Plan Review Notes
Plan Review Notes For Permit 21070167
Permit Number 21070167
Review Stop B
Sequence Number 2
Notes
Date Text
2021-09-13 09:47:46****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 803.11, PLEASE SHOW THE REQUIRED FIRE
 CLASSIFICATION FOR THE WALL AND CEILING FINISHES. PLAN
 SHEET A800.A. GENERAL NOTES REFER TO (IBC) CODE
 SECTIONS. THE REQUIRED FIRE CLASSIFICATION NEEDS TO BE
 ON THE FINISH SCHEDULES FOR WALL AND CEILING AREAS.
 2) FBC B 1004.4, PLEASE SHOW, UNDER DESIGN OCCUPANT
 LOAD ON PLAN SHEET GN100, THE OCCUPANT LOAD FOR THE
 1STFLOOR COMMUNITY ROOM.
 3) DOUBLE DOOR SWING POSITON IN COMMUNITY ROOM. OK
 4) FBC B 107.2.1, PLEASE ADD NOTE, UNDER SCOPE OF WORK
 ON PLAN SHEET GN100, NO FLOORING WILL BE REPLACED AND
 REMOVE THE FLOORING TILE SECTIONS FROM TILE SCHEDULE ON
 SHEET A800.A OR PROVIDE ON PLAN THE UNDERLAYMENT THAT
 WILL BE USED FOR FLOORING REPLACEMENTINCLUDING THE TEST
 REPORTS FOR SOUND AND FLAMESPREAD IN ACCORDANCE WITH
 FBC B 1207.2, 1207.3, & 603.1.
 5) OK, AS DEFERRED SUBMITTAL HAS BEEN INDICATED ON
 PLAN.
 6) FBC B 107.2.1, PLEASE PROVIDE THE, DESIGNER OF
 RECORD REVIEW STAMP APPROVED, PRODUCT APPROVALS FOR THE
 NEW EXTERIOR WINDOWS, DOORS, LOUVERS, AND ROOFING
 SYSTEMS & MATERIALS.
 7) NOTE: ALL SHOP DRAWINGS AND PRODUCT APPROVALS MUST
 BE REVIEW/APPROVED BY DESIGNER OF RECORD (ACKNOWLEDGED
 ON RESPONSE SHEET).
 8) OK, THE CONSTRUCTION TYPE HAS BEEN ADDED TO PLAN
 SHEET GN100.
 9) NOTE: WPB/FBC B 107.3.4.1, DEFERRED SUBMITTAL
 REQUIREMENTS HAVE BEEN ACKNOWLEDGED BY ENGINEER JEREMY
 M. CASE P.E.
  