| 2021-07-26 11:02:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) LIFE SAFETY SHEET - THE OCCUPANCY LOAD TOTAL FOR |
| | DINING INDICATES 43. OUTSIDE SEATING SHALL NOT NE |
| | INCLUDED IN THE OCCUPANCY TOTAL. |
| | |
| | 630/15= 42 |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | 1A) LIFE SAFETY SHEET - THE OCCUPANCY LOAD COUNT OF 42 |
| | APPEARS TO BE TOO LARGE FOR THIS AREA. THERE ARE |
| | APPROX. 16 CHAIRS AND 6 BAR STOOLS INDICATED = 22. HOW |
| | WOULD 20 MORE CHAIRS FIT? |
| | |
| | PLEASE PROVIDE DIMENSIONS OF HOW THE 630SQ FT IS |
| | CALCULATED. |
| | |
| | |
| | 1B) AS THIS IS A PROPOSED DONUT SHOP, IT WOULD APPEAR |
| | THAT WALKIN SERVICE AND STANDING ROOM IS REQUIRED. |
| | |
| | THAT AREA OCCUPANCY LOAD WOULD BE CLACULATED AT 7SQ |
| | FT/PERSON, NOT 15 FOR THE SEATING AREA. |
| | |
| | PLEAE EVIEW AND INDICATED DESIGNATED AREA AND CORRECT. |
| | |
| | |
| | |
| | 2) LIFE SAFETY SHEET - THE BAR COUNT INDICATES 2, |
| | |
| | THERE ARE 6 BAR STOOLS INDICATED. |
| | |
| | PLEASE CORRECT OR EXPLAIN. |
| | |
| | |
| | |
| | 3) LIFE SAFETY SHEET - THERE IS AN INDICATION UNDER |
| | GENERAL NOTES #6 & 15; SEE FIRE PROTECTION DRAWINGS FOR |
| | SPRINKLER LAYOUT. |
| | |
| | THIS OCCUPNACY HAS AN EXISTING SPRINKLER PROTECTION |
| | WITH ODIFICATION BEING REQUIRED. |
| | |
| | ANY AND ALL WORK, INCLUDING DEMO, ON THE FIRE SPRINKLER |
| | SYSTEM SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP |
| | DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 4) THERE ARE INDICATIONS OF HOOD INSTALLATION. |
| | |
| | ANY AND ALL WORK ON THE HOOD SYSTEM SHALL BE DONE UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 5) ELECTRICAL - THERE ARE INDICATIONS OF FIRE ALARM |
| | DEVICES.. |
| | |
| | ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE |
| | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |