| Date |
Text |
| 2021-08-27 05:54:56 | 1) SHT. G103 - PLUMBING SYSTEMS TABLE LISTS GREASE |
| | INTERCEPTOR AS "NR" YET ONE IS BEING INSTALLED. LIST |
| | THE TYPE, MANUFACTURER, AND SIZE OF THE INTERCEPTOR ON |
| | THIS TABLE. |
| | 2) SHT. G-104 - THE SIDE WALL GRAB BAR SHALL BE LOCATED |
| | IN ACCORDANCE WITH FBC-ACCESS. SEC.604.5.1 & FIGURE |
| | 604.5.1. THE LENGTH OF THE GRAB BAR SHALL BE A MINIMUM |
| | OF 42 INCHES. |
| | 3) SHT. G-104 - THE URINAL SCREEN SHALL BEGIN AT A |
| | HEIGHT NOT MMORE THAN 12 INCHES FROM AND EXTEND NOT |
| | LESS THAN 60 INCHES ABOVE THE FFINISHED FLOOR SURFACE |
| | PER FBC -BUILDING SEC.1210.3.2. THE PLAN SHOWS THE |
| | BOTTOM OF THE SCREEN AT 18 INCHES ABOVE THE FINISH |
| | FLOOR. |
| | 4) SHT. G-104 - WATER COOLER (DOUBLE) - SHOW COMPLIANCE |
| | WITH FBC-ACCESS. SEC. 602.7 FOR THE SPOUT OUTLET HEIGHT |
| | FOR STANDING PERSONS. |
| | 5) SHT. G-104 - ROOM SIGNAGE - TACTILE CHARACTERS ON |
| | SIGNS SHALL BE LOCATED 48 INCHES MINIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE |
| | BASELINE OF THE LOWEST TACTILE CHARACTER AND 60 INCHES |
| | MMAXIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE, |
| | MEASUURED FROM THE BASELINE OF THE HIGHEST TACTILE |
| | CHARACTER. FBC-ACCESS. SEC. 703.4.1. |
| | 6) SHT. B-101 SHOWS THE OCCUPANT LOAD OF THIS SPACE AS |
| | 49 PERSONS.A BUILDING OR TENANT SPACE USED FOR ASSEMBLY |
| | PURPOSES WITH AN OCCCUPANT LOAD OF LES THAN 50 PERSONS |
| | SHALL BE CLASSIFIED AS A GROUP B OCCUPANCY.THE PLANS |
| | CLASSIY THIS OCCUPANCY AS AN A-2 OCUPANCCY. CLARIFY |
| | 7) THE REQUIRED PLUMBING FIXTURES SHALL BE BASED ON A B |
| | OCCUPANCY PER FBC-PLUMBING TABLE 403.1. |
| | 8) BOTH TOILET ROOMS SHALL BE FULLLY ACCESSIBLE AND |
| | COMPLY WITH FBC-ACCESS. SEC.213.2. SHOW FULL COMPLIANCE |
| | FOR TOILET ROOM #104 ON THE PLANS. |
| | 9) SHOW THE LOCATION OF THE REQUIRED DRINKING FOUNTAIN |
| | ON THE PLAN AND THE REQUIRED CLEAR FLOOR SPACE FOR THE |
| | FIXTURE PER FBC-ACCESS. SEC.305 & 602.2. |
| | 10) SHT. B-101 NOTES THE SQUARE FOOTAGE OF THIS SPACE |
| | AS 1797 SQUARE FEET AND SHT. A-001 NOTES THE SQUARE |
| | FOOTAGE AS 1039 SQUARE FEET. CLARIFY. |
| | 11) SHT. AD-100 IS MISSING A DIGITAL SEAL & SIGNATURE. |
| | COMPLY WITH FL. ADMIN. CODE RULE 61G1-16.005. |
| | 12) SHT. A-400 - DETAIL #9 - THE DOOR SWINGS INTO THE |
| | CLEAR FLOOR SPACE FOR THE LAVATORY AND WATER CLOSET IN |
