Plan Review Notes
Plan Review Notes For Permit 21070167
Permit Number 21070167
Review Stop P
Sequence Number 3
Notes
Date Text
2021-10-14 12:25:123RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21070167
 10/13/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIE.
  
 1) SHEET GN100: THE REVISED PLAN SHEET NOW ESTABLISHES
 THE BASIS OF DESIGN FOR THE ACCESSIBLE DWELLING UNITS
 IS THE 2009 ICC/ANSI A117 ACCESSIBLE AND USABLE
 BUILDINGS AND FACILITIES STANDARD. TYPE A UNITS ARE
 SPECIFIED. PLEASE REVIEW SHEETS GN102, GN103, A805 &
 A806 AND PROVIDE THE FOLLOWING MISSSING DETAILS PER THE
 STANDARD:
  
 A) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 1003.11.7.4.
 B) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTIONS & FIGS. 604.5.1,
 604.5.2. PLEASE CORRECT REAR GRAB BARS ON SHEETS GN102
 & GN103 AND PROVIDE COMPLETE DETAILS ON SHEETS A805 &
 A806.
 C) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTIONS 1003.11.5 & 606.3.
 D) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 1003.11.6. THE DETAIL
 DOES NOT INDICATE REFLECTIVE SURFACE.
 E) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ?
 SECTION 1003.11.7.5.
 F) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.10.7.
 G) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTIONS
 606.2, 306.2, 306.3 AND FIG. 306.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECTION & FIG. 608.3.2.
 TO HELP EXPEDITE REVIEW AND INSPECTION OF THE GRAB
 BARS, PLEASE PROVIDE CONSISTENT LENGTH AND SPACING
 MEASUREMENTS ON THE PLANS AND INDICATE THE HEIGHT
 MEASUREMENTS ARE TO THE TOPS OF THE GRIPPING SURFACES.
 I) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION AND FIG. 608.5.2. THE ELEVATION
 DRAWINGS SHOW ONE CONTROL VALVE ABOVE THE 48-INCH
 MAXIMUM HEIGHT.
  
 2) GN100, A102: THE PLANS INDICATE HVI UNITS WILL BE
 INSTALLED ON THE 2ND-5TH FLOORS. PLEASE INDICATE WHICH
 CODE OR STANDARD IS THE BASIS OF DESIGN FOR THESE UNITS
 AND PROVIDE COMPLIANCE DRAWINGS AND DETAILS- SECTION
 107.2.1 WPB.
  
 3) D101B, D201.B: THE SHEETS ARE IN CONFLICT REGARDING
 THE TOILET COMPARTMENTS. IT APPEARS D201B NEEDS TO BE
 CORRECTED.
  
 4) SHEETS A102, A103, A104, A105: TO HELP EXPEDITE PLAN
 REVIEW, CONSTRUCTION, AND INSPECTION OF THE RENOVATED
 DWELLING UNITS, PLEASE PROVIDE REFERENCE NOTES OR
 TARGETS INDICATING ON WHICH SHEETS THE ENLARGED FLOOR
 PLANS ARE LOCATED- SECTION 107.2.1 WPB.
  
 5) SHEETS A101A & A814: THE KNEE AND TOE CLEARANCES FOR
 THE LOUNGE SINK SHALL BE IN COMPLIANCE WITH SECTIONS
 606.2, 306.2, & 306.3 FBC ACC.
  
 6) A101, A101B, A825: MISSING ACCESSIBILITY DETAIL PER
 THE FBC ACC:
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 B) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 C) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 E) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2, 306.2, & 306.3 FBC ACC.
 F) HEIGHT AND DEPTH OF THE URINAL- SECTION 605.2.
 G) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 URINAL- SECTION 605.3
 H) PLEASE PROVIDE THE DIMENSIONS OF THE EXISTING TOILET
 COMPARTMENTS TO VERIFY COMPLIANCE WITH SECTION 604.8.1.
 I) PLEASE NOTE THAT ACCESSIBLE TOILET COMPARTMENT DOORS
 SHALL NOT SWING INTO THE MINIMUM REQUIRED COMPARTMENT
 AREA, DOORS SHALL BE SELF-CLOSING, AND PULLS PROVIDED
 ON BOTH SIDES- 604.8.1.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE