Plan Review Notes
Plan Review Notes For Permit 21070481
Permit Number 21070481
Review Stop P
Sequence Number 2
Notes
Date Text
2021-09-29 17:09:411ST REVIEW FBC-2020 RES.
 PERMIT- 21070481
 9/28/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A100 SANITARY RISER: SHOW A 2-INCH FIXTURE
 DRAIN FOR THE WASHING MACHINE CONNECTING TO A MINIMUM
 3-INCH STACK AND BRANCH DRAIN- SECTION 406.2 FBC P.
  
 2) A101: SHOW THE LOCATIONS OF THE WASHING MACHINE
 SHUTOFF VALVES TO VERIFY THEY WILL BE IN A LOCATION
 WITH ACCESS- SECTION P2903.5.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  