| 2021-08-16 17:30:15 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21070278 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1 PLEASE SHOW HOW YOU WILL SUPPLY OUTDOOR |
| | AIR TO THE AHU UNITS. |
| | |
| | 2) SHEET M-3: PLEASE SHOW THE OUT AIR CALCULATIONS FOR |
| | EACH USE OF SPACE IN THIS TENANT SPACE. PLEASE REMEMBER |
| | YOU MAY USE FOOTNOTE (A) (NET OCCUPIABLE FLOOR AREA) |
| | THE KITCHEN, OFFICE AND DINING/BAR ARE SHOWING SMALLER |
| | AMOUNTS OF OUTDOOR AIR THAN IS REQUIRED. FBC M |
| | 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 3) PLEASE SHOW THE ELEVATION OF THE CONDENSING UNITS. |
| | WPB ADMINISTRATIVE CODE 107.3.5.1.1 |
| | |
| | 4) SHEET M-3: PLEASE SHOW THAT THE OUTDOOR AIR FROM |
| | KSF-1 IS TEMPERED AIR OR MEETS FBC M 508.1.1 |
| | |
| | 5) SHEET M-1: PLEASE SHOW THAT THE CONDENSING UNITS ARE |
| | PROTECTED FROM DAMAGE. FBC M 303.4 |
| | |
| | 6) SHEET M-1: PLEASE SHOW THE CONDENSATION PIPING AND |
| | THE TERMINATION LOCATION FOR THE AHU?S. FBC M 307 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |