| Date |
Text |
| 2021-09-16 15:02:03 | 09/16/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET A1.0; |
| | A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE |
| | DRINKING FOUNTAIN AND BREAKROOM PER THE 2020 FBC ACC |
| | SEC. 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| | 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET? |
| | |
| | 2. ON SHEET A1.1, DETAIL A; |
| | |
| | A. THE TOILET GRAB BAR SAYS 6 INCHES FROM THE WALL, |
| | WHICH IS NOT AN ACTUAL NUMBER AS THE TOILET IS 16 |
| | INCHES TO 18 INCHES TO THE CENTER, AND THAT NUMBER MAY |
| | CONFUSE THE INSTALLER. WOULD YOU PLEASE CORRECT PER THE |
| | 2020 FBC ACC SEC. 604.2 LOCATION AND WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? REFER TO G1.2 F. |
| | |
| | B. WOULD YOU PLEASE LABEL THE RESTROOM PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | C. ON DETAIL 1, THE 5'-0" FOR THE TURNING RADIUS IS NOT |
| | THE RIGHT LOCATION FOR THE MEN'S RESTROOM. WOULD YOU |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | D. WATER CLOSET FLUSH CONTROL SHALL BE OPEN SIDE PER |
| | THE 2020 FBC ACC SEC. 604.9.5. |
| | |
| | E. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER |
| | 2020 FBC P 425.3 WATER CLOSET SEATS. |
| | |
| | F. WOULD YOU PLEASE PROVIDE ELEVATIONS FOR THE |
| | ACCESSIBLE KITCHEN SINK PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. ON SHEET G1.2 DETAIL C, IT SHOWS THE VALVE AT 44" |
| | HANDICAP CAP WATER CLOSET FLUSH CONTROL SHALL BE HAND |
| | OPERATED OR AUTOMATIC AND SHALL BE 36" INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR PER THE 2020 FBC ACC SEC. |
| | 604.9.5. IF YOU ARE USING TANK-TYPE WOULD YOU, PLEASE |
| | DELETE OR CORRECT DETAIL C PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4. ON SHEET P0.1; |
| | |
| | A. IN THE SANITARY ISOMETRIC, THE TOILETS IS NOT DO NOT |
| | MATCH THE LAYOUT ON PAGE P2.1. WOULD YOU PLEASE CORRECT |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. IN THE WATER ISOMETRIC, THE HOT WATER LINES LOOPED |
| | FOR THE RECIRCULATING SYSTEM ARE NOT IN A CONTINUOUS |
| | LOOP. THERE ARE REQUIREMENTS IN THE FLORIDA ENERGY CODE |
| | SEC. C404.6.1. |
| | |
| | C. IN THAT SAME DETAIL, A TABLE LIMITS THE DISTANCE |
| | BETWEEN THE SOURCE AND THE OUTLET. PLEASE REFER TO |
| | TABLE 405.5.1 FOR THE MAXIMUM ALLOWABLE PIPE LENGTH |
| | METHOD AND SIZE ACCORDANTLY. |
| | |
| | D. THE RECALCULATING PER MANUFACTURES SPECIFICATION AND |
| | MAINTENANCE MAY REQUIRE SHUT-OFF VALVES ON EACH SIDE OF |
| | THE RECALCULATING PUMP PER THE 2020 FBC SEC. 606.2 |
| | LOCATION OF SHUTOFF VALVES. |
| | |
| | F. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125 PER THE 2020 FBC P |
| | 419.5 WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| | |
| | 5. ON SHEET P2.1; |
| | |
| | A. THE CONDENSATE LINE SAYS IT IS DRAINING INTO THE |
| | ROOF DRAIN, AND THIS IS NOT PERMITTED TO DISCHARGE INTO |
| | THE CITY'S STORM SYSTEM PER CITY ORDINANCE CHAPTER 90, |
| | ARTICLE III, SEC.90-126 (B)(5). WOULD YOU PLEASE |
| | PROVIDE AN ALTERNATIVE SOURCE? |
| | |
| | PLEASE FEEL FREE TO CONTACT ME ON ANY OF THE COMMENTS |
| | BY PHONE OR ZOOM MEETING IF YOU LIKE. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-672 |
| | |