Plan Review Notes
Plan Review Notes For Permit 21070505
Permit Number 21070505
Review Stop G
Sequence Number 2
Notes
Date Text
2021-10-22 14:01:122ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21070505
 10/22/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC.
  
 PLAN REVIEW RESULTS: DENIED
 FAILED COMMENT #5 IS LISTED BELOW WITH ADDITONAL NOTES
 IN CAP LETTERS.
  
 5) FAILED. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE
 GAS APPLIANCES. FBC-FUEL GAS SEC. 304.1. WHERE
 COMBUSTION AIR IS PROVIDED BY THE BUILDING?S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. FBC-FUEL GAS SEC.304.9.3. I
 WAS NOT ABLE TO LOCATE THE COMBUSTION AIR CALCULATIONS.
 PLEASE INDICATE IN THE RESPONSE NARRATIVE WHICH PLAN
 SHEET SHOWS THE COMBUSTION AIR CALCS AND METHOD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  