Plan Review Notes
Plan Review Notes For Permit 21070481
Permit Number 21070481
Review Stop G
Sequence Number 1
Notes
Date Text
2021-09-30 08:28:011ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21070481
 9/28/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A100 & A101: THE GAS PIPING AND APPLIANCE
 INSTALLATIONS FOR THE PROPOSED PROJECT SHALL BE
 DESIGNED AND INSTALLED IN ACCORDANCE WITH THE FBC- 2020
 7TH EDITION RESIDENTIAL CODE. PLEASE PROVIDE DESIGN
 CRITERIA ON THE PLANS.
  
 2) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES
 ALL NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE
 RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO
 FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL SHOW:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 3) PLEASE NOTE THAT THE MOST RECENT GAS PERMIT AT THE
 RESIDENCE WAS PERMIT #04121077. WPB BUILDING DEPT.
 RECORDS INDICATE A 505,000 BTU SYSTEM WITH AN EXISTING
 RANGE, STORAGE TYPE WATER HEATER AND A NEW POOL HEATER.
 THERE IS NO RECORD OF AN EXTERIOR TANKLESS GAS-FIRED
 WATER HEATER BEING LEGALLY PERMITTED THEREFORE IT SHALL
 BE REVIEWED AS A NEW WATER HEATER. PLEASE SUBMIT
 MANUFACTURER?S SPECIFICATIONS AND INSTALLATION MANUAL
 FOR THE WATER HEATER. PROVIDE AN EQUIPMENT SCHEDULE ON
 THE PLAN INDICATING THE MAKE AND MODEL, BTUH LOAD, AND
 EFFICIENCY RATING- TABLE C404.2 FBC EC. PROVIDE A
 DETAIL SHOWING THE INSTALLATION LOCATION AND REQUIRED
 CLEARANCES AS RECOMMENDED BY THE MANUFACTURER- SECTIONS
 G2406.1 & G2448.1 FBC RES.
  
 4) PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW RANGE AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION G2447.1
 FBC RES. PROVIDE COMBUSTION AIR CALCULATIONS AND
 INDICATE HOW THE AIR WILL BE PROVIDED- SECTION G2407.1
 FBC RES.
  
 5) PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW FIREPLACE
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL - SECTION G2434.1 FBC RES. PROVIDE
 COMBUSTION AIR AND VENTING PLANS FOR THE FIREPLACE IN
 ACCORDANCE WITH MANUFACTURER?S GUIDELINES. PLEASE
 INCLUDE COMBUSTION AIR CALCULATIONS, AND A VENTING
 DIAGRAM WHICH SHOWS THE TYPE AND SIZE OF VENT
 PIPES/DUCTS, VENT RUN LENGTHS AND VENT TERMINATION
 LOCATION- REFER TO SPECS AND SECTION G2427 FBC RES.
  
 6) INDICATE THE MAKES AND MODELS OF REGULATORS TO BE
 INSTALLED ON THE SYSTEM AND SUBMIT MANUFACTURER?S
 SPECIFICATIONS MARKED UP TO SHOW THE SELECTED MODELS,
 AND INPUT AND OUT PIPE SIZES AND PRESSURES- SECTION
 G2421.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  