Plan Review Notes
Plan Review Notes For Permit 21070505
Permit Number 21070505
Review Stop G
Sequence Number 1
Notes
Date Text
2021-08-28 07:31:371) SUBMIT THE SIZING TABLE FOR THE PE PIPE FROM THE
 2020 FBC-FUEL GAS CODE. WPB AMEND. TO BC SEC. 107.2.1.
 2) THE 3/4 INCH METALLIC LINE IS UNDERSIZED TO THE TWO
 GAS APPLIANCES. THE SYSTEM IS CAPABLE OF HANDLING A
 MAXIMUM 83 MBTU AT A DISTANCE OF 150 FEET DEVELOPED
 LENGTH. THE PIPING SHALL BE INCREASED TO 1 INCH PER
 FBC-FUEL GAS TABLE 402.4 (2).
 3) A SEPARATE PERMIT IS REQUIRED FOR THE GAS. PLACE A
 NOTE TO THIS EFFECT ON THE PLAN.
 4) SUBMIT COPIES OF THE GAS EQUIPMENT PECIFICATIONS.
 ALL GAS EQUIPMENT/ APPLIANCES SHALL BE LISTED AND
 LABELED PER FBC-FUEL GAS SEC.301.3.
 5) ) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES. FBC-FUEL GAS SEC. 304.1. WHERE COMBUSTION
 AIR IS PROVIDED BY THE BUILDING?S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. FBC-FUEL GAS SEC.304.9.3.
 6) SHT. P-102. THE PLAN SHOWS THE GAS LINE LABELED AS
 GW. CLARIFY
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  