| 2021-09-23 13:03:07 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21070167 |
| | 9/23/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES FOR |
| | FURTHER CLARIFICATION. |
| | |
| | 2) FAILED. GN100: PLEASE PROVIDE A LIST OF DWELLING |
| | UNITS, THE UNIT FLOOR LEVELS, AND COMMON AREAS THAT |
| | WILL BE ALTERED AND IMPROVED IN ACCORDANCE WITH THE |
| | CHOSEN ACCESSIBILITY STANDARD. INDICATE WHICH |
| | ADMINISTRATIVE AUTHORITY HAS DETERMINED THE TYPE A |
| | DESIGN TO BE USED AND THE NUMBER OF DWELLING UNITS TO |
| | BE REMODELED. PLEASE CLARIFY HOW THE 5% NUMBER OF UNITS |
| | TO BE CONVERTED TO TYPE A WAS DETERMINED-UNDER WHICH |
| | ADMISINSTRATIVE AUTHORITY- SECTION 201 2009 ICC/ANSI |
| | A117. |
| | |
| | 4) FAILED. GN102 & A805- 2009 ICC/ANSI A117: THE |
| | REVISED SHEET INDICATES ADA TYPE 5 DESIGN. FOR |
| | CLARIFICATION PLEASE INDICATE TYPE A OR B, 1BEDROOM OR |
| | EFFICIENCY FOR ALL FLOOR PLAN DRAWINGS A802- A806. |
| | PLEASE NOTE THERE IS NO CORRELATIING SCHEDULE FOR |
| | NUMBERED TYPE UNITS 2-6- SECTION 107.2.1 WPB. |
| | |
| | E) FAILED. THE CONTROLS AND HAND SHOWER SHALL BE |
| | LOCATED ON THE BACK WALL OF THE SHOWER ABOVE THE GRAB |
| | BAR, 48 INCHES MAXIMUM ABOVE THE SHOWER FLOOR AND 16 |
| | INCHES MINIMUM AND 27 INCHES MAXIMUM FROM THE END WALL |
| | BEHIND THE SET- SECTION AND FIGURE 608.4.2. THE |
| | ELEVATION 5 DETAIL ON A805 SHOWS CONTROLS AT (5FT. |
| | 10-5/8-INCHES) HOWEVER MAXIMUM ALLOWED IS 48 INCHES. |
| | |
| | F) FAILED. THE HORIZONTAL GRAB BARS SHALL BE INSTALLED |
| | 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE |
| | FINISHED BATHROOM FLOOR AND SHOWER FLOOR TO THE TOPS OF |
| | THE GRIPPING SURFACES- 609.4. DETAILS 5 & 6 ON A805- |
| | THE MEASUREMENT IS SHOWN TO THE CENTER OF THE GRAB |
| | BARS. |
| | |
| | H) FAILED. PROVIDE DETAILS FOR THE KITCHEN SINK REMOVAL |
| | CABINET INDICATING COMPLIANCE WITH SECTION 1003.12.4.1 |
| | ITEMS 1 & 2 (A, B, & C). SHEET GN101: SEE FIGURES |
| | C606.2(A), C306.1(B), & C306.1 (C) AND CORRECT DETAIL |
| | 20 TO THE MIN. 17 INCH AND MAX 25-INCH KNEE AND TOE |
| | CLEARANCE DIMENSIONS. PLEASE PLACE THE DIMENSIONS IN |
| | THE CORRECT LOCATION BELOW THE SINK. |
| | |
| | NEW COMMENT: INDICATE THE HEIGHTS OF THE MIRROR ARE |
| | FROM THE FINISHED FLOORS TO THE REFLECTIVE SURFACE- |
| | SECTION 603.3. |
| | |
| | 5) FAILED. GN103 & A806: 2009 ICC/ANSI A117: THE |
| | REVISED SHEET INDICATES ADA TYPE 6 DESIGN. FOR |
| | CLARIFICATION PLEASE INDICATE TYPE A OR B, 1BEDROOM OR |
| | EFFICIENCY FOR ALL FLOOR PLAN DRAWINGS A802- A806. |
| | PLEASE NOTE THERE IS NO CORRELATIING SCHEDULE FOR |
| | NUMBERED TYPE UNITS 2-6- SECTION 107.2.1 WPB. |
| | |
| | E) FAILED. THE CONTROLS AND HAND SHOWER SHALL BE |
| | LOCATED ON THE BACK WALL OF THE SHOWER ABOVE THE GRAB |
| | BAR, 48 INCHES MAXIMUM ABOVE THE SHOWER FLOOR AND 16 |
| | INCHES MINIMUM AND 27 INCHES MAXIMUM FROM THE END WALL |
| | BEHIND THE SET- SECTION AND FIGURE 608.4.2. THE |
| | ELEVATION 5 DETAIL ON A806 SHOWS CONTROLS AT (5FT. |
| | 10-5/8-INCHES) HOWEVER MAXIMUM ALLOWED IS 48 INCHES |
| | |
| | F) FAILED. THE HORIZONTAL GRAB BARS SHALL BE INSTALLED |
| | 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE |
| | FINISHED BATHROOM FLOOR AND SHOWER FLOOR TO THE TOPS OF |
| | THE GRIPPING SURFACES- 609.4. DETAILS 5 & 6 ON A806- |
| | THE MEASUREMENT IS SHOWN TO THE CENTER OF THE GRAB |
| | BARS. |
| | |
| | H) FAILED. PROVIDE DETAILS FOR THE KITCHEN SINK REMOVAL |
| | CABINET INDICATING COMPLIANCE WITH SECTION 1003.12.4.1 |