| | BOTH TTOILET ROOMS. COMPLY WITH FBC-ACCESS. |
| | SEC.603.2.3. |
| | 13) SHT. A-420 - DEATIL #4 - WHERE IS THIS FIXTURE |
| | LOCATED? SHOW ON THE PLANS. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 14) SHT.ID-101 - FINISH MATERIAL CT-2 IS NOT LISTED ON |
| | THE FINISH SCHEDULE. CLARIFY. |
| | 15) A HOT WATER RECRCULATION LINE WILL BE REQUIRED PER |
| | FBC-PLUMBING SEC.607.2. |
| | 16) SHT.P-101 - INDICATE ON THE PLAN WHAT STANDARD WAS |
| | USED IN THE SIZING OF THE GREASE INTERCEPTOR.THE PLAN |
| | REFERS TO A CH.24-42-6 FOR CHANGING DFU'S TO GPM. WHAT |
| | STANDARD IS THIS FROM? CLARIFY. |
| | 17) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR |
| | THE SIZING OF THE GREASE INTERCEPTOR PER FBC-PLUMBING |
| | SEC. 1003.2. |
| | 18) SUBMIT A DETAIL OF THE GREASE INTERCEPTOR THAT IS |
| | BEING INSTALLED. FBC-PLUMBING SEC. 1003.2. |
| | 19) SHT. P-103 - THE HAND SINKS SHALL DISCHARGE TO THE |
| | SANITARY PER FBC-PLUMBING SEC.1003.3.1. |
| | 20) TRAP PRIMERS ARE REQUIRED ON THE FLOOR DRAINS PER |
| | FBC-PLUMBING SEC.1002.4.1. |
| | 21) SHT. P-105 SHOWS THE DRAIN FROM EVAPORATOR W18A |
| | DISCHARGING TO THE GRESE WASTE SYSTEM. THE CONDENSATE |
| | SHALL DISCHARGE TO THE SANITARY OR THE STORM SYSTEM. |
| | FBC-PLUMBING SEC.1003.2. |
| | 22) SHT. P-104 CALLS OUT A NEW 1 1/2 INCH SHUTOFF VALVE |
| | ON THE WATER SUPPLY LINE BY THE TOILET ROOMS YET P-106 |
| | CALLS OUT THIS LINE AS 1 1/4. CLARIFY. |
| | 23) THE WATER SUPPLY LINE TO THE COFFE BREWERS, ICE |
| | MACHINES, ESPRESSO MACHINE, WATER DISPENSER, REVERSE |
| | OSMOSIS SYSTEM SHALL BE PROTECTED WITH A BACKFLOW |
| | DEVICE COMPLYING WITH FBC-PLUMBING TABLE 608.1 & ASSE |
| | 1024. |
| | 24) ANY CARBONATED BEVERAGE MACHINE SHALL HAVE THE |
| | WATER SUPPY LINE PROTECTED AGAINST BACKFLOW IN |
| | COMPLIANCE WITH FBC-PLUMBING TABLE 608.1 AND ASSE 1022. |
| | 25)THE DISHWASHER SHALL BE EQUIPPED WITH A BACKFLOW |
| | DEVICE. FBC-PLUMBING SEC. 608.16. |
| | 26) THE FOOD SEVICE PLANS ON THEM IN THE LOWER RIGHT |
| | HAND CORNER THAT READS "NOT FOR CONSTRUCTION". CLARIFY. |
| | 27) THE FOOD SERVICE PLANS HAVE NOT BEEN SIGNED & |
| | SEALED BY THE ARCHITECT OF RECORD ALTHOUGH THE TITLE |
| | BLOCK IS ON THE PLANS. COMPLY WITH FL. ADMIN. CODE RULE |
| | 61G1-16.005. |
| | 28) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | KITCHEN EQUIPMENT PER WPB AMEND. TO FBC SEC. 107.2.1. |
| | |