| 2021-12-10 13:37:32 | BUILDING REVIEW APPROVED WITH PROVISO |
| | (NOTE: SUBMIT FOR REVIEW PRIOR TO INSPECTIONS TO AVOID |
| | CONFLICT/DELAYS): |
| | 1)MUD ROOM ADDITION: NEED COMPLETE ROOF FRAMING PLAN |
| | FOR CONVENTIONAL FRAMING. SHOW ALL STRUCTURAL FRAMING |
| | MEMBERS AND CONNECTORS AT EACH END. |
| | |
| | 2)WALL SECTION (SHEET A202):PROVIDE ROOF SHEATHING |
| | COMPLETE INFORMATION. PLYWOOD THICKNESS AND FASTENING. |
| | SEE SEC. R803 FBC-RESIDENTIAL. NOTE: COORDINATE WITH |
| | CURRENT CEDAR SHINGLES PRODUCT APPROVAL. PROVIDE |
| | COMPLETE SPECS FOR WALL SHEATHING, EXTERIOR FINISH, |
| | FLOOR JOISTS CONNECTION TO NEW STEM WALL AND EXISTING |
| | WALL. PROVIDE COMPLETE SPECS FOR STEM WALL BEAM, ETC. |
| | |
| | 3)PROVIDE COMPLETE PRODUCT APPROVAL (NEED COVER PAGE & |
| | COMPLETE INSTALLATION DWGS)FOR: |
| | A)CEDAR SHINGLES. PROVIDE COMPLETE CURRENT PRODUCT |
| | APPROVAL SHOWING COMPLIANCE WITH SEC. R905.7 |
| | FBC-RESIDENTIAL. |
| | B)SKYLIGHT. |
| | C)WINDOW MULLIONS. NOTE: NEED TO SPECIFY MULLION SIZE. |
| | D)CASEMENT WINDOWS. NOTE: MULLION HIGHLIGHTED ON SHEET |
| | 13 OF 28 DOESN'T MEET THE CALCULATED DESIGN PRESSURES. |
| | NEED TO REVISE SIZE. |
| | E)DOUBLE HUNG WINDOWS. |
| | F)EXTERIOR DOORS. |
| | G)FIXED WINDOWS. IF REPLACED. |
| | D)HURRICANE SHUTTERS AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE CITY SAMPLE. |
| | |
| | 4)ARCHITECT OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT |
| | APPROVALS. |
| | |
| | 5)PROVIDE STAIRWAY, STAIRS, HANDRAILS, GUARDRAILS SHOP |
| | DRAWINGS REVIEWED BY ARCHITECT. |