| 2021-08-12 17:26:19 | 07/23/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SHOW THE DISTANCE OF THE LP TANK FROM THE EXTERIOR |
| | WALL OF THE STRUCTURE TO THE CONTAINER SURFACE AND FROM |
| | THE PROPERTY LINE TO THE CONTAINER SURFACE TO COMPLY |
| | WITH NFPA 58-17 SEC. 6.4.1 & TABLE 6.4.1.1. |
| | |
| | 2. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED, |
| | INSTALLED, OR PROTECTED SO THEIR OPERATION WILL NOT BE |
| | AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM |
| | THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| | EXTERIOR USE PER THE NFPA 58-17 SEC. 6.10.1.4. |
| | |
| | 4. LP-GAS CONTAINERS OR SYSTEMS INSTALLED WITHIN 10 FT |
| | OF PUBLIC VEHICULAR THOROUGHFARES SHALL BE PROVIDED |
| | WITH A MEANS OF VEHICULAR BARRIER PROTECTION PER THE |
| | 2020 NFPA 58-17 SEC. 6.8.1.2. |
| | |
| | 5. MANUFACTURES SPECIFICATION FOR THE FIRE PLEASE WERE |
| | NOT SUBMITTED AS STATED ON PCH-2 PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 6. HORIZONTAL ASME CONTAINERS DESIGNED FOR PERMANENT |
| | INSTALLATION IN STATIONARY ABOVEGROUND SERVICE SHALL BE |
| | PLACED ON MASONRY OR OTHER NONCOMBUSTIBLE STRUCTURAL |
| | SUPPORTS LOCATED ON CONCRETE OR MASONRY FOUNDATIONS |
| | WITH THE CONTAINER SUPPORTS PER THE NFPA 58-17 SEC. |
| | 6.8.3.1 |
| | |
| | 7. ON SHEET PCH-1; |
| | A. IT SAYS 100 LBS; WOULD YOU PLEASE PROVIDE THE SIZE |
| | IN GALLONS AND THE MANUFACTURES SPECIFICATION PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. TABLE GIVEN IS FOR NATURAL GAS, AND IT HAS AN LP |
| | TANK ON THE ISOMETRIC. WOULD YOU PLEASE PROVIDE THE |
| | CORRECT TABLE PER THE NFPA 58-17? |
| | |
| | C. WOULD YOU PLEASE PROVIDE THE CODE REFERENCE EDITION |
| | OR NFPA USED PER THE WPB AMENDMENTS TO FBC 102.3 |
| | APPLICATION OF REFERENCES. |
| | |
| | 8. WOULD YOU PLEASE PROVE THE STRAP DOWN METHOD FOR THE |
| | TANK THAT SHALL BE SECURELY ANCHORED TO WITHSTAND 170 |
| | MPH ULT WIND LOAD PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |