| Date |
Text |
| 2021-09-23 13:58:00 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21070167 |
| | 8/3/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAPS FOR FURTHER CLARIFICATIONE |
| | |
| | 1) FAILED. P201: PLEASE INCLUDE THE WATER HEATER |
| | EFFICIENCY RATINGS IN THE SCHEDULE- TABLE C404.1 FBC |
| | EC. NOT PROVIDED. RATINGS CAN BE DEFERRED AND VERIFIED |
| | WITH PRODUCT SUBMITTAL- SEE COMMENT #2 BELOW. |
| | |
| | 2) FAILED. P201: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | AND INSTALLATION MANUAL FOR THE NEW WATER HEATERS- |
| | SECTION 624.1 FBC FG. NOT PROVIDED. THE SPECIFICATIONS |
| | AND MANUAL MAY BE DEFERRED AND INCLUDED IN A LIST OF |
| | DEFERRED SUBMITTALS ON THE PLAN- SECTION 107.3.4.1 WPB. |
| | |
| | 2) FAILED. P106: PROVIDE A GAS PIPING PLAN AND RISER |
| | DRAWING SHOWING COMPLIANCE WITH THE FBC FG AND SECTION |
| | 107.3.5.15 WPB. |
| | |
| | B) FAILED. TYPE OF GAS- NATURAL OR LP AND SYSTEM |
| | PRESSURE. TYPE OF GAS NOT PROVIDED. |
| | |
| | C) FAILED. TOTAL BTU LOAD AND WATER HEATER BTU LOADS. |
| | LOADS NOT PROVIDED. |
| | |
| | D) FAILED. TYPES AND SIZES OF GAS PIPING. TYPE OF |
| | PIPING NOT PROVIDED. |
| | |
| | G) FAILED. LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND |
| | PIPE UNIONS. PIPE UNIONS NOT PROVIDED. PLEASE INDICATE |
| | THE SELECTED MAKE AND MODEL NUMBER OF THE REGULATORS, |
| | AND SUBMIT MARKED UP OR HIGHLIGHTED SPECS SHOWING THE |
| | SELECTED MODEL, THE INPUT AND OUTPUT PIPE SIZES AND |
| | PRESSURES- SECTION 410.2 FBC FG. PROVIDE A REGULATOR |
| | AND RELIEF VALVE VENTING PLAN AND DIAGRAM IN ACCORDANCE |
| | WITH SECTION 5.3- 5.3.2.1 NFPA 37, UNLESS THE SPECS |
| | SHOW COMPLIANCE WITH SECTION 5.3.1.2 (ITEMS 1-4). |
| | |
| | I) FAILED. PIPE SIZING TABLES FOR ALL NEW PIPING |
| | INSTALLATIONS. NOT PROVIDED. |
| | |
| | 3) FAILED. INDICATE HOW COMBUSTION AIR IS BEING |
| | PROVIDED TO THE WATER HEATERS AND PROVIDE CALCULATIONS- |
| | SECTION 304.1 FBC FG. NOT PROVIDED ON PLAN. THE |
| | NARRATIVE FROM THE ENGINEER PROVIDES INFORMATION THAT |
| | MUST BE PLACED ON THE PLAN. REFERENCE IS ALSO MADE TO |
| | THE WH MANUAL WHICH HAS NOT BEEN PROVIDED. AS |
| | PREVIOUSLY NOTE THE SPECS AND MANUAL MAY BE DEFERRED. |
| | PLEASE REFER TO SECTION 304.6.2 FBC FG FOR COMBUSTION |
| | AIR OPENING REQUIRMENTS AND PROVIDE INFORMATION AND/OR |
| | DETAILS ON THE PLAN. |
| | |
| | 4) FAILED. PROVIDE A VENTING DIAGRAM IN COMPLIANCE WITH |
| | SECTION 624.1 AND 503.3.2 FBC FG. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE VENT. THE ENGINEER'S NARRATIVE |
| | REFRENCES THE MANUAL WHICH HAS NOT BEEN SUBMITTED. |
| | PLEASE REFER TO SECTION 502.1 FBC FG AND INDICATE THE |
| | TYPE OF VENTING SYSTEM TO BE INSTALLED BASED ON THE |
| | CATEGORY OF THE WATER HEATERS- I, II, II, OR IV. |
| | PROVIDE A COMPLETE VENTING PLAN INDICATING THE TYPE OF |
| | MATERIAL, VENT RUN LENGTHS AND TERMINATION LOCATIONS-, |
| | 502, AND 503 FBC FG. PLEASE INCLUDE VENTING HANGING AND |
| | SUPPORT DETAILS- SECTION 503.6.11. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |