Plan Review Notes
Plan Review Notes For Permit 21070351
Permit Number 21070351
Review Stop B
Sequence Number 2
Notes
Date Text
2021-09-15 08:04:13CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) DRAWING A-2 - SHOWER WALL SHOWS PLYWOOD WHICH SHOULD
 BE SHOWN AS FIRE RETARDANT PLYWOOD PER FBC 603.1
 2) THE PROVIDED FLOORING ACOUSTICAL TEST REPORT IS FOR
 AN 8" CONCRETE SLAB - THE ORIGINAL DRAWINGS FOR THE
 BUILDING SHOW A 5.5" SLAB - PLEASE PROVIDE FLOORING
 ACOUSTICAL TEST REPORTS THAT HAVE A SIMILAR FLOOR
 CONCRETE SLAB THICKNESS.
 3) THE FLAME SPREAD TEST REPORT WILL NEED TO BE FOR A
 WOOD FLOOR SYSTEM OR THE UNDERLAYMENT ITSELF. (NOT A
 TILE SYSTEM)
  