Plan Review Notes
Plan Review Notes For Permit 21070345
Permit Number 21070345
Review Stop B
Sequence Number 1
Notes
Date Text
2021-07-16 08:28:46REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) ENERGY CALCS. HAVE BEEN REVISED - YOU WILL NEED TO
 REVISE THE DRAWINGS TO SHOW THE CORRECT INSULATION TO
 MATCH THE ENERGY CALCS.
 2) ENERGY CALCS. SHOW R30 IN THE CEILING - R30 BAT
 INSULATION IN A 2 X 10 RAFTER WILL NOT ALLOW FOR THE
 REQUIRED 1 INCH VENTILATION GAP PER FBC R 806.3 VENT
 AND INSULATION CLEARANCE.
 WHERE EAVE OR CORNICE VENTS ARE INSTALLED, BLOCKING,
 BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW
 OF AIR. NOT LESS THAN A 1-INCH (25 MM) SPACE SHALL BE
 PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING
 AND AT THE LOCATION OF THE VENT.
  