| Date |
Text |
| 2021-07-21 12:57:11 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. SHEET S2 GIVES SPECIFICATION OF FBC 2017, GOVERNING | | | CODE IS FBC 2020, CHECK ALL CODE REFERENCES. | | | | | | 2. SEE S1, S5, IT APPEARS THAT THE ENGINEER IS | | | SPECIFYING A MINIMUM FOOTING, BUT PLANS STATE THAT THE | | | EXISTING FOOTING WILL BE USED. NO INFORMATION WAS | | | PROVIDED ABOUT THE EXISTING FOOTING. PROVIDE A DETAIL | | | FOR THE EXISTING FOOTING TO SHOW THAT IT MEETS THE | | | ENGINEER'S SPECIFICATION. REVISE PLAN TO CLARIFY THAT | | | THE EXISTING FOOTING WILL BE USED, IF THAT IS THE CASE. | | | | | | REVISE PLAN ACCORDINGLY. THIS INFORMATION IS INCLUDED | | | ON PAGE 001 COVERSHEET BUT THAT PAGE IS NOT SIGNED AND | | | SEALED, FS471. | | | | | | | | | | | | |
|