Plan Review Notes
Plan Review Notes For Permit 21070505
Permit Number 21070505
Review Stop P-GREASE
Sequence Number 2
Notes
Date Text
2021-10-22 14:04:242ND REVIEW FBC-2020 GREASE WASTE
 PERMIT- 21070505
 10/22/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTED IN
 CAP LETTERS.
  
 16) FAILED. SHT.P-101 - INDICATE ON THE PLAN WHAT
 STANDARD WAS USED IN THE SIZING OF THE GREASE
 INTERCEPTOR. THE PLAN REFERS TO A CH.24-42-6 FOR
 CHANGING DFU'S TO GPM. WHAT STANDARD IS THIS FROM?
 CLARIFY. THE CALCULATION METHOD IS ACCEPTED HOWEVER THE
 HAND SINK AND FLOOR SINK DRAINAGE LOADS HAVE BEEN ADDED
 TO THE CALCULATIONS AND THE DRAINAGE FROM THOSE
 FIXTURES CANNOT GO INTO THE GREASE INTERCEPTOR- SECTION
 1003.3.1 FBC P.
  
 17) FAILED. SUBMIT FACTORY SIZING CALCULATIONS FROM
 SCHIER FOR THE SIZING OF THE GREASE INTERCEPTOR PER
 FBC-PLUMBING SEC. 1003.2. SEE COMMENT NOTES FOR COMMENT
 #16.
  
 19) FAILED. SHT. P-103 - THE HAND SINKS SHALL DISCHARGE
 TO THE SANITARY PER FBC-PLUMBING SEC.1003.3.1. SHEETS
 P103, P105, RS-3.0: REMOVE CLEAR WATER WASTE DRAINAGE
 FROM ALL OF THE HAND SINKS AND THE FLOOR SINKS
 CONVEYING DRAINAGE FROM THE ICE MAKER, WATER DISPENSER,
 RO SYSTEM, ETC.- SECTION 1003.3.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  