Plan Review Notes
Plan Review Notes For Permit 21070222
Permit Number 21070222
Review Stop P
Sequence Number 1
Notes
Date Text
2021-09-16 15:02:0309/16/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A1.0;
 A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 DRINKING FOUNTAIN AND BREAKROOM PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
 2. ON SHEET A1.1, DETAIL A;
  
 A. THE TOILET GRAB BAR SAYS 6 INCHES FROM THE WALL,
 WHICH IS NOT AN ACTUAL NUMBER AS THE TOILET IS 16
 INCHES TO 18 INCHES TO THE CENTER, AND THAT NUMBER MAY
 CONFUSE THE INSTALLER. WOULD YOU PLEASE CORRECT PER THE
 2020 FBC ACC SEC. 604.2 LOCATION AND WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS? REFER TO G1.2 F.
  
 B. WOULD YOU PLEASE LABEL THE RESTROOM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. ON DETAIL 1, THE 5'-0" FOR THE TURNING RADIUS IS NOT
 THE RIGHT LOCATION FOR THE MEN'S RESTROOM. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. WATER CLOSET FLUSH CONTROL SHALL BE OPEN SIDE PER
 THE 2020 FBC ACC SEC. 604.9.5.
  
 E. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS.
  
 F. WOULD YOU PLEASE PROVIDE ELEVATIONS FOR THE
 ACCESSIBLE KITCHEN SINK PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. ON SHEET G1.2 DETAIL C, IT SHOWS THE VALVE AT 44"
 HANDICAP CAP WATER CLOSET FLUSH CONTROL SHALL BE HAND
 OPERATED OR AUTOMATIC AND SHALL BE 36" INCHES MAXIMUM
 ABOVE THE FINISH FLOOR PER THE 2020 FBC ACC SEC.
 604.9.5. IF YOU ARE USING TANK-TYPE WOULD YOU, PLEASE
 DELETE OR CORRECT DETAIL C PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. ON SHEET P0.1;
  
 A. IN THE SANITARY ISOMETRIC, THE TOILETS IS NOT DO NOT
 MATCH THE LAYOUT ON PAGE P2.1. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. IN THE WATER ISOMETRIC, THE HOT WATER LINES LOOPED
 FOR THE RECIRCULATING SYSTEM ARE NOT IN A CONTINUOUS
 LOOP. THERE ARE REQUIREMENTS IN THE FLORIDA ENERGY CODE
 SEC. C404.6.1.
  
 C. IN THAT SAME DETAIL, A TABLE LIMITS THE DISTANCE
 BETWEEN THE SOURCE AND THE OUTLET. PLEASE REFER TO
 TABLE 405.5.1 FOR THE MAXIMUM ALLOWABLE PIPE LENGTH
 METHOD AND SIZE ACCORDANTLY.
  
 D. THE RECALCULATING PER MANUFACTURES SPECIFICATION AND
 MAINTENANCE MAY REQUIRE SHUT-OFF VALVES ON EACH SIDE OF
 THE RECALCULATING PUMP PER THE 2020 FBC SEC. 606.2
 LOCATION OF SHUTOFF VALVES.
  
 F. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125 PER THE 2020 FBC P
 419.5 WATER FOR PUBLIC HAND-WASHING FACILITIES.
  
 5. ON SHEET P2.1;
  
 A. THE CONDENSATE LINE SAYS IT IS DRAINING INTO THE
 ROOF DRAIN, AND THIS IS NOT PERMITTED TO DISCHARGE INTO
 THE CITY'S STORM SYSTEM PER CITY ORDINANCE CHAPTER 90,
 ARTICLE III, SEC.90-126 (B)(5). WOULD YOU PLEASE
 PROVIDE AN ALTERNATIVE SOURCE?
  
 PLEASE FEEL FREE TO CONTACT ME ON ANY OF THE COMMENTS
 BY PHONE OR ZOOM MEETING IF YOU LIKE.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-672
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved