2021-09-23 13:58:002ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21070167
 8/3/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAPS FOR FURTHER CLARIFICATIONE
  
 1) FAILED. P201: PLEASE INCLUDE THE WATER HEATER
 EFFICIENCY RATINGS IN THE SCHEDULE- TABLE C404.1 FBC
 EC. NOT PROVIDED. RATINGS CAN BE DEFERRED AND VERIFIED
 WITH PRODUCT SUBMITTAL- SEE COMMENT #2 BELOW.
  
 2) FAILED. P201: SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION MANUAL FOR THE NEW WATER HEATERS-
 SECTION 624.1 FBC FG. NOT PROVIDED. THE SPECIFICATIONS
 AND MANUAL MAY BE DEFERRED AND INCLUDED IN A LIST OF
 DEFERRED SUBMITTALS ON THE PLAN- SECTION 107.3.4.1 WPB.
  
 2) FAILED. P106: PROVIDE A GAS PIPING PLAN AND RISER
 DRAWING SHOWING COMPLIANCE WITH THE FBC FG AND SECTION
 107.3.5.15 WPB.
  
 B) FAILED. TYPE OF GAS- NATURAL OR LP AND SYSTEM
 PRESSURE. TYPE OF GAS NOT PROVIDED.
  
 C) FAILED. TOTAL BTU LOAD AND WATER HEATER BTU LOADS.
 LOADS NOT PROVIDED.
  
 D) FAILED. TYPES AND SIZES OF GAS PIPING. TYPE OF
 PIPING NOT PROVIDED.
  
 G) FAILED. LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND
 PIPE UNIONS. PIPE UNIONS NOT PROVIDED. PLEASE INDICATE
 THE SELECTED MAKE AND MODEL NUMBER OF THE REGULATORS,
 AND SUBMIT MARKED UP OR HIGHLIGHTED SPECS SHOWING THE
 SELECTED MODEL, THE INPUT AND OUTPUT PIPE SIZES AND
 PRESSURES- SECTION 410.2 FBC FG. PROVIDE A REGULATOR
 AND RELIEF VALVE VENTING PLAN AND DIAGRAM IN ACCORDANCE
 WITH SECTION 5.3- 5.3.2.1 NFPA 37, UNLESS THE SPECS
 SHOW COMPLIANCE WITH SECTION 5.3.1.2 (ITEMS 1-4).
  
 I) FAILED. PIPE SIZING TABLES FOR ALL NEW PIPING
 INSTALLATIONS. NOT PROVIDED.
  
 3) FAILED. INDICATE HOW COMBUSTION AIR IS BEING
 PROVIDED TO THE WATER HEATERS AND PROVIDE CALCULATIONS-
 SECTION 304.1 FBC FG. NOT PROVIDED ON PLAN. THE
 NARRATIVE FROM THE ENGINEER PROVIDES INFORMATION THAT
 MUST BE PLACED ON THE PLAN. REFERENCE IS ALSO MADE TO
 THE WH MANUAL WHICH HAS NOT BEEN PROVIDED. AS
 PREVIOUSLY NOTE THE SPECS AND MANUAL MAY BE DEFERRED.
 PLEASE REFER TO SECTION 304.6.2 FBC FG FOR COMBUSTION
 AIR OPENING REQUIRMENTS AND PROVIDE INFORMATION AND/OR
 DETAILS ON THE PLAN.
  
 4) FAILED. PROVIDE A VENTING DIAGRAM IN COMPLIANCE WITH
 SECTION 624.1 AND 503.3.2 FBC FG. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VENT. THE ENGINEER'S NARRATIVE
 REFRENCES THE MANUAL WHICH HAS NOT BEEN SUBMITTED.
 PLEASE REFER TO SECTION 502.1 FBC FG AND INDICATE THE
 TYPE OF VENTING SYSTEM TO BE INSTALLED BASED ON THE
 CATEGORY OF THE WATER HEATERS- I, II, II, OR IV.
 PROVIDE A COMPLETE VENTING PLAN INDICATING THE TYPE OF
 MATERIAL, VENT RUN LENGTHS AND TERMINATION LOCATIONS-,
 502, AND 503 FBC FG. PLEASE INCLUDE VENTING HANGING AND
 SUPPORT DETAILS- SECTION 503.6.11.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER