Plan Review Notes For Permit 21070505
Permit Number 21070505
Review Stop P-GREASE
Sequence Number 1
Notes
Date Text
2021-08-28 07:14:551) SHT.P-101 - INDICATE ON THE PLAN WHAT STANDARD WAS
 USED IN THE SIZING OF THE GREASE INTERCEPTOR.THE PLAN
 REFERS TO A CH.24-42-6 FOR CHANGING DFU'S TO GPM. WHAT
 STANDARD IS THIS FROM? CLARIFY.
 2) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR
 THE SIZING OF THE GREASE INTERCEPTOR PER FBC-PLUMBING
 SEC. 1003.2.
 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE GREASE
 INTERCEPTOR. PLACE THIS NOTE ON THE PLAN.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  