Plan Review Notes
Plan Review Notes For Permit 21070216
Permit Number 21070216
Review Stop B
Sequence Number 1
Notes
Date Text
2021-07-14 17:14:49PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTE: ASTM TEST REPORTS ARE REQUIRED - MANUFACTURER
 SPEC SHEETS ARE NOT ACCEPTABLE DUE TO DISCREPANCIES
 BETWEEN SPEC SHEETS/BROCHURES AND TEST REPORTS FOR SOME
 MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER
 SELECTED; THIS IS A GENERAL COMMENT)
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR ALL FLOORING
 SUBMITTALS PER FBC CHPT. 12 AND CHPT. 6:
  
 1. TOTAL SQUARE FOOTAGE OF NEW FLOORING. - 447SF
 2. TYPE OF PROPOSED FLOORING
 (TILE/MARBLE/LAMINATE/WOOD/OTHER). ENGINEERED WOOD
 LAMINATE
 3. STATED VALUE OF WORK.- $6,383.00
 4. EXISTING SITE CONDITIONS: SEE BELOW
 4A) THICKNESS OF SLAB.
 4B) CEILING ASSEMBLY (OPEN CONCRETE/SUSPENDED
 GYPSUM/ACOUSTICAL)
 5. PROPOSED UNDERLAYMENT. PROFLEX RCU-250
 6. TEST REPORTS FOR PROPOSED UNDERLAYMENT BASED ON
 EXISTING SITE CONDITIONS.
 7. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S,
 E-84, E-90 & E-492.
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE
 AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45
 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E
 492.
  
 FBC 603.1 FLAME SPREAD SEC 803.1.1, PROVIDE TEST DATA
 IN ACCORDANCE WITH ASTM E 84 OR UL 723
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723
 FBC 804.4.1 TEST REQUIREMENT.
  
 NOTICE: WE KEEP A LIBRARY OF THE POPULAR UNDERLAYMENTS
 AND ARE HAPPY TO UPLOAD THEM TO AN APPLICANTS
 SUBMITTAL. UNFORTUNETLY, WE DO NOT HAVE ANY TEST
 REPORTS FOR RCU-250 AS AN UNDERLAYMENT FOR ENGINEERED
 WOOD LAMINATE.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  