42-6 FOR |
| | CHANGING DFU'S TO GPM. WHAT STANDARD IS THIS FROM? |
| | CLARIFY. THE CALCULATION METHOD IS ACCEPTED HOWEVER THE |
| | HAND SINK AND FLOOR SINK DRAINAGE LOADS HAVE BEEN ADDED |
| | TO THE CALCULATIONS AND THE DRAINAGE FROM THOSE |
| | FIXTURES CANNOT GO INTO THE GREASE INTERCEPTOR- SECTION |
| | 1003.3.1 FBC P. |
| | |
| | 17) FAILED. SUBMIT FACTORY SIZING CALCULATIONS FROM |
| | SCHIER FOR THE SIZING OF THE GREASE INTERCEPTOR PER |
| | FBC-PLUMBING SEC. 1003.2. SEE COMMENT NOTES FOR COMMENT |
| | #16. |
| | |
| | 19) FAILED. SHT. P-103 - THE HAND SINKS SHALL DISCHARGE |
| | TO THE SANITARY PER FBC-PLUMBING SEC.1003.3.1. SHEETS |
| | P103, P105, RS-3.0: REMOVE CLEAR WATER WASTE DRAINAGE |
| | FROM ALL OF THE HAND SINKS AND THE FLOOR SINKS |
| | CONVEYING DRAINAGE FROM THE ICE MAKER, WATER DISPENSER, |
| | RO SYSTEM, ETC.- SECTION 1003.3.1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |