| Plan Review Notes For Permit 21070374 |
| Permit Number |
21070374 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-13 11:55:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PROPOSED TRELLIS INSTALLATION APPEARS TO IMPACT | | | AND OBSTRUCTT THE EXISTING FIRE SPRINKLER PROTECTION | | | SYSTEM. | | | | | | A REVIEW BY A CERTIFIED FIRE SPRINKLER CONTRACTOR IS | | | REQUIRED. | | | | | | ANY WORK ON THE FIRE SPRINKLER SYSTEM, INCLUDING DEMO, | | | SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT. | | | | | | 1A) SHEET A 501 - WITHIN THE LEGEND DIAMOND NOTE # 9 | | | INDICATES THE EXISTING FIRE SPRINKLERS TO REMAIN. | | | | | | THE DIAMOND # 9 COULD NOT BE FROUND IN ANY OF THE | | | CALL-OUTS SECTIONS. | | | | | | THOUGH EXISTING SPRINKLERS MAY REMAIN ABOVE THE | | | TRELLIS, THEY ARE NOT IDENTIFIED CORRECTLY, AND | | | SPRINKLER PROTECTION MAY BE REQUIRED TO EXTEND UNDER | | | THE TRELLIS | | | | | | PLEASE REVIEW AND CORRECT AND ADDRESS # 1 ABOVE. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|