| Plan Review Notes For Permit 21070505 |
| Permit Number |
21070505 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-02 08:30:34 | BUILD OUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC RESIDENTIAL WITH WPB | | | CHAPTER 1 AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) PRODUCT APPROVALS THAT ARE | | | LISTED ON THE DRAWINGS. | | | 2) EXTERIOR WALL (EWS02) - PLEASE PROVIDE EFIS | | | ATTACHMENT DETAILS - PLEASE SHOW THE STRUCTURAL BACKING | | | FOR THE EFIS IF REQUIRED FBC 1408.3 STRUCTURAL DESIGN. | | | THE UNDERLYING STRUCTURAL FRAMING AND SUBSTRATE SHALL | | | BE DESIGNED AND CONSTRUCTED TO RESIST LOADS AS REQUIRED | | | BY CHAPTER 16. | | | |
|