| Plan Review Notes For Permit 21070505 |
| Permit Number |
21070505 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-28 07:31:37 | 1) SUBMIT THE SIZING TABLE FOR THE PE PIPE FROM THE | | | 2020 FBC-FUEL GAS CODE. WPB AMEND. TO BC SEC. 107.2.1. | | | 2) THE 3/4 INCH METALLIC LINE IS UNDERSIZED TO THE TWO | | | GAS APPLIANCES. THE SYSTEM IS CAPABLE OF HANDLING A | | | MAXIMUM 83 MBTU AT A DISTANCE OF 150 FEET DEVELOPED | | | LENGTH. THE PIPING SHALL BE INCREASED TO 1 INCH PER | | | FBC-FUEL GAS TABLE 402.4 (2). | | | 3) A SEPARATE PERMIT IS REQUIRED FOR THE GAS. PLACE A | | | NOTE TO THIS EFFECT ON THE PLAN. | | | 4) SUBMIT COPIES OF THE GAS EQUIPMENT PECIFICATIONS. | | | ALL GAS EQUIPMENT/ APPLIANCES SHALL BE LISTED AND | | | LABELED PER FBC-FUEL GAS SEC.301.3. | | | 5) ) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS | | | APPLIANCES. FBC-FUEL GAS SEC. 304.1. WHERE COMBUSTION | | | AIR IS PROVIDED BY THE BUILDING?S MECHANICAL | | | VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE | | | SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE | | | REQUIRED VENTILATION AIR. FBC-FUEL GAS SEC.304.9.3. | | | 6) SHT. P-102. THE PLAN SHOWS THE GAS LINE LABELED AS | | | GW. CLARIFY | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|