| Plan Review Notes For Permit 21070481 |
| Permit Number |
21070481 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-10-11 19:40:59 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. SMOKE/CO ALARMS REQUIRED PER FBC-RE 314 AND 315 | | | | | | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, | | | E3609.3; WPB FBC 107.2.1 | | | | | | 3. ARC-FAULT PROTECTION REQUIRED PER NEC 210.12A, | | | 210.12B | | | | | | 4. TAMPERPROOF RECEPTACLES REQUIRED PER NEC 406.12 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|