| Plan Review Notes For Permit 21070505 |
| Permit Number |
21070505 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-25 16:25:50 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-102 | | | | | | GFCI PROTECTION OF KITCHEN OUTLETS PER 210.8(B)(2) | | | | | | 210.8(B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE | | | RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50 | | | AMPERES OR LESS AND THREEPHASE | | | RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100 | | | AMPERES OR LESS INSTALLED IN THE FOLLOWING LOCATIONS | | | SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION | | | FOR PERSONNEL. | | | | | | PAGE E-103 | | | | | | FAULT CURRENT CALCULATION REQUIRED FOR SERVICE AND | | | PANELS PER 110.9, 110.10 |
|