| Plan Review Notes For Permit 21070270 |
| Permit Number |
21070270 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-09 08:36:24 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL14645.2-R4 COVERS MULTIPLE FASTENER SPACING | | | TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT CORRECT | | | FASTENER SPACING FROM PAGE #2 OF THE INSTALLATION | | | INSTRUCTIONS THAT MEET OR EXCEED THE MINIMUM DESIGN | | | PRESSURE REQUIREMENT FOR EXPOSURE CATEGORY C AREAS. | | | (-108.17). ALL APPLICABLE DETAILS AND ATTACHMENTS MUST | | | BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. | | | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN | | | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING | | | |
|