| Plan Review Notes For Permit 21070232 |
| Permit Number |
21070232 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-08 11:11:18 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1 FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL5293-R45 SELECTED SYSTEM NO. W-7 DO NOT MEET | | | THE EXPOSURE CATEGORY C; ZONE 2 MINIMUM DESIGN PRESSURE | | | REQUIREMENT OF -79.38 OR ZONE 3 MINIMUM DESIGN PRESSURE | | | REQUIREMENT OF -108.17. PLEASE SELECT SYSTEM NO. THAT | | | MEETS OR EXCEEDS REQUIREMENTS. NO RATIONAL ANALYSIS IS | | | PERMITTED FOR THESE SYSTEMS AS PER LIMITATIONS: 5.7.3. | | | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY | | | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS | | | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT | | | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. | | | |
|