| Date |
Text |
| 2021-10-22 13:27:56 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21070505 |
| | 10/22/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTED IN |
| | CAP LETTERS. |
| | |
| | 8) FAILED. BOTH TOILET ROOMS SHALL BE FULLY ACCESSIBLE |
| | AND COMPLY WITH FBC-ACCESS. SEC.213.2. SHOW FULL |
| | COMPLIANCE FOR TOILET ROOM #104 ON THE PLANS. THE |
| | ARCHITECT IS REFERRING TO SECTION 213.2 EXCEPTION 4 FOR |
| | CLUSTERED TOILET ROOMS. THE TOILET ROOMS DO NOT APPEAR |
| | TO MEET THE EXCEPTION BECAUSE IT STATES ?NOT MORE THAN |
| | 50 PERCENT OF THE SINGLE USE TOILET ROOMS FOR EACH USE |
| | AT EACH CLUSTER SHALL BE REQUIRED TO COMPLY WITH 603. |
| | IT APPEARS THE INTENT OF THE SECTION WAS TO ALLOW |
| | ADDITIONAL TOILET ROOMS OVER AND ABOVE THE MINIMUM |
| | REQUIREMENTS TO NOT BE ACCESSIBLE WHEN CLUSTERED |
| | TOGETHER. BASED ON THE 48 OCCUPANT LOAD TWO SEPARATE |
| | TOILET ROOMS WERE REQUIRED TO BE INSTALLED- ONE F0R |
| | MALE AND ONE FOR FEMALE USE (EACH USE). THE FACT THAT |
| | THE PLUMBING CODE WHICH IS A COMPLETELY SEPARATE CODE |
| | VOLUME ALLOWS THOSE ROOMS TO BE LABELED UNISEX DOES NOT |
| | APPEAR TO EXEMPT ONE OF THE ROOMS FROM BEING ACCESSIBLE |
| | AS REQUIRED BY 213.2. IF THE INTENT IS TO STAY WITH |
| | THIS DESIGN PLEASE PROVIDE A SIGNED AND SEALED LETTER |
| | FROM THE ARCHITECT OF RECORD PROVIDING EVIDENCE THAT |
| | THE INTENT OF THE CODE IS BEING MET- SECTION 107.1 WPB |
| | 12) FAILED. SHT. A-400 - DETAIL #9 - THE DOOR SWINGS |
| | INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY AND WATER |
| | CLOSET IN BOTH TOILET ROOMS. COMPLY WITH FBC-ACCESS. |
| | SEC.603.2.3. TOILET ROOM DOORS ARE NOT PERMITTED TO |
| | SWING INTO THE CLEAR FLOOR SPACES PROVIDED FOR |
| | FIXTURES. APPROVAL OF THE DOOR SWINGING INWARD WILL |
| | DEPEND ON APPROVAL OF THE ROOM AS NON-ACCESSIBLE. |
| | |
| | 15) FAILED. A HOT WATER RECIRCULATION LINE WILL BE |
| | REQUIRED PER FBC-PLUMBING SEC.607.2. IN ACCORDANCE WITH |
| | SECTION C404.5.1 AND TABLE C404.5.1 THE MAXIMUM PIPING |
| | LENGTH FOR A ?-INCH HOT WATER LINE SUPPLYING A PUBLIC |
| | LAVATORY IS 2 FT. THE DESIGNER MUST DECIDE TO EITHER |
| | SPECIFY POINT OF USE WATER HEATERS AT THE LAVATORIES OR |
| | PROVIDE A RECIRCULATION PUMP FOR THE HW SYSATEM. PLEASE |
| | NOTE THAT SECTION 419.5 OF THE FBC P ALLOWS EITHER |
| | TEMPERED OR COLD WATER TO BE SUPPLIED TO A LAVATORY. |
| | |
| | 16) FAILED. SHT.P-101 - INDICATE ON THE PLAN WHAT |
| | STANDARD WAS USED IN THE SIZING OF THE GREASE |
| | INTERCEPTOR. THE PLAN REFERS TO A CH.24-42-6 FOR |
| | CHANGING DFU'S TO GPM. WHAT STANDARD IS THIS FROM? |
| | CLARIFY. THE CALCULATION METHOD IS ACCEPTED HOWEVER THE |
| | HAND SINK AND FLOOR SINK DRAINAGE LOADS HAVE BEEN ADDED |
| | TO THE CALCULATIONS AND THE DRAINAGE FROM THOSE |
| | FIXTURES CANNOT GO INTO THE GREASE INTERCEPTOR- SECTION |
| | 1003.3.1 FBC P. |
| | |
| | 17) FAILED. SUBMIT FACTORY SIZING CALCULATIONS FROM |
| | SCHIER FOR THE SIZING OF THE GREASE INTERCEPTOR PER |
| | FBC-PLUMBING SEC. 1003.2. SEE COMMENT NOTES FOR COMMENT |
| | #16. |
| | |
| | 19) FAILED. SHT. P-103 - THE HAND SINKS SHALL DISCHARGE |
| | TO THE SANITARY PER FBC-PLUMBING SEC.1003.3.1. SHEETS |
| | P103, P105, RS-3.0: REMOVE CLEAR WATER WASTE DRAINAGE |
| | FROM ALL OF THE HAND SINKS AND THE FLOOR SINKS |
| | CONVEYING DRAINAGE FROM THE ICE MAKER, WATER DISPENSER, |
| | RO SYSTEM, ETC.- SECTION 1003.3.1. |
| | |
| | 23) FAILED. THE WATER SUPPLY LINE TO THE COFFEE |
| | BREWERS, ICE MACHINES, ESPRESSO MACHINE, WATER |
| | DISPENSER, REVERSE OSMOSIS SYSTEM SHALL BE PROTECTED |
| | WITH A BACKFLOW DEVICE COMPLYING WITH FBC-PLUMBING |
| | TABLE 608.1 & ASSE 1024. SHEET P-106: BACKFLOW |
| | PREVENTERS FOR LINES SUPPLYING THE RO FILTER AND TANK |
| | NOT PROVIDED. TO THE ROUGH-IN SCHEDULE OR PROVIDE A |
| | SEPARATE SCHEDULE LISTING THE MAKES AND MODELS AND |
| | INSTALLATION LOCATIONS- SECTION 608.3 FBC P. |
| | |
| | 24) FAILED. ANY CARBONATED BEVERAGE MACHINE SHALL HAVE |
| | THE WATER SUPPLY LINE PROTECTED AGAINST BACKFLOW IN |
| | COMPLIANCE WITH FBC-PLUMBING TABLE 608.1 AND ASSE 1022. |
| | SHEETS P-101 & FS-3.0: TO HELP EXPEDITE THE REVIEW |
| | PLEASE ADD THE BACKFLOW DEVICES TO THE ROUGH-IN |
| | SCHEDULE OR PROVIDE A SEPARATE SCHEDULE LISTING THE |
| | MAKES AND MODELS AND INSTALLATION LOCATIONS- SECTION |
| | 608.3 FBC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |