| 2021-08-20 15:55:00 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21070505 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE |
| | KITCHEN HOODS WILL REQUIRE A SEPARATE PERMIT |
| | APPLICATION, DRAWINGS AND REVIEW. THE KITCHEN HOODS |
| | WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 2) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE |
| | REFRIGERATION SYSTEMS WILL REQUIRE A SEPARATE PERMIT |
| | APPLICATION, DRAWINGS AND REVIEW. THE REFRIGERATION |
| | SYSTEMS WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 3) SHEET -M-102: PLEASE BE MORE SPECIFIC WITH THE USE |
| | OF SPACE FOR THE OUTDOOR AIR CALCULATIONS. USING FBC M |
| | 403.3.1.1 AND TABLE 403.3.1.1 AND USING KITCHEN AND |
| | DINING ROOM AS THE USE OF SPACES. THE REQUIRED OUTDOOR |
| | AIR AND KITCHEN EXHAUST IS BELOW: |
| | KITCHEN- 214 CFM OF OUTDOOR AIR; KITCHEN 550 CFM OF |
| | EXHAUST; BAR- 211 CFM OF OUTDOOR AIR; DINING- 471 CFM |
| | OF OUTDOOR AIR. |
| | |
| | 4) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE |
| | COMPLETE MECHANICAL SYSTEM. FBC 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |