| 2022-05-16 08:01:42 | 3RD REVIEW FMC |
| | PERMIT: 21070278 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | IF USING AN ALTERNATE MEANS TO MEET THE OUTDOOR AIR |
| | REQUIREMENT PLEASE SUBMIT A COMPLETE DESIGN. FMC 403.2 |
| | OUTDOOR AIR REQUIRED. THE MINIMUM OUTDOOR AIRFLOW RATE |
| | SHALL BE DETERMINED IN ACCORDANCE WITH SECTION 403.3. |
| | |
| | EXCEPTION: WHERE THE REGISTERED DESIGN PROFESSIONAL |
| | DEMONSTRATES THAT AN ENGINEERED VENTILATION SYSTEM |
| | DESIGN WILL PREVENT THE MAXIMUM CONCENTRATION OF |
| | CONTAMINANTS FROM EXCEEDING THAT OBTAINABLE BY THE RATE |
| | OF OUTDOOR AIR VENTILATION DETERMINED IN ACCORDANCE |
| | WITH SECTION 403.3, THE MINIMUM REQUIRED RATE OF |
| | OUTDOOR AIR SHALL BE REDUCED IN ACCORDANCE WITH SUCH |
| | ENGINEERED SYSTEM DESIGN. |
| | |
| | 1) SHEET M-13: EACH CONTAMINANT OF CONCERN, FOR |
| | PURPOSES OF THE DESIGN, SHALL BE IDENTIFIED. FOR EACH |
| | CONTAMINANT OF CONCERN, INDOOR SOURCES AND OUTDOOR |
| | SOURCES SHALL BE IDENTIFIED, AND EMISSION RATE FOR EACH |
| | CONTAMINANT OF CONCERN FROM EACH SOURCE SHALL BE |
| | DETERMINED. PLEASE SHOW THIS INFORMATION IN THE CHART |
| | SUBMITTED. ASHRAE 62.1-2016 |
| | |
| | 2) SHEET M-13: THERE ARE SEVERAL DIFFERENT TUBE SIZES |
| | FOR THE MATTERHORN 1000, PLEASE IDENTIFY THE TUBE SIZE |
| | IN THE CHART FOR THIS DESIGN. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |