Text |
| 2021-09-15 08:04:13 | CONDO REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | 1) DRAWING A-2 - SHOWER WALL SHOWS PLYWOOD WHICH SHOULD | | | BE SHOWN AS FIRE RETARDANT PLYWOOD PER FBC 603.1 | | | 2) THE PROVIDED FLOORING ACOUSTICAL TEST REPORT IS FOR | | | AN 8" CONCRETE SLAB - THE ORIGINAL DRAWINGS FOR THE | | | BUILDING SHOW A 5.5" SLAB - PLEASE PROVIDE FLOORING | | | ACOUSTICAL TEST REPORTS THAT HAVE A SIMILAR FLOOR | | | CONCRETE SLAB THICKNESS. | | | 3) THE FLAME SPREAD TEST REPORT WILL NEED TO BE FOR A | | | WOOD FLOOR SYSTEM OR THE UNDERLAYMENT ITSELF. (NOT A | | | TILE SYSTEM) | | | |
|