| Plan Review Notes For Permit 21070505 |
| Permit Number |
21070505 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-10-22 14:01:12 | 2ND REVIEW FBC-2020 FUEL GAS | | | PERMIT- 21070505 | | | 10/22/2021 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC. | | | | | | PLAN REVIEW RESULTS: DENIED | | | FAILED COMMENT #5 IS LISTED BELOW WITH ADDITONAL NOTES | | | IN CAP LETTERS. | | | | | | 5) FAILED. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE | | | GAS APPLIANCES. FBC-FUEL GAS SEC. 304.1. WHERE | | | COMBUSTION AIR IS PROVIDED BY THE BUILDING?S MECHANICAL | | | VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE | | | SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE | | | REQUIRED VENTILATION AIR. FBC-FUEL GAS SEC.304.9.3. I | | | WAS NOT ABLE TO LOCATE THE COMBUSTION AIR CALCULATIONS. | | | PLEASE INDICATE IN THE RESPONSE NARRATIVE WHICH PLAN | | | SHEET SHOWS THE COMBUSTION AIR CALCS AND METHOD. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|