Plan Review Notes
Plan Review Notes For Permit 21070505
Permit Number 21070505
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-27 05:54:561) SHT. G103 - PLUMBING SYSTEMS TABLE LISTS GREASE
 INTERCEPTOR AS "NR" YET ONE IS BEING INSTALLED. LIST
 THE TYPE, MANUFACTURER, AND SIZE OF THE INTERCEPTOR ON
 THIS TABLE.
 2) SHT. G-104 - THE SIDE WALL GRAB BAR SHALL BE LOCATED
 IN ACCORDANCE WITH FBC-ACCESS. SEC.604.5.1 & FIGURE
 604.5.1. THE LENGTH OF THE GRAB BAR SHALL BE A MINIMUM
 OF 42 INCHES.
 3) SHT. G-104 - THE URINAL SCREEN SHALL BEGIN AT A
 HEIGHT NOT MMORE THAN 12 INCHES FROM AND EXTEND NOT
 LESS THAN 60 INCHES ABOVE THE FFINISHED FLOOR SURFACE
 PER FBC -BUILDING SEC.1210.3.2. THE PLAN SHOWS THE
 BOTTOM OF THE SCREEN AT 18 INCHES ABOVE THE FINISH
 FLOOR.
 4) SHT. G-104 - WATER COOLER (DOUBLE) - SHOW COMPLIANCE
 WITH FBC-ACCESS. SEC. 602.7 FOR THE SPOUT OUTLET HEIGHT
 FOR STANDING PERSONS.
 5) SHT. G-104 - ROOM SIGNAGE - TACTILE CHARACTERS ON
 SIGNS SHALL BE LOCATED 48 INCHES MINIMUM ABOVE THE
 FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE LOWEST TACTILE CHARACTER AND 60 INCHES
 MMAXIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE,
 MEASUURED FROM THE BASELINE OF THE HIGHEST TACTILE
 CHARACTER. FBC-ACCESS. SEC. 703.4.1.
 6) SHT. B-101 SHOWS THE OCCUPANT LOAD OF THIS SPACE AS
 49 PERSONS.A BUILDING OR TENANT SPACE USED FOR ASSEMBLY
 PURPOSES WITH AN OCCCUPANT LOAD OF LES THAN 50 PERSONS
 SHALL BE CLASSIFIED AS A GROUP B OCCUPANCY.THE PLANS
 CLASSIY THIS OCCUPANCY AS AN A-2 OCUPANCCY. CLARIFY
 7) THE REQUIRED PLUMBING FIXTURES SHALL BE BASED ON A B
 OCCUPANCY PER FBC-PLUMBING TABLE 403.1.
 8) BOTH TOILET ROOMS SHALL BE FULLLY ACCESSIBLE AND
 COMPLY WITH FBC-ACCESS. SEC.213.2. SHOW FULL COMPLIANCE
 FOR TOILET ROOM #104 ON THE PLANS.
 9) SHOW THE LOCATION OF THE REQUIRED DRINKING FOUNTAIN
 ON THE PLAN AND THE REQUIRED CLEAR FLOOR SPACE FOR THE
 FIXTURE PER FBC-ACCESS. SEC.305 & 602.2.
 10) SHT. B-101 NOTES THE SQUARE FOOTAGE OF THIS SPACE
 AS 1797 SQUARE FEET AND SHT. A-001 NOTES THE SQUARE
 FOOTAGE AS 1039 SQUARE FEET. CLARIFY.
 11) SHT. AD-100 IS MISSING A DIGITAL SEAL & SIGNATURE.
 COMPLY WITH FL. ADMIN. CODE RULE 61G1-16.005.
 12) SHT. A-400 - DETAIL #9 - THE DOOR SWINGS INTO THE
 CLEAR FLOOR SPACE FOR THE LAVATORY AND WATER CLOSET IN
 BOTH TTOILET ROOMS. COMPLY WITH FBC-ACCESS.
 SEC.603.2.3.
 13) SHT. A-420 - DEATIL #4 - WHERE IS THIS FIXTURE
 LOCATED? SHOW ON THE PLANS. WPB AMEND. TO FBC SEC.
 107.2.1.
 14) SHT.ID-101 - FINISH MATERIAL CT-2 IS NOT LISTED ON
 THE FINISH SCHEDULE. CLARIFY.
 15) A HOT WATER RECRCULATION LINE WILL BE REQUIRED PER
 FBC-PLUMBING SEC.607.2.
 16) SHT.P-101 - INDICATE ON THE PLAN WHAT STANDARD WAS
 USED IN THE SIZING OF THE GREASE INTERCEPTOR.THE PLAN
 REFERS TO A CH.24-42-6 FOR CHANGING DFU'S TO GPM. WHAT
 STANDARD IS THIS FROM? CLARIFY.
 17) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR
 THE SIZING OF THE GREASE INTERCEPTOR PER FBC-PLUMBING
 SEC. 1003.2.
 18) SUBMIT A DETAIL OF THE GREASE INTERCEPTOR THAT IS
 BEING INSTALLED. FBC-PLUMBING SEC. 1003.2.
 19) SHT. P-103 - THE HAND SINKS SHALL DISCHARGE TO THE
 SANITARY PER FBC-PLUMBING SEC.1003.3.1.
 20) TRAP PRIMERS ARE REQUIRED ON THE FLOOR DRAINS PER
 FBC-PLUMBING SEC.1002.4.1.
 21) SHT. P-105 SHOWS THE DRAIN FROM EVAPORATOR W18A
 DISCHARGING TO THE GRESE WASTE SYSTEM. THE CONDENSATE
 SHALL DISCHARGE TO THE SANITARY OR THE STORM SYSTEM.
 FBC-PLUMBING SEC.1003.2.
 22) SHT. P-104 CALLS OUT A NEW 1 1/2 INCH SHUTOFF VALVE
 ON THE WATER SUPPLY LINE BY THE TOILET ROOMS YET P-106
 CALLS OUT THIS LINE AS 1 1/4. CLARIFY.
 23) THE WATER SUPPLY LINE TO THE COFFE BREWERS, ICE
 MACHINES, ESPRESSO MACHINE, WATER DISPENSER, REVERSE
 OSMOSIS SYSTEM SHALL BE PROTECTED WITH A BACKFLOW
 DEVICE COMPLYING WITH FBC-PLUMBING TABLE 608.1 & ASSE
 1024.
 24) ANY CARBONATED BEVERAGE MACHINE SHALL HAVE THE
 WATER SUPPY LINE PROTECTED AGAINST BACKFLOW IN
 COMPLIANCE WITH FBC-PLUMBING TABLE 608.1 AND ASSE 1022.
 25)THE DISHWASHER SHALL BE EQUIPPED WITH A BACKFLOW
 DEVICE. FBC-PLUMBING SEC. 608.16.
 26) THE FOOD SEVICE PLANS ON THEM IN THE LOWER RIGHT
 HAND CORNER THAT READS "NOT FOR CONSTRUCTION". CLARIFY.
 27) THE FOOD SERVICE PLANS HAVE NOT BEEN SIGNED &
 SEALED BY THE ARCHITECT OF RECORD ALTHOUGH THE TITLE
 BLOCK IS ON THE PLANS. COMPLY WITH FL. ADMIN. CODE RULE
 61G1-16.005.
 28) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 KITCHEN EQUIPMENT PER WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  