Plan Review Notes
Plan Review Notes For Permit 21070458
Permit Number 21070458
Review Stop G
Sequence Number 1
Notes
Date Text
2021-08-12 17:26:1907/23/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SHOW THE DISTANCE OF THE LP TANK FROM THE EXTERIOR
 WALL OF THE STRUCTURE TO THE CONTAINER SURFACE AND FROM
 THE PROPERTY LINE TO THE CONTAINER SURFACE TO COMPLY
 WITH NFPA 58-17 SEC. 6.4.1 & TABLE 6.4.1.1.
  
 2. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED,
 INSTALLED, OR PROTECTED SO THEIR OPERATION WILL NOT BE
 AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM
 THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE PER THE NFPA 58-17 SEC. 6.10.1.4.
  
 4. LP-GAS CONTAINERS OR SYSTEMS INSTALLED WITHIN 10 FT
 OF PUBLIC VEHICULAR THOROUGHFARES SHALL BE PROVIDED
 WITH A MEANS OF VEHICULAR BARRIER PROTECTION PER THE
 2020 NFPA 58-17 SEC. 6.8.1.2.
  
 5. MANUFACTURES SPECIFICATION FOR THE FIRE PLEASE WERE
 NOT SUBMITTED AS STATED ON PCH-2 PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 6. HORIZONTAL ASME CONTAINERS DESIGNED FOR PERMANENT
 INSTALLATION IN STATIONARY ABOVEGROUND SERVICE SHALL BE
 PLACED ON MASONRY OR OTHER NONCOMBUSTIBLE STRUCTURAL
 SUPPORTS LOCATED ON CONCRETE OR MASONRY FOUNDATIONS
 WITH THE CONTAINER SUPPORTS PER THE NFPA 58-17 SEC.
 6.8.3.1
  
 7. ON SHEET PCH-1;
 A. IT SAYS 100 LBS; WOULD YOU PLEASE PROVIDE THE SIZE
 IN GALLONS AND THE MANUFACTURES SPECIFICATION PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. TABLE GIVEN IS FOR NATURAL GAS, AND IT HAS AN LP
 TANK ON THE ISOMETRIC. WOULD YOU PLEASE PROVIDE THE
 CORRECT TABLE PER THE NFPA 58-17?
  
 C. WOULD YOU PLEASE PROVIDE THE CODE REFERENCE EDITION
 OR NFPA USED PER THE WPB AMENDMENTS TO FBC 102.3
 APPLICATION OF REFERENCES.
  
 8. WOULD YOU PLEASE PROVE THE STRAP DOWN METHOD FOR THE
 TANK THAT SHALL BE SECURELY ANCHORED TO WITHSTAND 170
 MPH ULT WIND LOAD PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  