Plan Review Notes
Plan Review Notes For Permit 21070505
Permit Number 21070505
Review Stop M
Sequence Number 1
Notes
Date Text
2021-08-20 15:55:001ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21070505
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE
 KITCHEN HOODS WILL REQUIRE A SEPARATE PERMIT
 APPLICATION, DRAWINGS AND REVIEW. THE KITCHEN HOODS
 WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 2) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE
 REFRIGERATION SYSTEMS WILL REQUIRE A SEPARATE PERMIT
 APPLICATION, DRAWINGS AND REVIEW. THE REFRIGERATION
 SYSTEMS WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 3) SHEET -M-102: PLEASE BE MORE SPECIFIC WITH THE USE
 OF SPACE FOR THE OUTDOOR AIR CALCULATIONS. USING FBC M
 403.3.1.1 AND TABLE 403.3.1.1 AND USING KITCHEN AND
 DINING ROOM AS THE USE OF SPACES. THE REQUIRED OUTDOOR
 AIR AND KITCHEN EXHAUST IS BELOW:
 KITCHEN- 214 CFM OF OUTDOOR AIR; KITCHEN 550 CFM OF
 EXHAUST; BAR- 211 CFM OF OUTDOOR AIR; DINING- 471 CFM
 OF OUTDOOR AIR.
  
 4) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE
 COMPLETE MECHANICAL SYSTEM. FBC 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  