| | ITEMS 1 & 2 (A, B, & C). SHEET GN101: SEE FIGURES |
| | C606.2(A), C306.1(B), & C306.1 (C) AND CORRECT DETAIL |
| | 20 TO THE MIN. 17 INCH AND MAX 25-INCH KNEE AND TOE |
| | CLEARANCE DIMENSIONS. PLEASE PLACE THE DIMENSIONS IN |
| | THE CORRECT LOCATION BELOW THE SINK. PLEASE NOTE THE |
| | ARCHIITECT?S RESPONSE TO THIS COMMENTS REFERS TO SHEETS |
| | A902 & A903 WHICH HAVE NOT INCLUDED IN THE PLAN SETS. |
| | |
| | NEW COMMENT: INDICATE THE HEIGHTS OF THE MIRROR ARE |
| | FROM THE FINISHED FLOORS TO THE REFLECTIVE SURFACE- |
| | SECTION 603.3. |
| | |
| | 7) FAILED. A101.B: PROVIDE ENLARGED MEN'S AND WOMEN'S |
| | BATHROOM DRAWINGS INDICATING PLUMBING FIXTURE |
| | INSTALLATION COMPLIANCE WITH THE FBC ACCESSIBILITY |
| | CODE- 2020. BASED ON THE PLANS IT APPEARS THESE |
| | BATHROOMS ARE FOR BOTH PRIVATE AND PUBLIC USE. PLEASE |
| | SEE SECTION 213.3 AND PROVIDE DRAWINGS AND DETAILS IN |
| | COMPLIANCE WITH THE FBC ACC. PLEASE ADD CODE DATA TO |
| | SHEET A101, A101A, A1018- FBC ACCESSIBILITY- 2020 7TH |
| | EDITION. THE PLANS ARE INDICATING NON-COMPLIANCE FOR |
| | THE MEN'S AND WOMEN'S TOILET COMPARTMENTS WHICH ARE |
| | EACH REQUIRED TO CONTAIN AN ACCESSIBLE LAVATORY- |
| | SECTION 213.3.1, 604.8.1, & 604.8.6 FBC ACC. THE PLANS |
| | SHOW DEMOLITION OF THE EXISTING COMPARTMENTS WHICH |
| | INDICATES NEW CONSTRUCTION COMPARTMENTS CAN BE |
| | CONSTRUCTED AT THIS TIME TO MEET THE CODE. PLEASE REFER |
| | TO SECTION 202.3 FBC ACC FOR ADDITIONAL ADVISORY |
| | INFORMATION. PLEASE ALSO PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS FOR THE GROUND FLOOR BASED ON TABLE 403.1 |
| | FBC P. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED |
| | AND PROVIDED NUMBER OF FIXTURES. |
| | |
| | A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | THE WATER CLOSETS- SECTION 604.3. PENDING PLAN |
| | CORRECTIONS. |
| | |
| | B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | THE LAVATORIES- SECTION 606.2. PENDING PLAN |
| | CORRECTIONS. |
| | |
| | C) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3. |
| | SHEET A825- NOT PROVIDED IN COMPARTMENTS. |
| | |
| | D) FAILED. CENTERLINES OF THE WATER CLOSETS FROM THE |
| | SIDE WALLS- SECTION 604.2. SHEET A825- NOT PROVIDED. |
| | |
| | E) NEW COMMENT- REFER TO SECTION 604.8.1.2 FBC ACC AND |
| | VERIFY THE TOILET COMPARTMENT DOORS WILL BE SELF |
| | CLOSING. |
| | |
| | F) NEW COMMENT- THE DOOR FOR THE MEN?S TOILET |
| | COMPARTMENT SHALL NOT SWING INTO THE CLEAR FLOOR SPACE |
| | REQUIRED FOR THE ACCESSIBLE URINAL- SECTION 603.2.3 FBC |
| | ACC. |
| | |
| | 12) FAILED. P301: PROVIDE UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAILS FOR PIPE PENETRATIONS ON |
| | THE PLAN- SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC |
| | B. THE DETAIL PROVIDED DOES NOT MEET COMPLIANCE. THE |
| | DETAIL IS NOT A UL ASSEMBLY. THE ASSEMBLY MAY BE |
| | DEFERRED AND INCLUDED IN A LIST OF DEFERRED SUBMITTALS |
| | ON THE PLAN- SECTION 107.3.4.1 WPB. |
| | |
| | 13) FAILED. P401: PROVIDE CAST IRON PIPE AND FITTING |
| | SPECIFICATIONS IN COMPLIANCE WITH SECTION 303.5 P. |
| | |
| | CAST-IRON SOIL PIPES AND FITTINGS, AND THE COUPLINGS |
| | USED TO JOIN THESE PRODUCTS TOGETHER, SHALL BE |
| | THIRD-PARTY LISTED AND LABELED. THIRD-PARTY CERTIFIERS |
| | OR INSPECTORS SHALL COMPLY WITH THE MINIMUM INSPECTION |
| | REQUIREMENTS OF ANNEX A OR ANNEX A1 OF THE ASTM AND |
| | CISPI PRODUCT STANDARDS INDICATED IN THE CODE FOR SUCH |
| | PRODUCTS. NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |